Laserfiche WebLink
• • N ` <br /> Mr. Ruben Sanchez <br /> City of Everett <br /> Plan Check Number: B1812-022, Second Building Review <br /> March 19, 2019 <br /> Architectural <br /> General: <br /> 1. This comment has not been addressed. The original comment stated that the proposed <br /> project shall comply with the IEBC, and that the statement clarify the types of work included <br /> in the project. The response states that the work constitutes repairs per Chapter 6. <br /> However, the project involves the complete replacement of the moisture barrier at the top <br /> deck, and therefore constitutes Level 2 Alternations (Chapter 8) or at a minimum Level 1 <br /> Alternations (Chapter 7). The General Note"G"on Sheet A1.11 shall specify either Level 1 <br /> or Level 2 Alternations as the governing criteria. See IBC Sections 301.1 and 504.1. <br /> 2. This comment has not been addressed. The parking layout must be consistent with current <br /> City of Everett Standards (Drawing #340), including, but not limited to, parking aisle widths <br /> and parking stall dimensions. It appears that multiple dimensions on Detail E4/A1.11 may <br /> not satisfy this standard. Notably,the space and loading aisle widths for the accessible spaces <br /> are less than required. The response states that the City of Everett has approved striping <br /> that does not meet the standard, which is not acceptable. All new striping shall conform to <br /> Drawing #340. The detail shall be revised. See IBC Section 107.2.1. <br /> Accessibility: <br /> 3. This comment has not been addressed. The original comment is provided below. The <br /> response states that one van accessible space is provided at the"lower street level". Note <br /> that this space must be located within the structure to count towards the van-accessible <br /> requirement; spaces located in the street right-of way do not qualify. In addition, the <br /> existing space shall meet current dimensional requirements or shall be improved to meet <br /> the current standards. In addition, a minimum of two van-accessible spaces are required <br /> per IBC Section 106.5 based on the minimum 9 accessible spaces required. The minimum <br /> number of spaces required by IBC Sections 1106.4 and 1106.5 shall be provided regardless <br /> of the exceptions in IEBC Section 705.2 due to the required restriping. Note that accessible <br /> improvements are not limited to providing van accessible spaces. Other accessible spaces <br /> shall be improved to meet current requirements, or other inaccessible features shall be <br /> improved, as required by IEBC Section 705.2. Improvements may include, but are not <br /> limited to, restriping of other accessible spaces and adding signage. <br /> Sheets A1.11 and A1.12 indicate that the parking deck surface will have a new waterproof <br /> membrane applied. This work results in restriping of the parking spaces, including the <br /> accessible parking. The parking structure shall provide the required number of accessible <br /> parking spaces per IBC Table 1106.4. Based on the number of spaces indicate for the Top <br /> Deck, 2% of the available spaces for the entire garage shall be accessible. Additional <br /> documentation substantiating the accessible parking spacing shall be submitted for review. <br /> Van accessible spaces shall be provided per Section 1106.5. Spaces shall be distributed on <br /> all levels per 1106.6. Accessible spaces shall be provide with routes to the accessible <br /> means-of-egress per Section 1104.3. See IEBC Sections 806.1, and 705.1 and 705.2. <br /> 'o 3200 Cedar Street raTh 425.257.8800 0 everettpw@everettwa.gov <br /> Everett,WA 98201 425.257.8882 fax everettwa.gov <br /> 2I5. <br />