• <br /> Mr. Ruben Sanchez <br /> City of Everett <br /> Plan Check Number: B1812-022, Second Building Review <br /> March 19, 2019 <br /> Gravity System: <br /> 5. This comment has not been completely addressed. See IEBC Section 106.2.1. The <br /> following comments shall be addressed: <br /> a. Detail 14/S.10 includes a section cut referencing this detail. Verify the correct reference <br /> should be Section 15/S.10. <br /> b. Note 4 in Detail 17/S.10 specifies locating the existing reinforcement prior to drilling. <br /> Verify if Detail 14/S.10 and other details on this sheet should include this requirement. <br /> 6. No additional comment. <br /> 7. This comment has not been completely addressed. Verify if an end dimension should be <br /> provided. See IEBC Section 106.2.1. <br /> 8. No additional comment. <br /> 9. This comment has not been completely addressed. The following comments shall be <br /> addressed: <br /> a. Calculations have been submitted for the supplemental connection. The load appears to <br /> be applied incorrectly (i.e., downwards instead of upwards toward the top edge). The <br /> direction of loading shall be verified. Revised calculations substantiating the connection <br /> shall be submitted as needed. Note that the"concrete edge failure" mechanism appears <br /> to be 100% utilized (i.e., DCR=1.0) for the current direction of loading. Loading in the <br /> opposite direction is anticipated to yield a DCR>1.0. <br /> b. No additional comment. <br /> 10.This comment has not been completely addressed. Detail 13/S.10 specifies replacement of <br /> the support connection for precast beam. See IBC Sections 1604.1 and 1604.4. The <br /> following comments shall be addressed: <br /> a. Calculations substantiating the design of the connection shall be submitted for review. <br /> The calculation package does not appear to include the design of this connection as <br /> indicated by the response. <br /> b. The proposed FRP confinement includes inward angles that do not appear effective at <br /> remaining in tension. Verify if the FRP should be wrapped around the column, or at <br /> least the sides, and the corners filled (e.g., non-shrink grout, etc.) to maintain tension in <br /> the FRP and provide the required confinement to resist breakout failure of the proposed <br /> connection. <br /> O 3200 Cedar Street 425.257.8800 0 everettpw@everettwa.gov <br /> Everett,WA 98201 425.257.8882 fax everettwa.gov <br /> 1 <br />