House Specifics <br /> Is there currently a backwater valve at this location: No (not from C/O access on) <br /> Is backwater valve functioning properly: NA <br /> Is there currently a clean out on the side sewer: Yes in Basement <br /> How many at risk plumbing fixtures below the road surface are there: 5 <br /> Toilet,Sink,SH,Bar sink, Patio Drain <br /> How many down spouts are currently connected to the sewer: 0 <br /> Does side sewer have slope: No (not leaving foundation) Contractor error or soil <br /> settling. <br /> Depth of side sewer 10ft from house: 7'9" <br /> Sewer Report: <br /> Material: Concrete, pvc. <br /> Sewer Length:82' <br /> Condition: 2 bad points, flat dip in pipe as it leaves house, 2nd crack in top of pipe under <br /> driveway <br /> Explain: Sewer is flat leaving the basement. <br /> Recommend: Manually excavate line as it leaves house and re-grade line to have fall. If <br /> a B/W valve is placed here it will always have standing water pressure on the door. <br /> Any additional comments: <br /> • Install B/W valve near sidewalk depth at 9.5 feet this would make the rest of the <br /> side sewer a storage for any water going into system from back patio outside .. <br /> Problems Identified <br />