SEQUENCE OF OPERATIONS <br />RTU-113 <br />UNIT WILL BE CONTROLLED BY HONEYWELL DDC CONTROL SYSTEM. FAN SHALL RUN CONTINUOUSLY DURING THE OCCUPIED MODE AND SHALL CYCLE ON A CALL FOR HEAT/COOL DURING THE <br />UNOCCUPIED MODE. OCCUPIED SET POINTS SHALL BE 70 DEG F FOR HEAT AND 74 DEG F FOR COOLING, UNOCCUPIED SET POINTS SHALL BE 60 DEG F FOR HEAT AND 80 DEG F FOR COOLING. OCCUPIED <br />SCHEDULE SHALL BE COORDINATED WITH FACILITY STAF TO MEET FACILITY REQUIREMENTS. TEMPORARY 2-HOUR OCCUPANCY OVERRIDE WILL BE PROVIDE WITH BUTTON ON ALL TEMPERATURE <br />SENSORS LOCATED THROUGHOUT THE BUILDING. ECONOMIZER SHALL PROVIDE FIRST STAGE COOLING WHEN OSA CONDITIONS ALLOW. HEAT SHALL STAGE ON WHEN THERE IS A HEATING CALL. OSA <br />DAMPER SHALL BE CLOSED WHENEVER SYSTEM IS NOT IN ECONOMIZER MODE. SYSTEM SHALL UTILIZE OPTIMUM START LOGIC FOR MORNING WARMUP. <br />HIRVA <br />SYSTEM SHALL BE CONTROLLED BY HONEYWELL DDC CONTROL SYSTEM. SYSTEM SHALL BE INTERLOCKED WITH RTU-13 30 THAT FAN RUNS CONTINUOUSLY WHENEVER RTU-13 IS IN THE OCCUPIED MODE. <br />General Mechanical Notes <br />All thermostats used for both heating and cooling shall provide a range or cleadband of at least 5°F. WSEC Section C403.2.4.1.2 <br />All thermostats are to be seven day programmable, micro -processor based. <br />All heating and cooling systems shall have automatic start controls for each HVAC system WSEC Section C403.2.4.2.3 <br />All ductwork shall be constructed and sealed per SMACNA standards. <br />All ductwork shall be braced per IMC 2015. Duct support per Section 603.10. <br />All refrigerant used shall be Puron (R-410a). <br />All flues shall be located a minimum of 10'frorn outdoor air intakes. <br />All exhaust terminations shall be a minimum of 10' horizontally from, or Tabove outdoor intakes. <br />All air -economizers shall have modulating outdoor air and return air dampers capable of providing 100% outdoor air for cooling. WSEC Section C403.3.3.1 <br />All air -economizers shall be fully modulating and capable of partial cooling (integrated operation). WSEC Section C403.3.1 <br />Air handlers which supply in excess of 2,000 CFM shall have a return mounted smoke duct detector. <br />All addressable functions of duct smoke detectors, and wiring for shutdown, shall be by others. <br />All roof mounted units shall be secured to their respective roof curbs. <br />All exposed edges of internal duct liner shall be sealed with a mastic coating. <br />All completion requirements must comply with WSEC Section C408.1 <br />To comply with WSEC Section C408.1.1 & C403.2.10 systems documentation, record documents and training will be completed and coordinated with owner. <br />To comply with WSEC Section C408.2 preliminary commissioning report will be submitted to owner after being certified by registered design professional or approved agency. <br />All thermostats to be mounted such that the top of the device is 48" above finished floor. <br />All gas piping shall be sized per 2015 IFGC. <br />All HVAC systems shall be air balanced and adjusted to deliver final flow rates within 10% of design rates. <br />Outdoor air supply and exhaust ducts shall shut automatically when the system or spaces served are not in use or during building warm-up, cooldown, and setback. WSEC Section C403.2.4.3 <br />Outdoor air supply and exhaust ducts shall be equipped with motorized dampers according to WSEC Section C403.2.4.3 <br />Equipment shall meet the minimum efficiency requirements of WSEC Section 0403.2.3 <br />System sizing to comply with WSEC Section C403.2.2 <br />Damper leakage rates shall comply with WSEC Section C403.2.4.3 <br />All gas fired equipment greater than 226,000 Btu/h shall have an intermittent ignition device <br />Duct Insulation Schedule: All ductwork shall be insulated as follows: <br />DUCT TYPE: <br />LOCATION <br />INSULATION R-TYPE <br />TYPE <br />Supply/Return <br />Not within insulated envelope -(exterior oLbuilding onrooLinattic-above insulation, incrawlspa(es� <br />R-7 <br />2" wrap or liner <br />F_ Supply/Return/OA <br />O ojLnd) <br />Not within insulated envelopein-gr <br />R-5.3 <br />1.5" liner or V Spunstrand <br />CA Intake <br />Not within insulated envelope <br />R-0 <br />CA Intake (Rectangular) <br />Within insulated envelope, in mechanical room. <br />R-7 <br />2" liner <br />OA Intake (Round) <br />Within insulated envelope <br />R-7 <br />2" wrap <br />Supply on cooling systems <br />Within insulated envelope, not exposed to space served. <br />R-3.3 <br />1 " wrap or liner <br />Supply on cooling systems <br />Within insulated envelope, exposed to space served. <br />R-0 <br />Supply on heating only systems <br />insulated envelope <br />R-0 <br />Return <br />--Within <br />Within insulated envelope <br />R-0 <br />Exhaust <br />Other than R occupancy <br />Exhaust <br />R occupancv Residential) _ <br />-L _ <br />R-8 <br />2" wrap or liner <br />Offln''NUMM"S MIX <br />]IMT M—TIMENUMM REENIMM <br />Per section 403.2 of the 2015 IMC (Washington State Amendments), we are using ASH RAE Standard 62.12016 as an alternate means of compliance with the 2015 IMC Section <br />403.2 Washington State Amendments. <br />Description <br />Space <br />Occupancy <br />People OSA <br />Rate <br />Occupant <br />OSA/SQFT Density <br />Occupant <br />Count <br />Occupant Vent <br />Count V bz Reqlred <br />CO2 Min <br />(Per1000 <br />People (if <br />(SQFT/Rooms) <br />From ASHRAE Stcl 62.1) <br />NOTES <br />CFM/Person <br />SOFT) #/1000 SF <br />(People) <br />Known) CFM OSA CFM <br />OSA CFM <br />l�l�l9®1 <br />_ <br />Healthcare Partner 220 1,I o <br />Office Space <br />F <br />H <br />0.06 <br />5 <br />17.0 <br />20'1 <br />252 116 <br />Total =_1,64_01_ <br />_5 <br />F <br />1 9.7 <br />252 '1'16 <br />MARK <br />� M� <br />MODEL <br />08A <br />� EXHAUST <br />ESP <br />FLOW CNTRL <br />MCA <br />MOCP <br />Voltage <br />TEMP: <br />FILTRATION WT <br />I <br />Comments <br />CFM <br />(CFM) <br />IN H2O <br />(AMPS) <br />EFFICIENCY <br />EFF <br />(lbs) <br />HRV-1 <br />---FVAM300GVJU <br />I DAIKIN <br />360 <br />300 <br />J 0.60 <br />6� <br />CONSTANT <br />C <br />1 . 6 <br />-15 <br />_01o�� <br />208/230-1 <br />65% <br />L_ MERV 8 75 <br />r,iu I t: t-or iempeTT near recovery units, ouctworK snail oe oum io a 4 pressure ciass wrinin ju or me unii. <br />MARK <br />MAKE <br />MODEL <br />Comments <br />A <br />SHOEMAKER <br />700 MA <br />LAY IN SUPPLY <br />B <br />SHOEMAKER <br />MA <br />HARD LID SOPPY <br />C <br />SHOEMAKER <br />645T <br />LAY IN RETURN/EXHAUST/TRANSFER <br />D <br />SHOEMAKER <br />645 <br />HARD LID RETURN/EXHAUST/TRANSFER <br />E <br />SHOEMAKER <br />903 <br />SIDEWALL SUPPLY <br />F <br />SHOEMAKER <br />905 <br />SIDEWALL RETURNITRANSFER <br />G <br />SHOEMAKER <br />RD <br />ROUND CEILING SUPPLY GRILLE <br />H <br />SHOEMAKER <br />LSD <br />LINEAR SLOT DIFFUSER <br />..lkl t", "I i MARI NET, N-10.11, " MIA <br />MARK <br />MAKE <br />MODEL <br />CFM <br />ESP <br />(IN H20) <br />OSA MIN FLOW HEAT CAP (Stage 1) <br />(GPM) Input (BTUIH) Output <br />HEAT CAP (Stage 2) (AFUE) COOLING CAP REFGRNT <br />Input (BTU/H) Output Total (BTUIH) Sens. (LBS) <br />SEER <br />E <br />IEER <br />2-SPEED <br />MAX <br />MOTOR <br />MCA <br />(Amps) <br />MOCP <br />(Amps) <br />LRA <br />(Amps) <br />Voltage <br />(Volt - Phase) <br />DISCHARGE <br />VERTICAL/ <br />M <br />Rating <br />ight <br />(lbs.) <br />RETURN <br />MOUNTCO2 <br />SPACE <br />MOUNT CO2 <br />AIRFLOW <br />(JADE/DDC) <br />EXHAUST <br />ornmerl <br />(Coq§ILVFD <br />MOTOR <br />BHP <br />HORIZONTAL <br />SENSOR CITY <br />SENSOR OTC! <br />STATION <br />YIN <br />Y/N <br />14" CURB, DN SHOT <br />RTU-13 <br />CARRIER <br />48KC05 <br />1,600 <br />1.00 <br />0 CONSTANT 72,000 � 56,000 <br />82.0% 47,500 37,050 10.5 <br />14.0 <br />12.0 <br />- <br />1.7 <br />12.0 <br />15 <br />61 <br />460-3 <br />VERTICAL <br />MERV 13 <br />690 <br />—0 <br />0 <br />NO <br />YES <br />DDC <br />NO <br />ECONO — <br />HVAC 2ND FLOOR PLAN <br />118" <br />I <br />ALL DOCUMENTS, ELECTRONIC OR OTHERWISE, <br />PREPARED BY SUNSET AIR ARE FOR USE SOLELY <br />VV ITH RESPECT TO THE SUBJECT PROJECT. SUNSET <br />AIR IS THE OWNER OF THE DOCUMENTS, AND SHALL <br />RETAIN ALL COMMON LAW, STATUTORY, AND OTHER <br />RESERVE RIGHTS, INCLUDING COPYRIGHTS. <br />EXPRESSLY CONDITIONED UPON SUNSET AIR <br />PERFORMING THE CONSTRUCTION ASSOCIATED <br />WITH THE DOCUMENTS FOR THE PROJECT, SUNSET <br />AIR GRANTS TO CLIENT A NON-EXCLUSIVE LICENSE <br />TO REPRODUCE SUNSETARS DOCUMENTS SOLELY <br />FOR PURPOSES OF CONSTRUCTING, USING, AND <br />MAINTAINING THE PROJECT, PROVIDED THAT CLIENT <br />SHALL COMPLY WITH ALL OBLIGATIONS, INCLUDING <br />PROMPT PAYMENT OF ALL SUMS WHEN DUE, <br />EXPIRES: 08-11-18 <br />UJ <br />LIJ <br />Lu <br />>- <br />0 <br />> <br />C.) U.1 <br />LLA <br />0� M <br />CD LIJ CD <br />> C14 <br />—4- <br />00 <br />UJ 0-) <br />DESIGNED BY: <br />RMC <br />DRAWN BY: <br />SFC <br />REVIEWED BY: <br />RJP <br />REVISIONS <br />07.18.18 <br />ISSUE FOR DESIGN <br />DEVELOPMENT <br />09.10.18 <br />90% CD <br />09,20.18 <br />PERMIT SET <br />SHEET NUMBER <br />