5.3 WELDING <br />5.3.1 ALL WELDING SHALL BE IN ACCORDANCE WITH THE "STRUCTURAL <br />WELDING CODE," AWS D1.1, AWS D1.4 AND AWS D1.8 AS APPROPRIATE. <br />5.3.2 ALL WELDING SHALL BE BY CERTIFIED WELDERS; USE 70 KSI LOW <br />HYDROGEN FILLER METAL, AND SHALL BE PROTECTED PER AWS D1.1 <br />UNTIL USE. FOR ALL FULL PENETRATION WELDS, FILLER METAL SHALL <br />BE NOTCH TOUGH TO MEET CHARPY V-NOTCH OF 20 FOOT-POUND AT <br />-20°F. <br />5.3.3 NO WELDING OF REINFORCING STEEL SHALL BE ALLOWED EXCEPT <br />WHERE SHOWN. ALL WELDING OF REINFORCEMENT <br />SHALL BE PER ANSI(AWS D1.4. THE FOLLOWING FILLER <br />METAL SHALL BE USED WHEN WELDING REINFORCEMENT: <br />A. FOR WELDING OF ASTM A706 GR 60 REBAR, 80 KSI FILLER METAL, <br />B. FOR WELDING OF ASTM A615 GR 60 REBAR, NOT PERMITTED. <br />C. FOR WELDING OF ASTM A615 GR 40 REBAR, NOT PERMITTED. <br />5.3.4 ALL FULL PENETRATION FIELD AND SHOP WELDS SHALL BE FULL TIME <br />INSPECTED AND TESTED BY NON-DESTRUCTIVE PROCEDURES. <br />RESULTS OF TESTS SHALL BE SUBMITTED FOR REVIEW BY THE <br />STRUCTURAL ENGINEER. <br />�l►C�[I�7f�[t��3T�I��iI!#7�"iC7�w�ll[E��yNI►[t►tTN��I <br />5.4.1 FOR ALL WELDING OF REINFORCING STEEL, NON PREQUALIFIED <br />WELDS AND ALL WELDING OF COMPONENTS WHICH ARE PART OF THE <br />SEISMIC FORCE RESISTING SYSTEM, CONTRACTOR SHALL SUBMIT A <br />WELDING PROCEDURE SPECIFICATION (WPS) TO ENGINEER FOR <br />APPROVAL. PRIOR TO WELDING, EACH WPS SHALL INCLUDE ALL <br />NECESSARY INFORMATION REQUIRED BY AWS D1.1, AWS D1.4 AND <br />AWS D1.8 AND AS FOLLOWS: <br />A. APPLICABLE BASE METAL TYPES AND THICKNESSES, <br />B. SKETCH OF JOINT INDICATING APPLICABLE DIMENSIONS. <br />INDIVIDUAL PASSES SHALL BE IDENTIFIED AND NUMBERED TO <br />IDENTIFY THE SEQUENCE. THE SKETCH SHALL IDENTIFY THE <br />MAXIMUM THICKNESS AND BEAD WIDTH. IN NO CASE SHALL THE <br />LAYER THICKNESS EXCEED 1/4" NOR THE BEAD WIDTH EXCEED <br />5/8.11 <br />C. PREHEAT REQUIREMENTS. <br />D. ELECTRICAL CHARACTERISTICS (I.E., CURRENT, VOLTAGE, TRAVEL <br />SPEED, ETC.), <br />E. ELECTRODE REQUIREMENTS SHALL MEET THE REQUIREMENTS OF <br />AWS A5.1, AWS A5.5, AWS A5.17, AWS A5,23, AWS A5.18, AWS A5.20, <br />AWS A5.28, AND AWS A5.29, AS APPLICABLE FOR WELDING METHOD <br />USED. <br />5.6 STEEL JOISTS AND JOIST GIRDERS <br />5,6.1 DESIGN LOADS SHALL BE AS STATED IN SECTION 1,5 PLUS ANY <br />SPECIAL LOADS INDICATED ON THE DRAWINGS. UNLESS OTHERWISE <br />NOTED, MINIMUM DESIGN LOADS SHALL INCLUDE: <br />A. WHERE PRIMARY ROOF MEMBERS ARE EXPOSED TO A WORK <br />FLOOR A SINGLE NON -CONCURRENT CONCENTRATED LIVE LOAD <br />OF 2000 LBS SHALL BE LOCATED AT AT ANY PANEL POINT ALONG <br />THE TRUSS BOTTOM CHORD. <br />B. AT ROOF JOISTS AND JOIST GIRDERS, A MINIMUM NET UPLIFT <br />LOAD OF 12 PSF. <br />5.6.2 STEEL JOISTS AND JOIST GIRDERS SHALL BE MANUFACTURED PER <br />THE LATEST EDITION OF THE STANDARD SPECIFICATIONS FOR STEEL <br />JOISTS AND JOIST GIRDERS PUBLISHED BY THE STEEL JOIST <br />INSTITUTE. <br />5.6.3 ALL STEEL JOISTS AND JOISTS GIRDERS SHALL BE MANUFACTURED <br />BY A FABRICATOR CURRENTLY APPROVED BY ICC (INTERNATIONAL <br />CODE COUNCIL). MANUFACTURER SHALL BE A MEMBER OF SJI, AND <br />ALL STEEL JOISTS AND JOIST GIRDERS SHALL BE SJI APPROVED. <br />5.6.4 THE MANUFACTURER SHALL SUBMIT SHOP DRAWINGS AND <br />CALCULATIONS SEALED BY A PROFESSIONAL ENGINEER LICENSED IN <br />THE STATE OF THE PROJECT. <br />5.6.5 IT SHALL BE THE RESPONSIBILITY OF THE MANUFACTURER, THE <br />GENERAL CONTRACTOR, AND THE ERECTOR TO MANUFACTURE AND <br />INSTALL ALL STEEL JOISTS AND JOIST GIRDERS IN CONFORMANCE <br />WITH THE MOST CURRENT OSHA RULES (OSHA 29 CFR PART 1926.757), <br />5.6.6 PRE-ENGINEERED FLOOR JOISTS THAT EXCEED 25 FEET SHALL BE <br />CAMBERED BY 75% OF DEAD LOAD DEFLECTION. <br />5.6.7 LIMIT LIVE LOAD AND/OR SNOW LOAD DEFLECTION TO 1_1360 FOR <br />FLOOR FRAMING MEMBERS AND L/240 FOR ROOF FRAMING MEMBERS, <br />5.6.8 THE JOIST MANUFACTURER SHALL DESIGN THE JOISTS FOR UNIFORM <br />LOADS INDICATED ON THE STRUCTURAL DRAWINGS AS WELL AS ALL <br />SPECIAL LOADS NOTED ON THE STRUCTURAL PLANS AND DETAILS. <br />SPECIAL LOADS SHALL INCLUDE POINT LOADS FOR SUPPORT OF <br />SECONDARY FRAMING, OVERFRAMING AND SUPPORTED EQUIPMENT <br />(MECHANICAL UNITS, SUSPENDED EQUIPMENT, ETC.). <br />5.6.9 THE JOIST MANUFACTURER SHALL COORDINATE JOIST BRIDGING AT <br />EXPOSED LOCATIONS FOR ARCHITECTURAL APPEARANCE. BRIDGING <br />LOCATIONS SHALL ALSO BE COORDINATED TO AVOID CONFLICTS WITH <br />MECHANICAL DUCTWORK, SKYLIGHTS AND OTHER BUILDING <br />SYSTEMS. <br />5.7 STEEL DECKING <br />5.7.1 ALL STEEL DECKING SHALL BE FORMED FROM STEEL SHEETS <br />CONFORMING TO ASTM A-653, Fy A 38 KSI, AS A MINIMUM. THE <br />GALVANIZED COATING SHALL CONFORM TO ASTM A-653, G-60 OR G-90 <br />SPECIFICATIONS AS APPLICABLE. <br />5.7.2 ALL STEEL DECKING SHALL BE PLACED ON SUPPORTING FRAMEWORK <br />WITH A MINIMUM END LAP OF TWO INCHES CENTERED OVER <br />SUPPORTS. THE DECK SHALL BE ATTACHED TO SUPPORTS AND <br />FASTENED AT SIDE LAPS PER THE DIAPHRAGM SCHEDULE. <br />5.7.3 DECKING SHALL BE AS MANUFACTURED BYASC PROFILES, INC, OR <br />EQUIVALENT. ALTERNATE MANUFACTURERS SHALL BE PERMITTED <br />PROVIDED THE DECK MEETS OR EXCEEDS THE SECTION PROPERTIES <br />OF THE SPECIFIED DECK AND THE ALLOWABLE SHEAR CAPACITY <br />SPECIFIED IN THE DECK ATTACHMENT SCHEDULE. <br />5.7.4 IF CONCRETE TOPPING IS SPECIFIED, DECKING SHALL BE DEFORMED <br />OR EMBOSSED TO PROVIDE A MECHANICAL BOND WITH THE <br />CONCRETE. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO <br />PROVIDE DECKING SHORING WHERE REQUIRED BY THE <br />MANUFACTURER. <br />5.7.5 CONTRACTOR SHALL BE RESPONSIBLE TO COORDINATE WITH <br />ARCHITECTURAL DRAWINGS AND SPECIFICATIONS FOR ANY SPECIAL <br />REQUIREMENTS. <br />5.7.6 CONTRACTOR SHALL INSTALL DECKING AS REQUIRED TO PREVENT <br />MARRING/DAMAGING DECKING AT LOCATIONS EXPOSED TO VIEW <br />FROM BELOW. <br />-A <br />r< <br />Ln <br />A) <br />E <br />Ln <br />Lon) <br />Ln <br />u) <br />tn <br />o <br />r0 <br />® <br />rD <br />co <br />00 <br />0 <br />CL <br />s a <br />a. <br />ON WQ <br />mop`° <br />'Y p UrZG�Zh- 0o z <br />z �51 <br />�� pow <br />�w�zQo <br />�V VOw4 <br />pOC]p <br />z <br />x <br />�r. <br />}c <br />srN _0 ca <br />° <br />r 0 <br />r� <br />A Ln W <br />o� <br />TACONIA SEATTLE SPOKANE TRI-CITIES <br />2215 North 30th Street, Suite 300 Tacoma, DNA 98403 <br />253.383.2422 TEL 253,383.2572 f;A wnwi.ahbl.com WEB <br />is <br />a <br />gas <br />r,9 <br />c <br />M <br />