Laserfiche WebLink
• <br /> December 29,2021 <br /> Drew Martin, P.E.,S.E. <br /> Associate Engineer/Commercial Plans Examiner <br /> (425)257-8813 <br /> dmartin@everettwa.gov <br /> Plan Check Number:B2110-026,First Building Review comment responses <br /> Drew, <br /> Below are the responses to your comments. <br /> 1.The proposed project appears to involve converting a single-family residence into an adult <br /> family home (AFH).The submittal documents are required to include the AFH checklist.The <br /> checklist should include a floor plan on 8.5x11 paper per Section 3. Complete Sections 1, 2, <br /> and 4;do not complete Section 5.Submit the entire checklist with the floor plan.See the <br /> following link for the checklist: <br /> https://everettwa.gov/DocumentCenter/View/108/Adult-fam ily-home-checklist-PDF <br /> Response:AFH checklist has been included with a floor plan with the revised package. <br /> 2.The construction drawings should include a schedule stating the number of residence for each <br /> bedroom.The total number shall not exceed 6. <br /> Response:Plans have been revised to include this schedule. <br /> 3.The following comments should be addressed for the smoke and CO alarms: <br /> a. General Note 1 on sheet 3 should require the alarms to be wired to the building's main <br /> electrical system and provide with back-up battery power. <br /> Response:General note 1 hos been revised per this requirement. <br /> b.The alarms outside Bedroom B and the new bathroom are required to comply with the <br /> 1 � � <br />