• • <br /> I <br /> 16. The stair detail shows a maximum 4 inch opening.The code requirement is that a 4 inch sphere cannot <br /> pass through any opening, please correct. <br /> Revised Sheet 8 <br /> 17. The floor plans do not show the required landings. <br /> Revised Sheet 3 <br /> 18. Hand rails are required to be returned to the wall or terminate in a safety terminal please correct on <br /> the plans. <br /> Revised Sheet 8 <br /> 19. Provide seismic strapping for the water heater show on the plans. <br /> Revised Sheet 3 <br /> 20. Provide pressure relief valve to the outside.Show on plans. <br /> Revised Sheet 3 <br /> 21. The second floor cantilever is not shown on the North side of the floor plan. <br /> Revised Sheet 4 <br /> 22. The cantilever on the second floor is located in the 5 foot side yard set back and therefore is required <br /> to be one-hour fire-resistance rated. Openings are limited to 25% of the wall area, in the wall that <br /> projects into the 5 foot side yard setback. Please verify that the openings in the wall do not exceed <br /> 25%of the area of the wall.. arwl d cox-. Ihas <br /> Revised Sheet 6 Wel> ictc-rE-R'.c-eZ `cv'au- c.g..474ra4) -114:114 1'r1112" wpm, <br /> 23. It is difficult to determine which lines are representing the finished grade on the elevation drawings. ,ovFv <br /> Please correct the drawings to clearly define the finished grade. <br /> Revised Sheet 6&7 <br /> 24. The elevation drawing should call out all finish materials and roof pitch(es). <br /> Revised Sheet 6 <br /> 25. The section drawings should show,and label, all components including foundation(shown to scale at <br /> the required depth),sill plates, top and bottom plates, studs, insulation (floor, wall and ceiling) <br /> headers, rigid insulation at headers, wall floor and roof sheathing,joists, rim joist, rafters, blocking <br /> ventilation and roof trusses. <br /> Provided On New Sheet 13 <br /> 26. Specify which whole house ventilation system you will be using based on section M 1507.3.3 IRC. <br /> Specify the requirements of that system. Do not simply reference the code section. <br /> Revised Sheet 4&9 <br /> 27. Provide section drawing of the one-hour fire-resistance rated wall between dwelling units. <br /> Provided On New Sheet 13 <br /> 28. Dwelling units in 2 family dwellings shall be separated from each other I wall and floor assemblies <br /> having not less than a one-hour fire-resistance rating where tested in accordance with ASTM E 119 or <br /> UL 263. Fire resistance rated floor ceiling and wall assemblies shall extend 2 and be tight against the <br /> exterior wall, and wall assemblies shall extend from the foundation to the underside of the roof <br /> sheathing. Please correct the drawings to show these requirements. <br /> Provided On new Sheet 13 <br /> 29. The section cut references on the floor plans refer the wrong page location for the section drawings. <br /> Clarified On all pages effected <br /> 30. Provide sections and details for the cantilevered deck construction, including guardrail attachment. <br /> The height of the guardrail is noted as 34 inches on the plans it is required to be 36 inches minimum <br /> above the walking surface. <br /> Provided On new Sheet 13 <br /> Thank You. <br /> Page 2 of 2 <br />