<br />PART 1- GENERAL
<br />1.01 GENERAL REQUIREMENTS
<br />A. REFER TO DIVISION 01 SPECIFICATION. IF DIVISION 01 SPEC HAS DIFFERENT DIRECTION, SUBMIT REQUEST FOR INFORMATION
<br />(RFI).
<br />B. INSTALL ALL NEW WORK IN A NEAT WORKMANLIKE MANNER READILY ACCESSIBLE FOR OPERATION, MAINTENANCE AND REPAIR.
<br />C. CODES, PERMITS, AND INSPECTIONS
<br />1. ALL WORK SHALL COMPLY WITH REQUIREMENTS OF THE LOCAL ELECTRICAL CODE, LOCAL BUILDING DEPARTMENT,
<br />BUILDING MANAGEMENT, AND ALL AUTHORITIES HAVING JURISDICTION. APPLICABLE NATIONAL, STATE AND LOCAL CODES,
<br />LAWS AND REGULATIONS GOVERNING OR RELATING TO ANY PORTION OF THIS WORK SHALL BE INCORPORATED INTO AND
<br />MADE A PART OF THESE SPECIFICATIONS, CONTRACTOR. IS TO INFORM ENGINEER, OF ANY EXISTING WORK OR MATERIALS
<br />WHICH VIOLATE ANY OF THE ABOVE LAWS AND REGULATIONS. ANY WORK DONE BY THE CONTRACTOR CAUSING SUCH
<br />VIOLATION SHALL BE CORRECTED BY THIS CONTRACTOR AND AT NO EXPENSE TO THE OWNER.
<br />D. SITE VERIFICATION
<br />1. PRIOR TO SUBMISSION OF THE BID, THIS CONTRACTOR SHALL VISIT THE JOB SITE TO ASCERTAIN THE ACTUAL FIELD
<br />CONDITIONS AS THEY RELATE TO THE WORK INDICATED ON THE DRAWINGS AND DESCRIBED HEREIN(, DISCREPANCIES, IF
<br />ANY, SHALL BE BROUGHT TO THE ENGINEER'S ATTENTION PRIOR TO SUBMISSION OF THE BID, AND IF NOT RESOLVED TO
<br />SATISFACTION, SHALL BE SUBMITTED AS A WRITTEN QUALIFICATION OF THE BID. SUBMISSION OF A BID SHALL BE
<br />EVIDENCE THAT SITE VERIFICATION HAS BEEN PERFORMED AS DESCRIBED ABOVE.
<br />E. CONTRACT DOCUMENTS
<br />1. PRIOR TO SUBMISSION OF A FORMAL BID, THIS CONTRACTOR SHALL REVIEW ALL DRAWINGS OF THE ENTIRE PROJECT
<br />INCLUDING GENERAL CONSTRUCTION, DEMOLITION, ARCHITECTURAL, MECHANICAL, PLUMBING AND SPRINKLER AND SHALL
<br />INCLUDE ANY WORK REQUIRED IN THE BID WHICH IS INDICATED OR IMPLIED TO BE PERFORMED BY THIS TRADE IN OTHER
<br />SECTIONS OF THE WORK.
<br />2. DRAWINGS ARE DIAGRAMMATIC ,AND INDICATE GENERAL ARRANGEMENT OF WORK AND APPROXIMATE LOCATION OF
<br />EQUIPMENT. REFER TO ARCHITECTURAL DRAWINGS FOR ALL DIMENSIONS AND COORDINATE FINAL LOCATIONS OF
<br />SWITCHES LIGHT FIXTURES, RECEPTACLES ETC. WORK SHALL BE COORDINATED WITH OTHER TRADES TO AVOID
<br />CONFLICTS.
<br />3. IF A CONFLICT OCCURS IN THE SPECIFICATIONS AND/OR ON THE DRAWINGS, THE MORE STRINGENT SITUATION SHALL
<br />APPLY.
<br />4, ANY EQUIPMENT PARTS, MATERIALS, ACCESSORIES, OR LABOR THAT IS NECESSARY FOR PROPER PERFORMANCE OF THE
<br />ELECTRICAL WORK, ALTHOUGH NOT SPECIFICALLY MENTIONED HEREIN OR SHOWN ON THE DRAWINGS, SHALL BE
<br />FURNISHED AND INSTALLED WITHOUT ADDITIONAL COST.
<br />F. GUARANTEE
<br />1. ALL MATERIALS AND WORKMANSHIP SHALL BE GUARANTEED FOR A PERIOD OF ONE YEAR FROM DATE OF FINAL
<br />ACCEPTANCE OF THIS WORK. FINAL ACCEPTANCE SHALL BE DEFINED AS THE TIME AT WHICH THE ELECTRICAL WORK IS
<br />TAKEN OVER AND ACCEPTED BY THE OWNER, AND IS UNDER CARE, CUSTODY, AND CONTROL OF THE OWNER. ENGAGE THE
<br />SERVICES OF VARIOUS MANUFACTURERS SUPPLYING THE EQUIPMENT FOR THE PROPER STARTUP AND OPERATION OF ALL
<br />SYSTEMS INSTALLED, INSTRUCT THE OWNERS PERSONNEL IN THE PROPER OPERATION AND SERVICING OF THE
<br />EQUIPMENT.
<br />I E RESPONSIBILITY 2. .THE CONTRACTOR SHALL GUARANTEE TO REPLACE OR REPAIR PROMPTLY AND ASSUME FOR ALL
<br />EXPENSES INCURRED FOR ANY WORKMANSHIP AND EQUIPMENT IN WHICH DEFECTS DEVELOP WITHIN THE GUARANTEE
<br />PERIOD. THIS WORK SHALL BE DONE AS DIRECTED BY THE OWNER. THIS GUARANTEE SHALL INCLUDE RESPONSIBILITY TO
<br />PAY FOR ALL EXPENSES INCURRED IN REPAIRING AND REPLACING WORK OF OTHER TRADES AFFECTED BY DEFECTS,
<br />REPAIRS OR REPLACEMENTS IN EQUIPMENT SUPPLIED BY THIS CONTRACTOR.
<br />3, THIS CONTRACTOR IS RESPONSIBLE FOR THE MAINTENANCE AND OPERATION OF ALL SYSTEMS UNTIL THE FINAL
<br />ACCEPTANCE OF THE WORK.
<br />G. THE "GENERAL CONDITIONS OF THE CONTRACT FOR CONSTRUCTION" AIA DOCUMENT A201, LATEST EDITION, OR AS REQUIRED
<br />BY THE ARCHITECT DOCUMENTS, AND/OR THE STRUCTURAL ENGINEER'S DOCUMENTS, AS APPLICABLE, ARE PART OF THIS
<br />CONTRACT.
<br />H. DEFINITIONS
<br />1. "ELECTRICAL CONTRACTOR", "THIS CONTRACTOR' - THE PARTY OR PARTIES HAVE BEEN DULY AWARDED THE CONTRACT
<br />FOR AND ARE THEREBY MADE RESPONSIBLE FOR THE ELECTRICAL WORK AS DESCRIBED HEREIN.
<br />2. "THIS CONTRACT", "THE CONTRACT" - THE AGREEMENT COVERING THE WORK TO BE PERFORMED BY "THIS CONTRACTOR".
<br />3. "APPROVED", "EQUAL", "SATISFACTORY", "ACCEPTED", "ACCEPTABLE", "EQUIVALENT" SUITABLE FOR USE ON THE PROJECT,
<br />AS DETERMINED BY THE ENGINEER BASED ON DOCUMENTS PRESENTED FOR SUCH DETERMINATION.
<br />4. "THESE SPECIFICATIONS", "THIS SECTION, PART, DIVISIONS" (OF THE SPECIFICATION) - THE DOCUMENT SPECIFYING THE
<br />WORK TO BE PERFORMED BY "THIS CONTRACTOR".
<br />5. "THE ELECTRICAL WORK", "THIS WORK", - ALL LABOR MATERIALS, EQUIPMENT, APPARATUS, CONTROLS, ACCESSORIES, AND
<br />OTHER ITEMS REQUIRED FOR A PROPER AND COMPLETE INSTALLATION BY THE ELECTRICAL CONTRACTOR.
<br />6. "ARCHITECT", "ENGINEER", "OWNER'S REPRESENTATIVE" - THE PARTY OR PARTIES RESPONSIBLE FOR INTERPRETING,
<br />ACCEPTING AND OTHERWISE RULING ON THE PERFORMANCE UNDER THIS CONTRACT.
<br />7. "FURNISH" - PURCHASE AND DELIVER TO THE PROJECT SITE COMPLETE WITH EVERY NECESSARY APPURTENANCE AND
<br />SUPPORT, ALL AS PART OF THE ELECTRICAL WORK.
<br />8. "INSTALL" - UNLOAD AT THE DELIVERY POINT AT THE SITE AND PERFORM EVERY OPERATION NECESSARY TO ESTABLISH
<br />SECURE MOUNTING INSTALLATION AND CORRECT OPERATION AT THE PROPER LOCATION IN THE PROJECT, ALL AS PART
<br />OF
<br />THE ELECTRICAL WORK.
<br />9. "PROVIDE" "FURNISH" AND "INSTALL".
<br />10. "NEW" - MANUFACTURED WITHIN THE PAST TWO YEARS AND NEVER BEFORE USED.
<br />11. "RELOCATE" - MOVE EXISTING EQUIPMENT/DEVICES/FIXTURE AND ALL ACCESSORIES AS REQUIRED, INCLUDING THE
<br />EXTENSION OF EXISTING OR PROVIDING NEW CIRCUIT/CONDUCTORS/WIRING AS REQUIRED,
<br />12. "REMOVE" - DISMANTLE AND CART AWAY FROM SITE INCLUDING ALL RELATED ACCESSORIES. ALL OTHER EQUIPMENT AND
<br />OPERATIONS IN ANY WAY AFFECTED BY THE REMOVAL IS TO REMAIN IN FULL OPERATION. PROVIDE ALL NECESSARY
<br />COMPONENTS TO MAINTAIN SUCH OPERATION.
<br />1,02 SCOPE OF •
<br />A. PROVIDE ALL LABOR, MATERIALS, EQUIPMENT, AND CONTRACTOR'S SERVICES NECESSARY FOR COMPLETE, SAFE
<br />INSTALLATION OF ELECTRICAL WORK. THE SCOPEOF •RK SHALL INCLUDENOT BE • •
<br />I . DEMOLITION AND REMOVAL OF ELECTRICAL EQUIPMENT AS REQUIRED INCLUDING ALL CONDUCTORS, LOW VOLTAGE
<br />SYSTEM WIRING AND CONDUIT BACK TO THEIR SOURCE.
<br />2. INSTALLATION OF LIGHT FIXTURES ALAMPS
<br />INSTALLATION3. OF +', SWITCHES, RECEPTACLES,
<br />4INSTALLATION OF NEW RACEWAY AND CONDUCTORS FOR LIGHTING AND POWER.
<br />5. CUTTING, CHANNELING AND CHASING AS REQUIRED TO ACCOMMODATE THE ELECTRICAL INSTALLATION AND ROUGH
<br />6. ADDITION _ MODIFICATION OF EXISTING ELECTRICALDISTRIBUTION
<br />7. INSTALLATION OF HVAC POWER WIRING AND FINAL CONNECTIONS TO HVAC EQUIPMENT.
<br />8. INSTALLATION OF CONDUIT, JUNCTION BOXES, PULL BOXES, ETC. REQUIRED FOR THE AFOREMENTIONED EQUIPMENT.
<br />9. MAINTENANCE AND PROPER OPERATION OF EXISTING BASE BUILDING SYSTEMS WITHIN THE CONTRACT AREA IN
<br />ACCORDANCE •
<br />10. TEMPORARY AND POWER DURING CONSTRUCTION.
<br />11. GROUNDING OF ALL EQUIPMENT AS REQUIRED BY CODE AND AS SPECIFIED.
<br />12, MODIFICATION AND/OR EXPANSION OF THE EXISTING FIRE ALARM SYSTEM,
<br />B. CUTTING AND•
<br />1. THIS CONTRACTOR SHALL BE RESPONSIBLE FOR ALL CUTTING, CHASING, FITTING AND PATCHING THAT MAY BE REQUIRED
<br />• ELECTRICAL WORK. ALL PATCHING{LL BE OF THE SAME MATERIALS,WORKMANSHIP,• AACCURATELY MATCH ALL SURROUNDING WORK AND BUILDING STANDARDS.
<br />2. ALL PENETRATIONS THROUGH FIRE RATED WALLS, PARTITIONS, ETC, SHALL BE FIRE STOPPED UTILIZING APPROVED
<br />ND SHALL
<br />3. AFTER COMPLETION OF WORK UNDER THIS SECTION, CONTRACTOR SHALL CLEAN-UP RESULTANTIDEBRIS FROM THIS
<br />WORK AND REMOVE FROM THE SITE.
<br />1.03 COORDINATIONBUILDING +
<br />A. THIS CONTRACTOR IS TO OBTAIN A COPY OF THE BUILDING RULES AND REGULATIONS PRIOR TO BID SUBMISSION TO
<br />DETERMINE REQUIREMENTS AND THE EXTENT OF PREMIUM TIME WORK REQUIRED BY BUILDING MANAGEMENT. FOR THE
<br />PURPOSE OF THE BID ASSUME ANY NOISY WORK (E.G., CHOPPING, CORE DRILLING ETC.) AND BASE BUILDING SYSTEM
<br />INTERRUPTIONS ARE TO BE PERFORMED OUTSIDE NORMAL BUSINESS HOURS.
<br />B. THIS CONTRACTOR IS RESPONSIBLE FOR ADHERING TO THE BUILDING OWNERS RULES AND REGULATIONS. ANY
<br />DISCREPANCIES BETWEEN THE CONTRACT DOCUMENTS AND THE BUILDING RULES AND REGULATIONS, SHALL BE SUBMITTED IN
<br />WRITING TO THE » FOR REVIEW, WITH BID
<br />C. COORDINATE WITH BUI• OWNER ■ ANY SERVICE INTERRUPTION OF D GIVE NOTICE
<br />» R#
<br />BY BUILDING RULES AND REGULATIONS OR A MINIMUM OF TWO (2) DAYS PRIOR TO ANY WORK, WHICHEVER IS MORE
<br />CONTRACTOR TO . •R ON SO AS NOT •DISTURB EXISTING TENANTS
<br />ON
<br />OTHER
<br />FLOORS.
<br />1.04 SHOP DRAWINGS
<br />A. SUBMIT SHOP DRAWINGS CERTIFIED BY ALL TRADES THAT COORDINATION HAS BEEN COMPLETED. SUBMIT ALL CERTIFIED
<br />EQUIPMENT CUTS WITH CONSTRUCTION WIRING DIAGRAMS, SHOP DRAWINGS SUBMISSION SHALL INCLUDE, BUT NOT BE
<br />LIMITED TO, THE FOLLOWING:
<br />1. DISTRIBUTION EQUIPMENT.
<br />2. OVERCURRENT PROTECTIVE DEVICES (FUSES AND BREAKERS).
<br />3. LIGHTING FIXTURES.
<br />4. LIGHTING CONTROLS.
<br />5. DEVICES.
<br />6. FIRE ALARM SYSTEM EQUIPMENT AND WIRING SCHEMATIC.
<br />B. PROVIDE SHOP DRAWINGS IN ELECTRONIC FORMAT. SPECIFIC JOB REQUIREMENTS MAY BE MORE STRINGENT AND
<br />CONTRACTOR IS RESPONSIBLE TO OBTAIN REQUIREMENTS FROM CONSTRUCTION MANAGER, GENERAL CONTRACTOR OR
<br />ARCHITECT.
<br />1.05 MAINTENANCE MANUALS
<br />A. SUBMIT FOUR (4) LOOSE-LEAF BOUND OPERATING AND MAINTENANCE MANUALS WITH INDEX AND INDEX TABS TO INCLUDE THE
<br />FOLLOWING:
<br />1. OPERATING AND MAINTENANCE INSTRUCTIONS ON ALL SYSTEMS.
<br />2. MANUFACTURERS' CATALOG CUTS ON ALL EQUIPMENT.
<br />3. ALL ITEMS SUBMITTED FOR REVIEW IN SHOP DRAWING SECTION,
<br />1.06 AS -BUILT DRAWINGS
<br />A. CONTRACTOR SHALL MAINTAIN RECORD DRAWING PRINTS ON JOB SITE AND RECORD, AT TIME OF OCCURRENCE, DEVIATIONS
<br />FROM CONTRACT DOCUMENTS DUE TO FIELD COORDINATION, BULLETINS, OR ADDENDA.
<br />B. CONTRACTOR SHALL REVISE SHOP DRAWINGS TO CONFORM TO RECORD DRAWINGS AND SUBMIT AN AS -BUILT CONDITION
<br />(DEVICES, EQUIPMENT, CIRCUITRY, ETC.) DRAWINGS UPON COMPLETION OF THE PROJECT. FINAL SUBMISSION OF
<br />REPRODUCIBLE AS -BUILT DRAWINGS ARE TO BE SIGNED AND CERTIFIED BY INSTALLING CONTRACTOR THAT THIS IS THE AS -
<br />BUILT CONDITION OF THE WORK.
<br />1.07 SUBSTITUTIONS
<br />A. NO SUBSTITUTE MATERIAL OR MANUFACTURER OF EQUIPMENT SHALL BE PERMITTED WITHOUT A FORMAL WRITTEN SUBMITTAL
<br />TO THE ENGINEER WHICH INCLUDES ALL DIMENSIONAL, PERFORMANCE AND MATERIAL SPECIFICATIONS. ANY CHANGES IN
<br />LAYOUT, MECHANICAL CHARACTERISTICS, STRUCTURAL REQUIREMENTS, OR DESIGN DUE TO THE USE OF A SUBSTITUTION
<br />SHALL BE SUBMITTED TO THE ENGINEER AS PART OF THIS PROPOSAL. THE CONTRACTOR TAKES FULL RESPONSIBILITY FOR
<br />THE SUBSTITUTION AND ALL CHANGES RESULTING FROM SUBSTITUTION. ALL ITEMS SHALL BE SUBMITTED FOR REVIEW IN
<br />CONJUNCTION WITH THE SUBMITTAL OF THE ALTERNATE. ANY SUBSTITUTION MUST BE SUBMITTED WITH AN EXPLANATION WHY
<br />A SUBSTITUTION IS BEING UTILIZED AND HOW THE PROPOSED MATERIAL MEETS OR EXCEEDS THE SPECIFICATIONS OF THE
<br />MATERIAL BEING SUBSTITUTED. IF THE SUBSTITUTED ITEM DEVIATES FROM THE SPECIFIED ITEM, THOSE DEVIATIONS ARE TO
<br />BE IDENTIFIED ON A LINE BY LINE BASIS. IF THE SUBSTITUTE IS BEING UTILIZED FOR FINANCIAL REASONS, THE ASSOCIATED
<br />CREDIT MUST BE SIMULTANEOUSLY SUBMITTED.
<br />B. ALL SUBSTITUTED EQUIPMENT SHALL CONFORM TO SPACE REQUIREMENTS AND PERFORMANCE REQUIREMENTS SHOWN ON
<br />CONTRACT DOCUMENTS, CONTRACTOR SHALL REPLACE ANY EQUIPMENT THAT DOES NOT MEET THESE REQUIREMENTS AT HIS
<br />OWN EXPENSE, ANY MODIFICATIONS TO ASSOCIATED SYSTEMS OR ADDITIONAL COSTS ATTRIBUTED TO THIS SUBSTITUTION
<br />SHALL BE AT THIS CONTRACTOR'S EXPENSE.
<br />C. CONTRACTOR SHALL SUBMIT BID BASED ON SPECIFIED ITEMS AND SHALL SUPPLY AS AN ALTERNATE PRICE ANY
<br />SUBSTITUTIONS.
<br />1.08 ACCESS DOORS IN GENERAL CONSTRUCTION
<br />A. THIS CONTRACTOR SHALL SUBMIT TO THE ARCHITECT FOR APPROVAL A PLAN INDICATING THE SIZE AND LOCATION OF ALL
<br />ACCESS DOORS REQUIRED FOR OPERATION AND MAINTENANCE OF ALL CONCEALED EQUIPMENT, DEVICES, JUNCTION BOXES,
<br />PULL BOXES ETC. THIS CONTRACTOR SHALL ARRANGE FOR THE FURNISHING AND INSTALLATION OF ALL ACCESS DOORS IN
<br />FINISHED CONSTRUCTION AND INCLUDE COSTS IN THE BID. ACCESS DOORS SHALL BE OF ADEQUATE SIZE TO PROVIDE ACCESS
<br />TO CONCEALED ITEMS FOR OPERATION AND MAINTENANCE.
<br />mrdlviufflm�"'
<br />A. PANELBOARD BOXES SHALL BE MADE OF SHEET STEEL"BENT-UP" OR RIVETED ORBOLTED
<br />LTEDTOG ETHER WITH EXTERIOR ANGLE
<br />IRON FRAME. BOX SHALL BE OF SUFFICIENT SIZE TO ALLOW A GUTTER AT LEAST 5-3/4" IN WIDTH ENTIRELY SURROUNDING EACH
<br />SECTION OF BOARD. INCREASE GUTTER SIZE TO ACCOMMODATE FEEDER SIZE, PANELBOARDS SHALL BE SURFACE OR FLUSH
<br />TYPE AS NOTED ON THE DRAWINGS. PANEL BOX AND COVER SHALL BE GIVENTWO COATS 0F GREY ENAMEL PAINT.
<br />B. PROVIDE CODE GAUGE STEEL DOORS FOR ALL PANELBOARD BOXES. FRONT COVER SHALL BE A "DOOR WITHIN A DOOR" TYPE.
<br />THE OUTER DOOR (TRIM) SHALL ALLOW ACCESS TO ENTIRE PANELBOARD BOX INCLUDING GUTTER SPACES, OUTER DOOR
<br />(TRIM) SHALL BE ATTACHED DIRECTLY TO BOX BY A FULL LENGTH PIANO HINGE. THE INNER DOOR SHALL ALLOW ACCESS TO
<br />CIRCUIT BREAKERS ONLY. PROVIDE LOCK AND KEY FOR INNER DOOR.
<br />C. PANEL BUS BARS SHALL BE COPPER PROPORTIONED FOR A CURRENT DENSITY OF 1000 AMPERES PER SQUARE INCH OF
<br />CROSS -SECTIONAL AREA. PROVIDE A COPPER GROUND BAR IN EACH PANEL. PROVIDE AN ISOLATED GROUND BAR IN PANELS
<br />AS INDICATED ON PANEL SCHEDULES.
<br />D. PANELS SHALL BE PROVIDED WITH NEUTRAL BARS SIZED AT 100% OF THE PHASE BUS BARS AS CALLED FOR ON PANEL
<br />SCHEDULES.
<br />E. A TYPEWRITTEN( LIST OF CIRCUITS SHOWING CLEARLY THE LOADS SUPPLIED BY EACH CIRCUIT SHALL BE INSTALLED ON THE
<br />INSIDE OF EACH PANEL BOARD DOOR THIS LIST SHALL BE MOUNTED IN A STEEL FRAME UNDER A PLASTIC WINDOW. EACH
<br />PANEL SHALL BE EXTERNALLY TAGGED WITH PERMANENT LAMACOID PLATE INDICATING PANEL IDENTIFICATION AND VOLTAGE,
<br />F. PHASE LEGS OF ALL PANELS SHALL BE BALANCED AT SUPPLY POINT, ANY PANEL FOUND WITH UNBALANCED LOADS SHALL
<br />HAVE ITS CIRCUITS REARRANGED AS REQUIRED TO BALANCE PHASE LEGS WITHIN 10%.
<br />2.02 DISCONNECT SWITCHES
<br />A. UNLESS OTHERWISE NOTED, DISCONNECT SWITCHES SHALL BE "QUICK -MAKE, QUICK -BREAK," HEAVY DUTY TYPE IN NEMA 1
<br />ENCLOSURES FUSED OR UNFUSED AS INDICATED ON THE DRAWINGS. PROVIDE ALL FUSES AS REQUIRED. PROVIDE
<br />WEATHERPROOF NEMA 3R DISCONNECT SWITCHESWHERE INSTALLED OUTDOORS OR AS INDICATED ON DRAWINGS,
<br />2.03 CIRCUIT BREAKERS
<br />A. FOR PANELBOARD APPLICATIONS, CIRCUIT BREAKERS SHALL BE BOLTED TO THE PANELBOARD BUS BARS. WHERE CIRCUIT
<br />BREAKERS ARE INSTALLED IN EXISTING PANELBOARD BREAKERS SHALL BE OF THE SAME MANUFACTURER AND BE COMPATIBLE
<br />WITH EXISTING PANELBOARD. FOR STAND ALONE APPLICATIONS, CIRCUIT BREAKERS SHALL BE IN A NEMA 1 ENCLOSURE.
<br />B. CIRCUIT BREAKERS SHALL BE "THERMAL MAGNETIC -TYPE, QUICK -MAKE, QUICK -BREAK WITH NON -WELDING CONTACTS
<br />COMPENSATED FOR AMBIENT TEMPERATURES AND SHALL HAVE A MINIMUM SHORT CIRCUIT RATING OF 22,000 AMPERES
<br />SYMMETRICAL FOR 120/280V PANELS.
<br />C. CIRCUIT BREAKERS RATED AT 400A OR HIGHER SHALL BE ADJUSTABLE ELECTRONIC TRIP MOLDED CASE.
<br />D. ANY CIRCUIT BREAKERS MADE AVAILABLE DUE TO DEMOLITION SHALL BE DESIGNATED AS SPARE ON PANELBOARD
<br />DIRECTORIES AND SWITCHED IN THE OFF POSITION.
<br />2.04 FUSES
<br />A. FUSES SHALL BE CURRENT LIMITING TYPE WITH AN INTERRUPTING CAPACITY OF 200,000 RMS AMPERES AND OF THE
<br />CONTINUOUS CURRENT RATINGS AS SHOWN ON THE DRAWINGS.
<br />B. THEY SHALL HAVE AVERAGE MELTING TIME -CURRENT CHARACTERISTICS TO MEET THE UNDERWRITERS'LABORATORIES
<br />REQUIREMENTS FOR "CLASS W 0-600 AMP FUSES AND "CLASS L" OVER 600 AMP FUSES.
<br />2.05 RACEWAYS
<br />A. ALL WIRES SHALL BE RUN IN CONDUIT AS SPECIFIED HEREINAFTER; EACH LENGTH OF CONDUIT SHALL BEAR THE MAKER'S
<br />TRADEMARK OR STAMP. THE PLANS INDICATE THE GENERAL LOCATION OF OUTLET BOXES AND CIRCUITING. THE CONDUIT
<br />RUNS FOR THESE CIRCUITS MAY BE MODIFIED AT THE TIME OF INSTALLATION TO ADAPT SAME TO BUILDING CONSTRUCTION.
<br />B. FOR ALL SIZES OF CONDUIT LARGER THAN 1-1/2", USE STANDARD ELBOW; IN SMALLER SIZES, FIELD BENDS WILL BE PERMITTED
<br />INSTEAD OF USING MANUFACTURED ELBOWS BUT CARE MUST BE TAKEN NOT TO DAMAGE THE CONDUIT. THE RADIUS OF THE
<br />INNER CURVE OF ANY BEND SHALL NOT BE ANY LESS THAN THAT PERMITTED BY CODE.
<br />C. CONDUIT SHALL BE SECURELY FASTENED IN PLACE AND HANGERS, SUPPORTS OR FASTENINGS SHALL BE PROVIDED AT EACH
<br />ELBOW AND AT EACH END OF EACH STRAIGHT RUN TERMINATED AT A BOX OR CABINET, WHERE RISER CONDUITS PIERCE
<br />FLOOR SLABS, THEY SHALL REST ON EACH FLOOR WITH APPROVED BEAM CLAMPS, PIPE STRAPS OR HEAVY IRON TIES WIRED
<br />TO THE STRUCTURAL MEMBERS SUPPORTING EQUIPMENT. SIZE AND TYPE OF ANCHOR SHALL BE BASED ON THE COMBINED
<br />WEIGHTS OF CONDUIT, HANGER AND CABLES.
<br />D. INSTALL CONDUIT EXPANSION FITTINGS IN EACH CONDUIT RUN WHEREVER IT CROSSES AN EXPANSION JOINT AND WHEREVER
<br />THE CONDUIT LENGTH EXCEEDS 200 FEET.
<br />E, RUNNING THREADS SHALL NOT BE USED. WHERE CONDUIT WITH TAPERED THREADS CANNOT BE COUPLED WITH STANDARD
<br />CONDUIT COUPLINGS UTILIZE O.ZJGEDNEY SPLIT COUPLING OR ERICKSON COUPLINGS.
<br />F. LAY OUT AND INSTALL ALL CONDUIT RUNS TO AVOID PROXIMITY TO STEAM AND HOT WATER PIPES. DO NOT RUN CONDUIT
<br />WITHIN THREE INCHES OF SUCH PIPES EXCEPT WHERE CROSSINGS ARE UNAVOIDABLE, THEN THE CONDUIT SHALL BE KEPT AT
<br />LEAST 1 INCH FROM THE COVERING OF THE PIPE CROSSING.
<br />G. UNLESS OTHERWISE INDICATED OR SPECIFIED, ALL WRING SHALL BE INSTALLED CONCEALED IN CEILINGS, WALLS, SLABS, PIPE
<br />CHASES, AND FURRED SPACES WHENEVER POSSIBLE.
<br />H. FEEDERS AND BRANCH CIRCUITRY ABOVE HUNG CEILING AND IN PARTITIONS SHALL BE RUN IN ELECTRICAL METALLIC TUBING
<br />(EMT) UNLESS OTHERWISE NOTED. FINAL CONNECTIONS TO MOTORS, LIGHT FIXTURES, ETC, MAY BE DONE WITH FLEXIBLE
<br />METALLIC CONDUIT (NO LONGER THAN SIX FEET).
<br />I. ALL CONDUIT WHERE SUBJECT TO PHYSICAL DAMAGE, EXPOSED TO THE OUTDOORS, AND WHERE CONCEALED IN CONCRETE
<br />SHALL BE RIGID THREADED REGARDLESS OF SIZE.
<br />J. ELECTRIC METALLIC TUBING SHALL BE INDUSTRY STANDARD THIN WALL CONDUIT; EMT SHALL BE HOT DIPPED GALVANIZED
<br />STEEL ONLY, IT SHALL NOT BE LESS THAN 3/4" TRADE SIZE UNLESS OTHERWISE NOTED. EMT FITTINGS AND COUPLINGS SHALL
<br />BE COMPRESSION TYPE OR DOUBLE SET STEEL SCREW TYPE.
<br />K. FLEXIBLE METALLIC CONDUIT SHALL BE OF THE GROUNDING TYPE. IT SHALL CONSIST OF GALVANIZED STEEL TAPE FORMED
<br />INTO AN INDUSTRY STANDARD INTERLOCKING COIL. IT SHALL NOT BE LESS THAN 3/4" TRADE SIZE UNLESS OTHERWISE NOTED.
<br />L. HOT DIPPED GALVANIZED RIGID STEEL CONDUIT SHALL BE USED IN LIEU OF EMT, WHERE SUBJECTED TO ANY WATER OR
<br />MOISTURE CONDITIONS AND WHERE BURIED IN POURED SLABS, WALLS OR COLUMNS.
<br />M. THREADED FITTINGS SHALL BE USED WITH RIGID CONDUIT.
<br />N. EMPTY CONDUIT FOR NEW COMMUNICATION AND DATA OUTLETS IN PARTITIONS SHALL BE V THIN WALL RUN CONCEALED
<br />WALLS, TERMINATED AND BUSHED 6" INTO ACCESSIBLE HUNG CEILING AND DIRECTED TOWARDS PARTICULAR
<br />COMMUNICATION/DATA ROOM OR CLOSET. FURNISH DRAG LINE.
<br />0. ALL METAL CONDUITS TERMINATING IN A METAL ENCLOSURE SHALL HAVE AN INSULATED BUSHING. PROVIDE "GROUNDING"
<br />TYPE BUSHING WHERE REQUIRED.
<br />2,06 WIRE AND CABLE
<br />A. ALL CONDUCTORS SHALL BE SOFT DRAWN ANNEALED COPPER, MINIMUM CONDUCTIVITY 98% OF PURE COPPER PER ASTM 63,
<br />TYPE THHN/THWN INSULATED. ALL CONDUCTORS SHALL HAVE 600 VOLT RATED INSULATION UNLESS OTHERWISE NOTED.
<br />S. METAL CLAD CABLE (TYPE MC) WITH GROUND WIRE FOR CONCEALED BRANCH CIRCUITRY MAY BE USED WHEN WRITTEN
<br />APPROVAL IS GIVEN TO THE CONTRACTOR FROM THE BUILDING OWNER. IT SHALL ONLY BE INSTALLED WHERE PERMITTED BY
<br />CODE EXCEPT CIRCUIT HOMERUN TO FIRST OUTLET WHICH SHALL BE IN EMT. ARMOR CLAD CABLE (TYPE AC) SHALL NOT BE
<br />PERMITTED.
<br />C. THE MINIMUM WIRE SIZE FOR BRANCH CIRCUITS SHALL BE NO, 12 AWG EXCEPT 120 VOLT CIRCUITS OVER 100' IN LENGTH SHALL
<br />BE NO. 10 AWG.
<br />D. RECESSED LIGHTING FIXTURES FOR HUNG CEILING APPLICATIONS SHALL BE SUPPLIED WITH TYPE THHN INSULATED WIRE IN
<br />FLEXIBLE METALLIC CONDUIT, IN LENGTHS NOT TO EXCEED 6 FEET FROM ADJACENT JUNCTION BOXES.
<br />E. CONNECTION TO RECESSED CEILING FIXTURES SUPPLIED WITH PIGTAILS SHALL BE ARRANGED SO THAT UP TO FOUR SUCH
<br />FIXTURES MAY BE CONNECTED INTO A SINGLE OUTLET BOX. NO FIXTURE SHALL BE SUPPLIED FROM AN OUTLET IN ANOTHER
<br />ROOM.
<br />F. UNLESS SPECIFIED OTHERWISE, ALL WIRES #10 AWG AND SMALLER SHALL BE SOLID, CONDUCTORS #8 AWG AND LARGER SHALL
<br />BE STRANDED.
<br />G. COLOR CODING SHALL BE BUILDING STANDARD. WHERE NO BUILDING STANDARD EXISTS, FACTORY COLOR CODING SHALL BE
<br />AS FOLLOWS:
<br />1. 120/208 VOLT SYSTEM: PHASE W - BLACK, PHASES'- RED, PHASE'C' - BLUE, NEUTRAL- GREY, EQUIPMENT GROUND -
<br />GREEN.
<br />H. INSTALL AND CONNECT UP COMPLETE CONDUCTORS FOR ALL CIRCUITS AND WIRING SYSTEMS. UP TO 3 SINGLE CIRCUITS MAY
<br />BE RUN IN A CONDUIT UNLESS OTHERWISE NOTED.
<br />I. NO CONDUCTORS SHALL BE PULLED INTO ANY CONDUIT RUN BEFORE ALL CONDUIT JOINTS ARE MADE UP TIGHTLY, AND THE
<br />ENTIRE RUNT IS SECURED IN PLACE. WHEN REQUIRED TO EASE THE PULLING OF WIRES INTO CONDUIT, USE POWDERED
<br />SOAPSTONE, MINERALLAC #100 OR APPROVED EQUAL BY THOMAS AND BETTS,
<br />J. TAG ALL FEEDERS IN ALL PULL BOXES, GUTTER SPACES, AND WIREWAYS THROUGH WHICH THEY PASS.
<br />K. TERMINATE STRANDED CONDUCTORS #6 AWG AND LARGER AT SWITCHBOARDS, TRANSFORMERS, UPS SYSTEMS WITH
<br />COMPRESSION TYPE CONNECTORS. AT PANELBOARDS TERMINATE WITH MECHANICAL LUGS.
<br />L. JOIN OR TAP STRANDED CONDUCTORS (#6 AWG AND LARGER) WITH PRESSURE INDENT TYPE CONNECTORS BURNDY, NEPCO,
<br />OR O.Z./GEDNEY WITH COMPOSITION INSULATING COVERS.
<br />M. SPLICES IN BRANCH( WIRING (#8 AWG AND SMALLER) SHALL BE TWISTED AND MADE MECHANICALLY TIGHT; THEN SECURED WITH
<br />PIGTAIL CONNECTORS, CRIMP TYPE CONNECTORS SHALL NOT BE USED, UTILIZE UL LISTED "SILICON FILLED" PIGTAIL
<br />CONNECTORS WHERE LOCATED IN WET ENVIRONMENTS, OUTDOORS OR IN DATA PROCESSING/COMMUNICATION ROOM RAISED
<br />FLOOR CAVITIES.
<br />N. SUPPORT CONDUCTORS IN VERTICAL RACEWAYS AT THE TOP OF ANY RACEWAY LONGER THAN 20 FEET. INCLUDE ADDITIONAL
<br />SUPPORTS SPACED AT INTERVALS WHICH ARE NOT GREATER THAN 40 FEET. SUPPORT SHALL BE O.Z./GEDNEY TYPE R.
<br />2.07 WIRING DEVICES
<br />A. WIRING DEVICES SHALL BE SPECIFICATION GRADE DECORA UNLESS OTHERWISE NOTED. ALL DEVICES AND PLATES SHALL BE
<br />PLUMB AND FLUSH MOUNTED UNLESS OTHERWISE NOTED. REFER TO SYMBOL LIST.
<br />B. SWITCHES SHALL BE 120/277 VOLTS, RATED AT 20 AMPERES, QUIET OPERATION TYPE, FINISH OF TOGGLE AND DEVICE PLATE
<br />SHALL BE AS DIRECTED BY ARCHITECT.
<br />DIRECTED BY
<br />SIZE AN TYPE T MATCH LIGHTING LOAD. FINISH AS EC T VOLT, WATTAGE S E D PE 0
<br />C. DIMMERS SHA
<br />LL BE RATED AT 120
<br />ARCHITECT. WHERE DIMMER SWITCHES ARE LOCATED NEXT TO SINGLE POLE OR VARIABLE SPEED TYPE SWITCHES, THE
<br />SINGLE POLE/VARIABLE SPEED SWITCHES SHALL MATCH THE DIMMING SWITCH STYLE.
<br />D. STANDARD RECEPTACLES SHALL BE STRAIGHT BLADE, 120 VOLT, 20 AMP, 2 POLE, 3 WIRE, DUPLEX GROUNDING TYPE, NEMA
<br />CONFIGURATION 5-20R. RECEPTACLES SHALL COMPLY WITH NEMA WD 1, NEMA WD 6, UL 498 AND FS W-C-596.
<br />E. GFCI RECEPTACLES, IN ADDITION TO THE REQUIREMENTS OF PARAGRAPH 2.08.D, SHALL BE NON -FEED -THROUGH TYPE, AND
<br />SHALL ADDITIONALLY COMPLY WITH UL 943 CLASS A. GFCI RECEPTACLES SHALL INCLUDE INDICATOR LIGHT THAT SHOWS WHEN
<br />THE GFCI HAS MALFUNCTIONED AND NO LONGER PROVIDES PROPER GFCI PROTECTION.
<br />F. WHERE INSTALLED IN A WET LOCATION, OR OUTDOORS, PROVIDE WET -LOCATION, IN -USE TYPE WEATHERPROOF COVER
<br />PLATES. WEATHERPROOF/WET LOCATION COVER PLATES SHALL BE NEMA 250, COMPLYING WITH TYPE 3R, WEATHER -
<br />RESISTANT, IN -USE TYPE, DIE-CAST ALUMINUM WITH LOCKABLE COVER.
<br />G. MULTIPLE DEVICES AT A COMMON( LOCATION( SHALL BE INSTALLED IN A COMMON MULTIGANG BOX WITH A COMMON
<br />FACEPLATE. DERATE DIMMER SWITCHES PER MANUFACTURER'S REQUIREMENTS WHEN GANGED.
<br />2,08 OCCUPANCY/VACANCY SENSORS
<br />A. CONTRACTORS WORK SHALL INCLUDE ALL LABOR, MATERIALS, TOOLS, APPLIANCES CONTROL HARDWARE, SENSORS, WIRE,
<br />JUNCTION BOXES AND EQUIPMENT NECESSARY FOR A COMPLETELY OPERATIONAL SENSOR CONTROL SYSTEM, AS DESCRIBED
<br />HEREIN.
<br />6, ALL SENSORS SHALL BE EITHER SELF CONTAINED OR INSTALLED AS PART OF OTHER SPECIFIED SYSTEMS OF THE
<br />ULTRASONIC/INFRARED (DUAL TECHNOLOGY) TYPE PROVIDING VOLUMETRIC COVERAGE WITH THE DET
<br />ECTION AREA. SENSORS
<br />SHALL BE SOLID STATE DESIGN AND DESIGN FOR ENERGY CONSERVATION.
<br />C. ALL REQUIRED POWER PACKS AND ROOM CONTROLLERS ARE TO BE PROVIDED WITH TRANSFORMERS AND RELAYS.
<br />D. PROVIDE CONTROL SWITCHES AND STATIONS FOR CEILING SENSOR OPERATION.
<br />E. SENSORS LOCATED IN ADJACENT ROOMS OR SPACES OR CONTROLLING DIFFERENT LIGHT FIXTURES (NOT INTENDED TO BE
<br />PART OF THE SAME ZONE) SHALL OPERATE AT DIFFERENT FREQUENCIES IN ORDER TO PREVENT "CROSS - TALK" BETWEEN
<br />SENSORS.
<br />F. SENSORS SHALL BE ABLE TO BE WIRED IN PARALLEL TO ALLOW COVERAGE OF LARGE AREAS,
<br />G. ALL SENSORS SHALL BE SET AT FULL SENSITIVITY AND MAXIMUM FOOT CANDLES. COVERAGE SHALL REMAIN CONSTANT AFTER
<br />SENSITIVITY CONTROL HAS SET, SENSORS SHALL BE SET AT 10 MINUTE TIME DELAY.
<br />H. BEFORE THE TENANT MOVE -IN DATE AND TURN OVER OF THE PROJECT, THE ELECTRICAL CONTRACTOR SHALL COORDINATE
<br />WITH SENSOR TECHNICAL REPRESENTATIVE TO FIELD ADJUST SENSOR SENSITIVITY AND LOCATION TO ENCOMPASS ENTIRE
<br />ROOM OR AREA WITHOUT NUISANCE TRIPPING FROM ADJACENT AREAS.
<br />I. SENSORS SHALL BE LOCATED AT LEAST 6' -O" FROM HVAC DIFFUSERS. NO REDUCTION IN COVERAGE SHALL OCCUR WHEN AIR
<br />CONDITIONING IS IN OPERATION,
<br />J. FOR ADDITIONAL INFORMATION, MOUNTING REQUIREMENT AND WIRING DIAGRAMS REFER TO MANUFACTURER TECHNICAL
<br />LITERATURE.
<br />2.09 LIGHT FIXTURES
<br />A. ALL LIGHT FIXTURES MOUNTING HARDWARE SHALL MATCH AND BE COORDINATED WITH THE NEW OR EXISTING CEILING
<br />SYSTEM TYPE. ALL FIXTURES SHALL BE EQUIPPED WITH "EARTHQUAKE" CLIPS.
<br />B. ALL FIXTURES THAT ARE EXISTING TO BE REUSED SHALL BE CLEANED. ANY DEFECTIVE OR DAMAGED PARTS SHALL BE
<br />REPAIRED OR REPLACED REPAAPING AND REBALLASTING NOT REQUIRED FOR LED FIXTURES.
<br />C. ALL FIXTURES SHALL BE FREE OF LIGHT LEAKS ABOVE AND BELOW CEILING.
<br />D. FLUORESCENT BALLASTS SHALL BE UL'S CLASS "P" AND SHALL CONFORM TO ANSI AND UL SPECIFICATION WITH LABELS OF
<br />APPROVAL BY UL AND CERTIFICATION BY C.B.M. BALLASTS SHALL COMPLY WITH THE STATE ENERGY CODE, BALLASTS FOR
<br />FLUORESCENT LAMPS SHALL BE OF THE ENERGY SAVING SUPER LOW HEAT DESIGN WITH HIGH POWER FACTOR (0.9 MINIMUM)
<br />AND A HIGH BALLAST FACTOR (0.95 MINIMUM).
<br />E. ELECTRONIC BALLASTS SHALL BE HIGH -FREQUENCY, FULL OUTPUT TYPE FOR USE WITH 265 MA RAPID START T-8 LAMPS. THEY
<br />SHALL HAVE AN 'A' SOUND RATING OR BETTER. ALL ELECTRONIC BALLASTS SHALL HAVE LESS THAN 10% TOTAL HARMONIC
<br />CURRENT DISTORTION (THD). BALLASTS SHALL MEET OR EXCEED FCC REGULATIONS PART 18. ELECTRONIC BALLASTS FOR 1, 2,
<br />3, OR 4 LAMP COMBINATIONS AS WELL AS COMPACT FLUORESCENT LAMPS SHALL BE USED AS REQUIRED TO ACCOMMODATE
<br />THE FIXTURE DESCRIBED IN THE FIXTURE SCHEDULE.
<br />F. WHERE DIMMING OF FLUORESCENT AND/OR LED FIXTURES ARE REQUIRED, THE ELECTRONIC BALLAST AND/OR L.E.D. DRIVER
<br />INSTALLED MUST BE COMPATIBLE WITH THE DIMMING SWITCH/SYSTEM. THE CONTRACTOR SHALL VERIFY COMPATIBILITY WITH
<br />THE BALLAST/DRIVERS AND THE DIMMING SWITCH/SYSTEM,
<br />G. PROVIDE LAMPS SUITABLE FOR LIGHTING FIXTURES IN WHICH THEY ARE USED AND AS INDICATED ON THE DRAWINGS.
<br />FLUORESCENT LAMPS SHALL BE "RAPID START" AND SHALL DELIVER NOT LESS THAN 4100 LUMENS; COLOR SHALL BE WARM
<br />WHITE UNLESSOTHERWISE NOTED. INCANDESCENT LAMPS SHALL BE INSIDE FROSTED AND RATED AT 120 VOLTS UNLESS
<br />OTHERWISE SPECIFIED
<br />H. ALL LIGHT FIXTURES SHALL BE MOUNTED A MINIMUM OF 3" AWAY FROM DUCTWORK AND PIPING INSULATION, WHERE THIS
<br />CANNOT BE ACHIEVED CONTRACTOR SHALL PURCHASE IC RATED FIXTURES AS REQUIRED AS PART OF CONTRACT WORK.
<br />2.10 PULL BOXES; JUNCTION BOXES, AND OUTLET BOXES
<br />A. PULLBOXES, JUNCTION BOXES AND OUTLET BOXES SHALL BE MANUFACTURED FROM GALVANIZED INDUSTRY STANDARD
<br />GAUGE SHEET STEEL.
<br />B. PROVIDE PULL BOXES AND JUNCTION BOXES IN LONG STRAIGHT RUNS OF RACEWAY TO ASSURE THAT CABLES ARE NOT
<br />DAMAGED WHEN THEY ARE PULLED, TO FULFILL REQUIREMENTS AS TO THE NUMBER OF BENDS PERMITTED IN RACEWAY
<br />BETWEEN CABLE ACCESS POINTS, THE ACCESSIBILITY OF CABLE JOINTS AND SPLICES, AND THE APPLICATION OF CABLE
<br />SUPPORTS.
<br />C. PULLBOXES AND JUNCTION BOXES SHALL BE SIZED SO THAT THE MINIMUM BENDING RADIUS CRITERIA SPECIFIED FOR THE
<br />WIRES AND CABLE ARE MAINTAINED.
<br />D. SWITCH RECEPTACLE AND WALL OUTLET BOXES SHALL BE A NOMINAL 4 INCH SQUARE, 1-1/2 INCH OR 2-1/8 INCH DEEP AS
<br />REQUIRED BY CODE WITH A RAISED COVER, UNLESS OTHERWISE INDICATED ON THE DRAWING. PROVIDE 3/8 INCH FIXTURE .
<br />STUD AS REQUIRED, GANGED OUTLET BOXES SHALL BE SUFFICIENT LENGTH TO SUIT CONDITIONS.
<br />E. LIGHTING FIXTURE BOXES SHALL BE 4-INCH OCTAGON WITH 3/8-INCH FIXTURE STUDS, FOR SUSPENDED CEILING WORK,
<br />PROVIDE A 4-INCH OCTAGON BOX WITH REMOVABLE BACEPLATE WHERE REQUIRED.
<br />F. INCLUDE ALL REQUIRED JUNCTION/PULL BOXES AND OUTLET BOXES REGARDLESS OF INDICATIONS ON THE DRAWINGS WHICH
<br />DUE TO SYMBOLIC METHODS OF NOTATION, MAY NOT SHOW ALL THAT ARE ACTUALLY REQUIRED).
<br />G. WHERE BOXES HAVE ANY SINGLE HORIZONTAL DIMENSION LARGER THAN 36", THEY SHALL BE FITTED WITH CABLE SUPPORT
<br />RACKS CONSISTING OF 3/4" DIAMETER STEEL PIPES WITH FLANGED ENDS BOLTED TO THE SIDES OR FRAME OF THE PULL
<br />BOXES. EACH PIPE SUPPORT SHALL BE FITTED WITH A CONTINUOUS FIBER INSULATING SLEEVE. THE PIPE SUPPORTS SHALL BE
<br />ARRANGED IN TIERS CORRESPONDING TO THE CABLES ENTERING AND LEAVING THE BOX. SUFFICIENT PIPE SUPPORT RACKS
<br />SHALL BE INCLUDED WITH THE PULLBOX SO THAT NO CABLE REMAINS UNSUPPORTED FOR A HORIZONTAL DISTANCE GREATER
<br />THAN 36". IN NO CASE SHALL CABLE SUPPORT PIPE RACKS BE MOUNTED SO THAT THEY INTERFERE WITH THE REMOVAL OF
<br />SCREW C01°°ERS.
<br />H. PULL/JUNCTION BOX BARRIERS SHALL BE PROVIDED FOR SYSTEMS AS FOLLOWS:
<br />1. BETWEEN( NORMAL AND EMERGENCY WIRING.
<br />I, BARRIERS IN JUNCTION AND PULL BOXES SHALL BE OF CONDUCTIVE MATERIAL OF ADEQUATE THICKNESS FOR MECHANICAL
<br />STRENGTH( BUT IN NO CASE LESS THAN 1/8 EACH BARRIER SHALL HAVE AN ANGLE IRON FRAMING SUPPORT ALL AROUND.
<br />J. ALL EQUIPMENT, DEVICE BOXES, JUNCTION BOXES, PULLBOXES AND OUTLET BOXES SHALL BE INSTALLED SO AS TO ALLOW
<br />ACCESS TO THE BOX. IF NECESSARY AND APPROVED BY ARCHITECT, PROVIDE ACCESS DOOR OR COVERPLATES IN AREAS
<br />WHERE UNOBSTRUCTED ACCESS IS NOT POSSIBLE.
<br />2.11 SUPPORT AND FASTENINGS
<br />A. ALL SUPPORTS AND FASTENINGS NECESSARY FOR THE SUPPORT OF ELECTRICAL EQUIPMENT SHALL BE IN ACCORDANCE WITH
<br />THE BEST INDUSTRY PRACTICE AND AS SPECIFIED HEREIN.
<br />B. FURNISH AND INSTALL ALL STEEL SUPPORTING MEMBERS, HANGERS, BRACKETS OR OTHER SPECIAL DETAILS REQUIRED AND
<br />(NECESSARY FOR THE PROPER INSTALLATION OF ELECTRIC EQUIPMENT.
<br />C. SUPPORT LESS THAN 2" TRADE SIZE, VERTICALLY RUN CONDUIT AT INTERVALS NO GREATER THAN 8 FEET. SUPPORT SUCH
<br />CONDUITS 2" TRADE SIZE OR LARGER, AT INTERVALS NO GREATER THAN THE STORY HEIGHT, OR 15 FT. WHICHEVER IS
<br />SMALLER.
<br />D. WHERE THEY ARE NOT EMBEDDED IN CONCRETE, SUPPORT LESS THAN 1" TRADE SIZE, HORIZONTALLY RUN CONDUITS AT
<br />INTERVALS NO GREATER THAN 7 FT, SUPPORT SUCH CONDUITS, 1" TRADE SIZE OR LARGER, AT INTERVALS NO GREATER THAN
<br />10 FT.
<br />E. INCLUDE SUPPORTING FRAMES OR RACKS EXTENDING FROM SLAB TO SLAB FOR WORK INDICATED AS BEING SUPPORTED
<br />FROM WALLS UNLESS WALLS OF CONCRETE BLOCK OR SIMILAR STRUCTURAL CONSTRUCTION.
<br />F. INCLUDE SUPPORTING FRAMES OR RACKS FOR EQUIPMENT, INTENDED FOR VERTICAL SURFACE MOUNTING, WHICH IS
<br />REQUIRED I ED IN A FREE STANDING POSITION.
<br />G. EXCEPT FOR BRANCH CIRCUITRY INSTALL ALL CONDUITS IN HUNG CEILING SPACE ON ACCEPTABLE HANGERS AND INSERTS,
<br />CONDUIT OR MC CABLE FOR BRANCH CIRCUITRY SHALL BE SUPPORTED BY CLAMPS OR PIPE STRAPS SECURED TO THE CEILING
<br />SUPPORT SYSTEM (BLACK IRON), FROM STRUCTURAL MEMBERS OR FROM THE DECK. SUPPORT FROM CEILING TEES, CROSS
<br />TEES OR SUPPORT WIRES IS PROHIBITED.
<br />2.12 GROUNDING
<br />A. PROVIDE A GREEN EQUIPMENT GROUND CONDUCTOR IN ALL FEEDERS AND BRANCH CIRCUIT CONDUITS AS INDICATED.
<br />B. PROVIDE SUPPLEMENTARY GROUND BONDING WHERE METALLIC CONDUITS TERMINATE AT METAL CLAD EQUIPMENT (OR AT
<br />THE METAL PULL BOX OF EQUIPMENT) FOR WHICH A GROUND BUS IS SPECIFIED WITH A BUSHING OF THE GROUNDING TYPE
<br />CONNECTED INDIVIDUALLY TO GROUND BUS.
<br />C ALL GROUND WIRES SHALL BE SUITABLY PROTECTED FROM MECHANICAL INJURY.
<br />D. PROVIDE ISOLATED GROUND BUS BAR AND CONDUCTORS WHERE INDICATED ON DRAWINGS.
<br />2,13ACCEPTABLE MANUFACTURERS
<br />A. PANELBOARDS; SIEMENS, EATON, GE (ABB), OR SCHNEIDER ELECTRIC
<br />B. DISCONNECT SWITCHES: SIEMENS, EATON, GE (ABB), OR SCHNEIDER ELECTRIC
<br />C. CIRCUIT BREAKERS: SIEMENS, EATON, GE (ABB), OR SCHNEIDER ELECTRIC
<br />D. FUSES: BUSSMAN, MERSEN (FERRAZ SHAWMUTT)
<br />E. RACEWAY: ALLIED TUBE & CONDUIT, WHEATLAND TUBE, OR REPUBLIC
<br />F. WIRE/CABLE: GENERAL CABLE, SOUTHWIRE, CERRO & SIMPLEX
<br />G. METAL CLAD CABLE: AFC, SOUTHWIRE, KAF-TECH
<br />H. JUNCTION/PULL BOXES: APPLETON ELECTRIC, CROUSE HINDS OR O.ZJ GEDNEY CO,
<br />1. TRANSFORMERS: SIEMENS, GE (ABS), OR SCHNEIDER ELECTRIC
<br />J. FIRE STOP MATERIAL: HILTI, 3M ( NOTE: MATERIAL MUST BE ACCEPTABLE TO LOCAL AHJ)
<br />K. FITTINGS, COUPLINGS, BUSHINGS, CONNECTORS: OZ GEDNEY, BURNDY, NEPCO, THOMAS AND BETTS
<br />L LAMPS: AS SPECIFIED BY ARCHITECT
<br />M. D A DRIVERS: SPECIFIED BY ARCHITECT
<br />R S S S E
<br />N. OCCUPANCY SENSORS: WATT STOPPER, LUTRON
<br />0. LIGHT SWITCHES: LEGRAND PASS & SEYMOUR, HUBBELL, LEVITON, LUTRON
<br />P. DIMMER SWITCHES: LEGRAND PASS & SEYMOUR TITAN, LUTRON T-STAR (NT/NTLV SERIES)
<br />Q. RECEPTACLES: LEGRAND PASS & SEYMOUR, HUBBELL, LEVITON
<br />2.14 FIRE ALARM SYSTEM
<br />A. THE ELECTRICAL CONTRACTOR SHALL FURNISH NEW FIRE ALARM EQUIPMENT AS SHOWN AND CONNECT TO THE EXISTING FIRE
<br />ALARM SYSTEM. RETAIN AND COORDINATE WITH THE BASE BUILDING FIRE ALARM SYSTEM VENDOR PRIOR TO ANY WORK. THE
<br />ELECTRICAL CONTRACTOR'S BID SHALL INCLUDE ANY FIRE ALARM VENDOR'S COST FOR TIE-IN'S, PROGRAMMING, INSPECTIONS,
<br />MODIFICATIONS, COMPONENTS, DEVICES, PARTS, ETC.
<br />B. WHERE CONSTRUCTION INTERFERES WITH EXISTING FIRE ALARM EQUIPMENT, OR IT IS LOCATED ON EXISTING WALLS TO BE
<br />DEMOLISHED, IT SHALL BE THE RESPONSIBILITY OF THIS CONTRACTOR TO NOTIFY THE BUILDING OWNER AND RELOCATE AT
<br />OWNER'S DIRECTION(.
<br />C IT IS THIS CONTRACTOR'S RESPONSIBILITY TO MAINTAIN FIRE ALARM SPEAKERS, STROBES, SMOKE DETECTORS, FIRE WARDEN
<br />STATIONS AND OTHER FIRE SAFETY DEVICES IN OPERATION AT ALL TIMES.
<br />D. FIRE ALARM SYSTEM VENDOR AND CONTRACTOR SHALL BE PRESENT DURING ALL TESTS AND FIRE DEPARTMENT INSPECTIONS
<br />AND SUBSEQUENT INSPECTIONS AS PART OF CONTRACT WORK. CONTRACTOR SHALL BE RESPONSIBLE FOR THE PREPARATION
<br />AND FILING OF ANY AND ALL NECESSARY DRAWINGS, FORMS, ETC. REQUIRED BY THE LOCAL AUTHORITIES HAVING
<br />ASSOCIATED WITH T AFOREMENTIONED WORK SHALL B INCLUDED
<br />T PAY ALL FEES. ASSOC 11 HE 0 S E CONTRACTOR 0 S S JURISDICTION.
<br />IN BASE BID.
<br />E. ANY AND ALL TIE-IN WITH BASE BUILDING SYSTEM IF REQUIRED SHALL BE PERFORMED BY BASE BUILDING FIRE ALARM SYSTEM
<br />TED BASE BUILDING SYSTEM CONTRACTOR H WORK HALL BE COORDINATED WITH B T CONTRACTORS. ALL SUCH 0 S 0
<br />F. PRIOR TO SCHEDULING FIRE DEPARTMENT INSPECTION AND FINAL SYSTEM TEST, THIS CONTRACTOR SHALL COORDINATE WITH
<br />BASE BUILDING FIRE ALARM CONTRACTOR AND BUILDING MANAGEMENT AND PERFORM A PRE -TEST OF THE FIRE ALARM
<br />SYSTEM.
<br />G. ALL SYSTEM TESTING SHALL BE PERFORMED DURING NON -BUSINESS HOURS OR DURING THE WEEKENDS AT NO EXTRA COST
<br />TO THE CLIENT, CONTRACTOR SHALL COORDINATE WITH BUILDING MANAGEMENT AND BASE -BUILDING FIRE ALARM SYSTEM
<br />CONTRACTORS FOR BUILDING REQUIREMENTS AND SCHEDULING OF SUCH TESTS
<br />0
<br />V
<br />o U
<br />10 d
<br />(3 -2 c
<br />C °� u
<br />a, �
<br />v a �
<br />� z 3:
<br />v) 0 i
<br />0) C �,-
<br />NQo:o
<br />o � � CD -
<br />U.Q)o" �o
<br />G L0 - C)
<br />00 0-
<br />V3 ® � -_
<br />75
<br />Iin
<br />Cl
<br />I
<br />s
<br />I
<br />73
<br />MNMMMI
<br /><
<br />ME
<br />-
<br />11
<br />III b� • ♦.
<br />,f
<br />zzzzz
<br />111"
<br />'% R;
<br />r
<br />I °
<br />� ( , . k
<br />z
<br />Lu
<br />0
<br />0
<br />z
<br />0
<br />U
<br />a
<br />O Ln
<br />u n
<br />ORIGINAL SHEET - ARCH D
<br />
|