Architectural Comments: <br />1. The architectural plans on Sheets A3.01-A through A3.03-B split the plans between two <br />sheets. The break line is positioned in the same place for both halves of the building <br />such that the construction along this line is not clear. The; break line should be adjusted <br />so there: is an overlapping region between the sheets. Alternatively, the drawing scale <br />allows the entire plan to be shown on a single; sheet. See the structural plans. The plan <br />sheets should be revised. See Section R106.1.1. <br />Response: The break line has been adjusted so there is an overlapping. Please refer to <br />revised A3.01, A3.02 & A3.03 <br />2. Additional smoke and CO alarms should be provided outside of Bedrooms 112, 212, and <br />216. See Sections R314.2.2(2) (WAC) and R315.3 (WAC). <br />Response: Smoke & CO alarms added. Please refer to revised A3.01 & A3.02 <br />3. The energy code requirements on Sheet A1.01-A specify the wall insulation as "R-21 plus <br />R-4". The R-4 insulation should be continuous. This should also be revised in the <br />credits listed below. See WSEC Table. R406.2. <br />Response: Please refer to revised A1.01 & A9.01. <br />4. The thermal ratings for the components of the exterior envelop are listed in the "2015 <br />WA State Energy Code" section of the notes on Sheet A1.01-A. The details on Sheets <br />A9.01 and A9.02 are not consistent. Other references, sections, and details in the <br />drawings may similarly, be incorrect. See Section 106.1.1 and WSEC Table R406.2. <br />Examples Include but are not limited to: <br />a. The building sections on Sheets A5.01 through A5.03 should specify R-38 insulation <br />at the first floor. Alternatively, the insulation should be shown and reference the <br />notes on Sheet A1.01-A. <br />b. Exterior Wall Type D in Detail 04/A9.01 specifies "R-21+R4 batt insulation". This <br />should be R-21 plus R-46 insulation. <br />c. Floor Assembly Detail 05/A9.01 specifies R-30 insulation. This should be minimum <br />R-38. <br />Response: Floor & wall specifications revised. Please refer to revised A5.01-A5.03, A1.01 & <br />A9.01-A9.02. <br />Design Lyric LLC (425) 836-4800 9824 223rd Place NE, Redmond, WA 98053 <br />