1 DRAWING SHEET INDEX I FIRE ALARM SYMBOL LEGEND I APPLICABLE CODES AND STANDARDS I SCOPE OF WORK 1 <br />SHEET <br />DESCRIPTION <br />FA001 <br />INFORMATION SHEET <br />FA101 <br />KEY PLAN - AREA OF WORK AND ENLARGED CANOPY VIEW <br />QTY <br />SYMBOL <br />DESCRIPTION <br />BRAND <br />MODEL <br />oQ <br />TYPE <br />PANELS & ANNUNCIATORS <br />1(E) <br />FACP <br />FIRE ALARM CONTROL PANEL <br />SILENT <br />KNIGHT <br />MODEL 5208 <br />MFG <br />MFG <br />N/A <br />N/A <br />INITIATING DEVICES <br />1(E) <br />© <br />MANUAL PULL STATION, DOUBLE ACTION <br />EXISTING <br />EXISTING <br />4A <br />A <br />l(E) <br />SOP <br />PHOTOELECTRIC SMOKE DETECTOR <br />EXISTING <br />EXISTING <br />4K <br />A <br />1 FIRE ALARM CABLE LEGEND I ABBREVIATIONS LEGEND <br />CABLE TYPE <br />NFPA 72 CIRCUIT TYPE <br />TYPICAL DEVICES <br />CONDUCTORS <br />A <br />SIGNALING LINE CIRCUIT (SLC) <br />ADDRESSABLE INITIATING DEVICES <br />18/2* <br />B <br />FIRE ALARM ANNUNCIATOR CIRCUIT (FAAC) <br />FIRE ALARM ANNUNCIATOR <br />18/2* <br />C <br />24VDC POWER CIRCUIT <br />DEVICES REQUIRING 24VDC TO OPERATE <br />14/2* SOLID <br />D <br />DOOR HOLDER CIRCUIT <br />DOOR HOLDER DEVICES REQUIRING 24VDC <br />14/2* SOLID <br />E <br />SERIAL COMMUNICATION CIRCUIT (RS232) <br />INTERNAL/EXTERNAL PRINTERS <br />18/2* <br />H <br />AUDIBLE CIRCUIT (HORN ONLY) <br />AUDIBLE DEVICES (HORNS) <br />14/2* SOLID <br />K <br />REMOTE TEST SWITCH CIRCUIT (RTS) <br />REMOTE TEST SWITCH <br />14/2* SOLID <br />NJ <br />NETWORK COMMUNICATION CIRCUIT (RS485) <br />MULTIPLE FACP NODES <br />18/2* <br />R <br />RELAY CIRCUIT <br />AC UNIT/HVLS FAN <br />14/2* SOLID <br />S <br />SPEAKER APPLIANCE CIRCUIT (SPK) <br />SPEAKER DEVICES (SPEAKERS) <br />16/2* <br />`J <br />NOTIFICATION APPLIANCE CIRCUIT (NAC) <br />AUDIBLE/VISUAL DEVICES (HORNS/STROBES) <br />14/2* SOLID <br />Z <br />ZONE INDICATING DEVICE CIRCUIT (IDC) <br />CONVENTIONAL FIRE ALARM APPLIANCES <br />16/2* <br />FIRE ALARM CABLE NOTE(S): <br />1. *WIRE TYPE FOR ALL FIRE ALARM EQUIPMENT (INITIATING, NOTIFICATION, ETC.) SHALL BE INSTALLED PER MANUFACTURER <br />REQUIREMENTS, CODE REQUIREMENTS & SPECIFICATIONS. WIRE TYPES SHALL BE: FPL, FPLR, & FPLP. INSTALLING CONTRACTOR TO <br />DETERMINE TYPE OF WIRE TO BE USED. <br />AC = ABOVE CEILING <br />AFF = ABOVE FINISHED FLOOR <br />AHJ = AUTHORITY HAVING JURISDICTION <br />ALM = ALARM <br />ANN = ANNUNCIATOR <br />BMS = BUILDING MANAGEMENT SYSTEM <br />C = CEILING MOUNTED <br />CD = CANDELA RATING <br />DET = DETECTOR <br />DGP = DATA GATHERING PANEL <br />E = EXISTING TO REMAIN <br />EOL = END OF LINE <br />EPO = EMERGENCY POWER OFF <br />FAA = FIRE ALARM ANNUNCIATOR <br />FACP = FIRE ALARM CONTROL PANEL <br />FATC = FIRE ALARM TERMINAL CABINET <br />FBO = FURNISHED BY OTHERS <br />FCC = FIRE COMMAND CENTER <br />FSD = FIRE SMOKE DAMPER <br />FTR = FIRE ALARM TRANSPONDER <br />H = HIGH HUMIDITY <br />HT = HEIGHT <br />HVAC = HEATING VENTILATION & AIR CONDITIONING <br />IMS = INFORMATION MANAGEMENT SYSTEM <br />MAX = MAXIMUM <br />MIN = MINIMUM <br />N/A = NOT APPLICABLE <br />NAC = NOTIFICATION APPLIANCE CIRCUIT <br />NDU = NETWORK DISPLAY UNIT <br />NEC = NATIONAL ELECTRIC CODE <br />NFPA = NATIONAL FIRE PROTECTION ASSOCIATION <br />NIC = NOT IN CONTRACT <br />NPU = NETWORK PROCESSING UNIT <br />NTS = NOT TO SCALE <br />PAP = PRE -ACTION PANEL <br />RC = EXISTING TO REMOVE AND COVER <br />RD = EXISTING DEVICE TO BE RELOCATED <br />RL = RELOCATED DEVICE <br />RR = REMOVE EXISTING & REPLACE WITH NEW <br />SCC = STATUS COMMAND CENTER <br />SLC = SIGNALING LINE CIRCUIT <br />SMK = SMOKE <br />SUPV = SUPERVISORY <br />TAC = TRUEALERT ADDRESSABLE CONTROLLER <br />TRBL = TROUBLE <br />TS = TAMPER SWITCH <br />TYP = TYPICAL <br />UON = UNLESS OTHERWISE NOTED <br />VCC = VOICE COMMAND CENTER <br />VT = VALVE TAMPER <br />W = WATTAGE <br />W( = WITH <br />W/0 = WITHOUT <br />WF = WATERFLOW <br />WG = WIRE GUARD <br />WP = WEATHERPROOF <br />XP = EXPLOSION PROOF <br />AUTHORITY HAVING JURISDICTION: CITY OF EVERETT FIRE DEPARTMENT <br />PROJECT BUILDING DATA: <br />• BUILDING STORIES: 1 STORY <br />• OCCUPANCY TYPE: S-1,B <br />• FIRE PROTECTION: FULLY SPRINKLED <br />CODE REFERENCES: <br />+ 2015 - WASHINGTON FIRE CODE (2015 IFC WITH AMENDMENTS) <br />• 2015 - WASHINGTON BUILDING CODE (2015 IBC WITH AMENDMENTS) <br />• AUTOMATIC FIRE DETECTION & SUPRESSION SYSTEM ORDINENCE NO. <br />1902-92 <br />STANDARDS: <br />• 2013 NFPA 72 - NATIONAL FIRE ALARM & SIGNALING CODE <br />• 2014 NFPA 70 - NATIONAL ELECTRICAL CODE <br />1. THE TRUCK CANOPY TENANT IMPROVEMENT SHALL CONSIST OF THE ADDITION OF NEW SPRINKLER MONITORING EQUIPMENT IN THE CANOPY AREA. CONTRACTOR SHALL <br />INTERCONNECT NEW SPRINKLER MONITORING EQUIPMENT WITH THE EXISTING FIRE ALARM SYSTEM. THE INTENT IS TO MONITOR THE NEW POINTS WITH THE EXISTING FIRE ALARM <br />SYSTEM. THE EXISTING FACP IS A SILENT KNIGHT 5208 ADDRESSABLE FRCP AND IS TO REMAIN (CONTRACTOR TO CONFIRM). CONTRACTOR TO COORDINATE THE LOCATIONS AND <br />TYPES OF SPRINKLER EQUIPMENT TO BE INSTALLED IN THE CANOPY AREA WITH THE SPRINKLER CONTRACTOR PRIOR TO ANY DEMOLITION OR INSTALLATION. <br />2. THE POWER CIRCUIT TO THE FACP AND TO THE FIRE ALARM POWER SUPPLIES SHALL BE ON A DEDICATED 120V, 20A BRANCH CIRCUIT BREAKER, AND SHALL HAVE A RED MARKING, <br />LOCK -ON PROVISION AND SHALL BE IDENTIFIED AS "FIRE ALARM CIRCUIT CONTROL." THE LOCATION OF THE CIRCUIT DISCONNECT MEANS (CIRCUIT BREAKER) SHALL BE <br />PERMANENTLY IDENTIFIED AT THE FIRE ALARM CONTROL UNIT. <br />3. CONTRACTOR SHALL FURNISH ALL EQUIPMENT, MATERIALS, TOOLS, LABOR, ENGINEERING, SUBMITTAL DRAWINGS, SCHEDULES, PERMITS, PERMIT FEES, APPROVALS, ETC., NECESSARY <br />FOR A COMPLETE FIRE ALARM SYSTEM FOR THE TENANT IMPROVEMENT AREAS ONLY AS DESCRIBED WITHIN THESE DRAWINGS AND AS REQUIRED BY ALL LOCAL AND NATIONAL <br />CODES AND ORDINANCES. CONTRACTOR SHALL NOT DELETE OR ADD ANY EQUIPMENT OR DEVICES WITHOUT WRITTEN DIRECTIVE OF THE OWNER AND ENGINEER. <br />4. CONTRACTOR SHALL FULLY TEST ALL FIRE ALARM EQUIPMENT, DEVICES, AND CIRCUITS UPON COMPLETION OF INSTALLATION AND PREPARE NEW ULC CERTIFICATE. ALL <br />DOCUMENTATION SHALL BE COPIED TO PROJECT ENGINEER AS PART OF THE REQUIRED PROJECT CLOSE-OUT DOCUMENTATION. <br />S. CONTRACTOR IS RESPONSIBLE TO COORDINATE INSTALLATION WITH ALL TRADES AND TO MEET ALL PROJECT SCHEDULES AND DEADLINES. <br />6. CONTRACTOR SHALL PROVIDE COMPLETE SITE SURVEY TO THE BUILDING PRIOR TO BID IN ORDER TO FAMILIARIZE THEMSELVES WITH THE PROPOSED SCOPE OF WORK AREA, <br />7. CONTRACTOR TO BE A LICENSED VENDOR OF THE FIRE ALARM SYSTEM EQUIPMENT AND BE FULLY CAPABLE OF MODIFYING AND REPROGRAMMING THE FACP AND RELATED <br />EQUIPMENT. <br />8. CONTRACTOR SHALL MONITOR ANY CARBON MONOXIDE DETECTORS THAT ARE PROVIDED BY THE MEP CONTRACTOR. COORDINATE EXACT DEVICE LOCATION, INTERFACE <br />REQUIREMENTS, AND QUANTITY WITH THE MEP CONTRACTOR. <br />1 CONDUIT PERCENTAGE FILL CALCULATIONS I DEVICE MOUNTING REQUIREMENTS I PROJECT CONTACT INFORMATION I CONTRACTOR NOTES <br />PER NFPA 70 TABLE 140% FILL (FOR REFERENCE ONLY) <br />DESCRIPTION <br />DIA IN. <br />AREA SQ. IN. <br />40% AREA <br />1/2" EMT CONDUIT <br />0.622 <br />0,304 <br />0.122 <br />3/4" EMT CONDUIT <br />0.824 <br />0.533 <br />0.213 <br />I" EMT CONDUIT <br />1.049 <br />0.664 <br />0.346 <br />1-1/4" CONDUIT <br />1.380 <br />1.496 <br />0.598 <br />1-1/2" EMT CONDUIT <br />1.610 <br />2.036 <br />1 0.814 <br />2" EMT CONDUIT <br />2.067 <br />3.356 <br />_1342 <br />KEYNOTE: <br />REFERENCE POINT-TO-POINT DEVICE DETAILS OR PRODUCT <br />SUBMITTAL DATA SHEETS FOR BACK BOX REQUIREMENTS OF <br />INDIVIDUAL UNITS. <br />2O MANUAL PULL STATION INSTALLATION TO BE IN <br />COMPLIANCE WITH IFC, ADA & JURISDICTIONAL <br />REQUIREMENTS. <br />FINISHED CEILING <br />OR HIGH CEILING <br />PER NFPA 72 AUDIO/VISUAL <br />AND VISUAL DEVICES LOCATION. <br />WALL MOUNTED APPLIANCES <br />SHALL BE MOUNTED SUCH THAT <br />THE ENTIRE LENS IS NOT LESS <br />THAN 80" INCHES AND NOT <br />GREATER THAN 96" INCHES <br />ABOVE THE FINISHED FLOOR <br />1 SITE PLAN I SEQUENCE OF OPERATIONS <br />Op <br />Eo C M <br />SMOKE <br />AUDIOVISUAL <br />DETECTOR <br />ON CEILING <br />NOTIFICATION DEVICE <br />��{ WP <br />EiWP <br />PULL STATION <br />©— <br />48" MAX TO THE HIGHEST POINT <br />OF THE ACTIVATING HANDLE OR <br />LEVER PER IFC REQUIREMENTS <br />FINISHED FLOOR <br />NOTES: <br />1. TROUBLE CONDITIONS INCLUDING: WIRING SHORT, OPEN C <br />GROUND FAULT, LOW BATTERY, BATTERY FAILURE, AC LOSS, <br />DEVICE, EQUIPMENTAL FUNCTION, EQUIPMENT FAILURE. <br />2. THIS GENERAL ALARM SEQUENCE OF OPERATIONS IS SHOVA <br />REFERENCE ONLY. THE EXISTING SEQUENCE OF OPERATION <br />REMAIN THE SAME. AUTHORIZED CONTRACTOR TECHNICIA <br />BECOME FAMILIAR WITH THE EXISTING SEQUENCE OF OPER, <br />SHALL PROGRAM THE NEW DEVICES ACCORDINGLY. <br />CYCTFM TNPI ITC <br />ARCHITECT: <br />MG2 <br />1101 SECOND AVENUE, SUITE 100 <br />SEATTLE, WA. 98101 <br />PHONE: 206.962.6500 <br />WWW.MG2.COM <br />FIRE ALARM CONSULTING FIRM: <br />NRG FIRE CONSULTING, LLC <br />7511 GREENWOOD AVENUE NORTH #600 <br />SEATTLE, WA 98103 <br />PHONE: 206.789.0165 <br />WWW.NRGFIRECONSULTING.COM <br />FIRE ALARM SYSTEM DESIGNER: <br />DESIGNER OF RECORD: SEAN E. PISONI, CET <br />NICET #: 93223 <br />EXPIRATION DATE: DECEMBER 2020 <br />AUTHORITY HAVING JURISDICTION: <br />CITY OF EVERETT FIRE DEPARTMENT <br />OFFICE OF THE FIRE MARSHAL <br />2930 WETMORE AVENUE, SUITE 7-A <br />EVERETT, WA 98201 <br />PHONE: 425.257.8120 <br />FAX: 425.257.8139 <br />RFMARKC <br />1 <br />SMOKE DETECTOR <br />• <br />• <br />• <br />• <br />• <br />• <br />• <br />• <br />1 <br />2 <br />CARBON MONOXIDE DETECTOR <br />• <br />• <br />• <br />• <br />• <br />• <br />• <br />2 <br />3 <br />MANUAL PULL STATION <br />• <br />• <br />• <br />• <br />• <br />• <br />• <br />• <br />3 <br />4 <br />DUCT DETECTOR <br />• <br />• <br />• <br />• <br />• <br />+ <br />4 <br />5 <br />WET SPRINKLER SYSTEM WATERFLOW SWITCH <br />• <br />• <br />• <br />• <br />• <br />• <br />• <br />• <br />• <br />5 <br />6 <br />WET/DRY SPRINKLER SYSTEM TAMPER SWITCH <br />• <br />• <br />• <br />• <br />• <br />6 <br />7 <br />DRY SPRINKLER SYSTEM ALARM PRESSURE SWITCH <br />• <br />• <br />• <br />• <br />• <br />•1 <br />7 <br />8 <br />DRY SPRINKLER SYSTEM HIGH/LOW PRESSURE SWITCH <br />• <br />• <br />• <br />• <br />• <br />8 <br />9 <br />POST INDICATOR VALVE SWITCH <br />• <br />• <br />• <br />• <br />• <br />9 <br />10 <br />BACKFLOW PREVENTOR <br />• <br />• <br />• <br />+ <br />• <br />10 <br />11 <br />FIRE PUMP RUNNING <br />• <br />• <br />• <br />• <br />• <br />11 <br />12 <br />FIRE PUMP POWER LOSS <br />• <br />• <br />+ <br />• <br />• <br />12 <br />13 <br />FIRE PUMP PHASE REVERSAL <br />• <br />+ <br />• <br />• <br />+ <br />13 <br />14 <br />TROUBLE SEE NOTE 1 <br />• <br />+ <br />• <br />• <br />• <br />14 <br />1. THESE DRAWINGS ARE PERFORMANCE BASED ONLY AND DO NOT SHOW ALL FIRE ALARM EQUIPMENT. IT IS THE CONTRACTOR'S RESPONSIBILITY TO VERIFY LOCATION AND <br />CONDITION OF ALL EXISTING FIRE ALARM EQUIPMENT, CIRCUITING, CONDUITS, ETC, AND CONFIRM REQUIREMENTS OF NEW REQUIRED FIRE ALARM EQUIPMENT WITH LOCAL AHJ. <br />CONTRACTOR IS RESPONSIBLE FOR ALL PERMITS, PLANS, CALCULATIONS, APPROVAL, ETC. <br />2. THE FIRE ALARM SYSTEM SHALL BE MONITORED BY AN APPROVED U.L. CENTRAL STATION MONITORING SERVICE. INTERFACE WILL BE FULLY LISTED AND APPROVED FOR THIS <br />PURPOSE. <br />3. SIGNALING LINE CIRCUITS SHALL BE CLASS A, PER NFPA 72, CURRENT ADOPTED ADDITION. NOTIFICATION AND INITIATING CIRCUITS SHALL BE CLASS B, PER NFPA 72, CURRENT <br />ADOPTED EDITION. A MINIMUM OF 10% EXCESS CAPACITY IS REQUIRED ON ALL NOTIFICATION CIRCUITS. <br />4. INSTALLATION OF DEVICES SHALL BE IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS. POWER LIMITED AND NON -POWER LIMITED FIELD WIRING MUST BE INSTALLED <br />WITHIN THE FACP ENCLOSURE IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS AND APPLICABLE ELECTRICAL CODES. <br />5. ALL WIRE SHALL BE SOLID CONDUCTORS OR COPPER, MINIMUM SIZE OF NO.18 AWG, AND INSULATION RATED AT 600V. ALL WIRING SHALL COMPLY WITH MANUFACTURER'S <br />RECOMMENDATIONS AND BE INSTALLED ACCORDING TO APPLICABLE ELECTRICAL CODES. ALL WIRING SHALL BE APPROPRIATELY COLOR -CODED, AND PERMANENT WIRE MARKERS <br />SHALL BE USED TO IDENTIFY THE TERMINATIONS FOR, EACH CIRCUIT AT THE CONTROL PANEL. REFER TO 'APPLICABLE CODES & STANDARDS' FOR SPECIFIC CODE REFERENCES. <br />6. ALL CONDUITS, BOXES, FITTINGS, ETC. WITHIN FINISHED AREAS SHALL BE CONCEALED BEHIND DRYWALL, DROP CEILING OR OTHER FINISHED SURFACES. EXPOSED WIRING IS NOT <br />ALLOWED FOR FIRE ALARM WIRING. CONTRACTOR SHALL MAINTAIN ALL AREAS OF THE BUILDING IN A NEAT AND WORKMANLIKE MANNER. <br />7. ALL WIRING, CONDUIT, BOXES (UNLESS OTHERWISE INDICATED), FITTINGS, COUPLINGS, CONNECTORS, STRAPS, SUPPORTS, PULL -LINES, BUSHINGS, ETC. SHALL BE PROVIDED AND <br />INSTALLED BY A LICENSED ELECTRICAL CONTRACTOR. ALL CONDUIT SIZES AND BACK BOX SIZES SHALL BE CONFIRMED WITH THE FIRE ALARM EQUIPMENT SUPPLIER. ALL WORK SHALL <br />MEET OR EXCEED THE REQUIREMENTS OF THE NATIONAL ELECTRICAL CODE. <br />8. MAINTAIN THE FIRE RESISTANCE INTEGRITY OF ALL WALL, CEILING, AND ROOF ASSEMBLIES ANYTIME THAT WORK IS NOT ACTIVELY BEING PERFORMED. <br />9. THE ELECTRICAL CONTRACTOR SHALL PROVIDE ALL LINE VOLTAGE (120 V. MAX.) AND LOW -VOLTAGE (UP TO 50 VAC/VDC) CIRCUITING IN SEPARATE CONDUIT. CONDUIT FILLS SHALL <br />BE NOT MORE THAN 75% OF THAT ALLOWED BY THE NATIONAL ELECTRICAL CODE. <br />10. SYSTEM OPERATION, TESTING, TURN OVER, WARRANTY, COMPLIANCE, AND AFTER MARKET SERVICE SHALL BE PROVIDED BY THE APPROVED FIRE ALARM VENDOR. <br />11. NRG FIRE CONSULTING OR THE ENGINEER OF RECORD SHALL NOT BE RESPONSIBLE FOR THE CONTRACTOR'S FAILURE TO CARRY OUT THE CONSTRUCTION WORK IN ACCORDANCE <br />WITH THE CONTRACT DOCUMENTS, NOR SHALL THEY BE REQUIRED TO SUPERVISE THE CONDUCT OF THE CONSTRUCTION PROCEDURES FOLLOWED BY THE CONTRACTOR, <br />SUBCONTRACTORS, THEIR RESPECTIVE EMPLOYEES OR ANY OTHER PERSON AT THE JOB SITE OTHER THAN NRG FIRE CONSULTING, LLC REPRESENTATIVES AND/OR THE ENGINEER OF <br />RECORD. <br />12. THE DESIGNER AND/OR THE ENGINEER OF RECORD SHALL NOT BE RESPONSIBLE FOR UNAUTHORIZED CHANGES TO OR USE OF THESE PLANS. ALL CHANGES MUST BE IN WRITING <br />AND MUST BE APPROVED BY THE PROJECT ARCHITECT. <br />13. THE FIRE ALARM VENDOR AND/OR INSTALLING CONTRACTOR SHALL CONTACT THE ARCHITECT WITH COMMENTS OR EXCEPTIONS TO THE APPROVED PLANS AND SPECIFICATIONS <br />PRIOR TO BID. THE CONTRACTOR ASSUMES RESPONSIBILITY FOR ALL WORK SHOWN ON THE APPROVED PLANS AND MODIFICATIONS SHALL NOT BE ALLOWED WITHOUT APPROVAL <br />FROM THE PROJECT ARCHITECT. <br />14, THE INSTALLATION CONTRACTOR SHALL COORDINATE ALL FINAL EQUIPMENT LOCATIONS WITH THE LATEST PROJECT FIXTURE PLANS PRIOR TO INSTALLATION. CONTRACTOR TO <br />COORDINATE ALL WIRING, CONDUITS, BOXES, AND EQUIPMENT WITH OTHER SYSTEM CONTRACTORS TO AVOID POTENTIAL CONFLICTS AND EQUIPMENT OBSTRUCTIONS. <br />15. ANY DISCREPANCIES BETWEEN PLANS WILL REQUIRE THE MORE STRINGENT TO BE BID ON AND INSTALLED. <br />16. CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING ANY REQUIRED MECHANICAL LIFTS TO PERFORM INSTALLATION OF THE FIRE ALARM SYSTEM. <br />17. CONTRACTOR SHALL UPDATE THE AS -BUILT DRAWING SET DAILY WITH JOB PROGRESS. RETURN THE AS -BUILT DRAWING SET TO THE BUILDING OWNER NO LATER THAN 7 DAYS <br />AFTER FINAL TEST. <br />18. CONTRACTOR IS RESPONSIBLE FOR REMOVING ANY OLD FIRE ALARM EQUIPMENT, PANELS, BOXES, CONDUIT, WIRING, ETC. FROM THE BUILDING PRIOR TO COMPLETION OF THE <br />PROJECT. THESE REMOVED ITEMS SHALL BE REMOVED FROM JOB SITE AND DISPOSED OF PROPERLY ACCORDING TO THE LOCAL JURISDICTION. <br />e <br />7611 Greenwood Avenue, #600 <br />Seattle, WA 98103 <br />(21 6) 789-0165 <br />nr # 4econsuffin .r.om <br />DWS5 <br />EVERETT DISTRIBUTION CENTER <br />6617 ASSOCIATED BLVD. <br />EVERETT, WA 98203 <br />i• <br />• <br />1 <br />i� <br />i <br />• <br />DESCRIPTION A DATE <br />CIA REVIEW SET 05/22/2020 <br />90% QA REVIEW SET 06/1912020 <br />PERMIT SET 09/17/2020 <br />JOB NUMBER <br />20574401E <br />DRAWN BY CHECKED BY <br />DRS SEP <br />SHEET TITLE <br />INFORMATION SHEET - <br />