1 DRAWING SHEET INDEX I FIRE ALARM SYMBOL LEGEND I APPLICABLE CODES AND STANDARDS I SCOPE OF WORK 1
<br />SHEET
<br />DESCRIPTION
<br />FA001
<br />INFORMATION SHEET
<br />FA101
<br />KEY PLAN - AREA OF WORK AND ENLARGED CANOPY VIEW
<br />QTY
<br />SYMBOL
<br />DESCRIPTION
<br />BRAND
<br />MODEL
<br />oQ
<br />TYPE
<br />PANELS & ANNUNCIATORS
<br />1(E)
<br />FACP
<br />FIRE ALARM CONTROL PANEL
<br />SILENT
<br />KNIGHT
<br />MODEL 5208
<br />MFG
<br />MFG
<br />N/A
<br />N/A
<br />INITIATING DEVICES
<br />1(E)
<br />©
<br />MANUAL PULL STATION, DOUBLE ACTION
<br />EXISTING
<br />EXISTING
<br />4A
<br />A
<br />l(E)
<br />SOP
<br />PHOTOELECTRIC SMOKE DETECTOR
<br />EXISTING
<br />EXISTING
<br />4K
<br />A
<br />1 FIRE ALARM CABLE LEGEND I ABBREVIATIONS LEGEND
<br />CABLE TYPE
<br />NFPA 72 CIRCUIT TYPE
<br />TYPICAL DEVICES
<br />CONDUCTORS
<br />A
<br />SIGNALING LINE CIRCUIT (SLC)
<br />ADDRESSABLE INITIATING DEVICES
<br />18/2*
<br />B
<br />FIRE ALARM ANNUNCIATOR CIRCUIT (FAAC)
<br />FIRE ALARM ANNUNCIATOR
<br />18/2*
<br />C
<br />24VDC POWER CIRCUIT
<br />DEVICES REQUIRING 24VDC TO OPERATE
<br />14/2* SOLID
<br />D
<br />DOOR HOLDER CIRCUIT
<br />DOOR HOLDER DEVICES REQUIRING 24VDC
<br />14/2* SOLID
<br />E
<br />SERIAL COMMUNICATION CIRCUIT (RS232)
<br />INTERNAL/EXTERNAL PRINTERS
<br />18/2*
<br />H
<br />AUDIBLE CIRCUIT (HORN ONLY)
<br />AUDIBLE DEVICES (HORNS)
<br />14/2* SOLID
<br />K
<br />REMOTE TEST SWITCH CIRCUIT (RTS)
<br />REMOTE TEST SWITCH
<br />14/2* SOLID
<br />NJ
<br />NETWORK COMMUNICATION CIRCUIT (RS485)
<br />MULTIPLE FACP NODES
<br />18/2*
<br />R
<br />RELAY CIRCUIT
<br />AC UNIT/HVLS FAN
<br />14/2* SOLID
<br />S
<br />SPEAKER APPLIANCE CIRCUIT (SPK)
<br />SPEAKER DEVICES (SPEAKERS)
<br />16/2*
<br />`J
<br />NOTIFICATION APPLIANCE CIRCUIT (NAC)
<br />AUDIBLE/VISUAL DEVICES (HORNS/STROBES)
<br />14/2* SOLID
<br />Z
<br />ZONE INDICATING DEVICE CIRCUIT (IDC)
<br />CONVENTIONAL FIRE ALARM APPLIANCES
<br />16/2*
<br />FIRE ALARM CABLE NOTE(S):
<br />1. *WIRE TYPE FOR ALL FIRE ALARM EQUIPMENT (INITIATING, NOTIFICATION, ETC.) SHALL BE INSTALLED PER MANUFACTURER
<br />REQUIREMENTS, CODE REQUIREMENTS & SPECIFICATIONS. WIRE TYPES SHALL BE: FPL, FPLR, & FPLP. INSTALLING CONTRACTOR TO
<br />DETERMINE TYPE OF WIRE TO BE USED.
<br />AC = ABOVE CEILING
<br />AFF = ABOVE FINISHED FLOOR
<br />AHJ = AUTHORITY HAVING JURISDICTION
<br />ALM = ALARM
<br />ANN = ANNUNCIATOR
<br />BMS = BUILDING MANAGEMENT SYSTEM
<br />C = CEILING MOUNTED
<br />CD = CANDELA RATING
<br />DET = DETECTOR
<br />DGP = DATA GATHERING PANEL
<br />E = EXISTING TO REMAIN
<br />EOL = END OF LINE
<br />EPO = EMERGENCY POWER OFF
<br />FAA = FIRE ALARM ANNUNCIATOR
<br />FACP = FIRE ALARM CONTROL PANEL
<br />FATC = FIRE ALARM TERMINAL CABINET
<br />FBO = FURNISHED BY OTHERS
<br />FCC = FIRE COMMAND CENTER
<br />FSD = FIRE SMOKE DAMPER
<br />FTR = FIRE ALARM TRANSPONDER
<br />H = HIGH HUMIDITY
<br />HT = HEIGHT
<br />HVAC = HEATING VENTILATION & AIR CONDITIONING
<br />IMS = INFORMATION MANAGEMENT SYSTEM
<br />MAX = MAXIMUM
<br />MIN = MINIMUM
<br />N/A = NOT APPLICABLE
<br />NAC = NOTIFICATION APPLIANCE CIRCUIT
<br />NDU = NETWORK DISPLAY UNIT
<br />NEC = NATIONAL ELECTRIC CODE
<br />NFPA = NATIONAL FIRE PROTECTION ASSOCIATION
<br />NIC = NOT IN CONTRACT
<br />NPU = NETWORK PROCESSING UNIT
<br />NTS = NOT TO SCALE
<br />PAP = PRE -ACTION PANEL
<br />RC = EXISTING TO REMOVE AND COVER
<br />RD = EXISTING DEVICE TO BE RELOCATED
<br />RL = RELOCATED DEVICE
<br />RR = REMOVE EXISTING & REPLACE WITH NEW
<br />SCC = STATUS COMMAND CENTER
<br />SLC = SIGNALING LINE CIRCUIT
<br />SMK = SMOKE
<br />SUPV = SUPERVISORY
<br />TAC = TRUEALERT ADDRESSABLE CONTROLLER
<br />TRBL = TROUBLE
<br />TS = TAMPER SWITCH
<br />TYP = TYPICAL
<br />UON = UNLESS OTHERWISE NOTED
<br />VCC = VOICE COMMAND CENTER
<br />VT = VALVE TAMPER
<br />W = WATTAGE
<br />W( = WITH
<br />W/0 = WITHOUT
<br />WF = WATERFLOW
<br />WG = WIRE GUARD
<br />WP = WEATHERPROOF
<br />XP = EXPLOSION PROOF
<br />AUTHORITY HAVING JURISDICTION: CITY OF EVERETT FIRE DEPARTMENT
<br />PROJECT BUILDING DATA:
<br />• BUILDING STORIES: 1 STORY
<br />• OCCUPANCY TYPE: S-1,B
<br />• FIRE PROTECTION: FULLY SPRINKLED
<br />CODE REFERENCES:
<br />+ 2015 - WASHINGTON FIRE CODE (2015 IFC WITH AMENDMENTS)
<br />• 2015 - WASHINGTON BUILDING CODE (2015 IBC WITH AMENDMENTS)
<br />• AUTOMATIC FIRE DETECTION & SUPRESSION SYSTEM ORDINENCE NO.
<br />1902-92
<br />STANDARDS:
<br />• 2013 NFPA 72 - NATIONAL FIRE ALARM & SIGNALING CODE
<br />• 2014 NFPA 70 - NATIONAL ELECTRICAL CODE
<br />1. THE TRUCK CANOPY TENANT IMPROVEMENT SHALL CONSIST OF THE ADDITION OF NEW SPRINKLER MONITORING EQUIPMENT IN THE CANOPY AREA. CONTRACTOR SHALL
<br />INTERCONNECT NEW SPRINKLER MONITORING EQUIPMENT WITH THE EXISTING FIRE ALARM SYSTEM. THE INTENT IS TO MONITOR THE NEW POINTS WITH THE EXISTING FIRE ALARM
<br />SYSTEM. THE EXISTING FACP IS A SILENT KNIGHT 5208 ADDRESSABLE FRCP AND IS TO REMAIN (CONTRACTOR TO CONFIRM). CONTRACTOR TO COORDINATE THE LOCATIONS AND
<br />TYPES OF SPRINKLER EQUIPMENT TO BE INSTALLED IN THE CANOPY AREA WITH THE SPRINKLER CONTRACTOR PRIOR TO ANY DEMOLITION OR INSTALLATION.
<br />2. THE POWER CIRCUIT TO THE FACP AND TO THE FIRE ALARM POWER SUPPLIES SHALL BE ON A DEDICATED 120V, 20A BRANCH CIRCUIT BREAKER, AND SHALL HAVE A RED MARKING,
<br />LOCK -ON PROVISION AND SHALL BE IDENTIFIED AS "FIRE ALARM CIRCUIT CONTROL." THE LOCATION OF THE CIRCUIT DISCONNECT MEANS (CIRCUIT BREAKER) SHALL BE
<br />PERMANENTLY IDENTIFIED AT THE FIRE ALARM CONTROL UNIT.
<br />3. CONTRACTOR SHALL FURNISH ALL EQUIPMENT, MATERIALS, TOOLS, LABOR, ENGINEERING, SUBMITTAL DRAWINGS, SCHEDULES, PERMITS, PERMIT FEES, APPROVALS, ETC., NECESSARY
<br />FOR A COMPLETE FIRE ALARM SYSTEM FOR THE TENANT IMPROVEMENT AREAS ONLY AS DESCRIBED WITHIN THESE DRAWINGS AND AS REQUIRED BY ALL LOCAL AND NATIONAL
<br />CODES AND ORDINANCES. CONTRACTOR SHALL NOT DELETE OR ADD ANY EQUIPMENT OR DEVICES WITHOUT WRITTEN DIRECTIVE OF THE OWNER AND ENGINEER.
<br />4. CONTRACTOR SHALL FULLY TEST ALL FIRE ALARM EQUIPMENT, DEVICES, AND CIRCUITS UPON COMPLETION OF INSTALLATION AND PREPARE NEW ULC CERTIFICATE. ALL
<br />DOCUMENTATION SHALL BE COPIED TO PROJECT ENGINEER AS PART OF THE REQUIRED PROJECT CLOSE-OUT DOCUMENTATION.
<br />S. CONTRACTOR IS RESPONSIBLE TO COORDINATE INSTALLATION WITH ALL TRADES AND TO MEET ALL PROJECT SCHEDULES AND DEADLINES.
<br />6. CONTRACTOR SHALL PROVIDE COMPLETE SITE SURVEY TO THE BUILDING PRIOR TO BID IN ORDER TO FAMILIARIZE THEMSELVES WITH THE PROPOSED SCOPE OF WORK AREA,
<br />7. CONTRACTOR TO BE A LICENSED VENDOR OF THE FIRE ALARM SYSTEM EQUIPMENT AND BE FULLY CAPABLE OF MODIFYING AND REPROGRAMMING THE FACP AND RELATED
<br />EQUIPMENT.
<br />8. CONTRACTOR SHALL MONITOR ANY CARBON MONOXIDE DETECTORS THAT ARE PROVIDED BY THE MEP CONTRACTOR. COORDINATE EXACT DEVICE LOCATION, INTERFACE
<br />REQUIREMENTS, AND QUANTITY WITH THE MEP CONTRACTOR.
<br />1 CONDUIT PERCENTAGE FILL CALCULATIONS I DEVICE MOUNTING REQUIREMENTS I PROJECT CONTACT INFORMATION I CONTRACTOR NOTES
<br />PER NFPA 70 TABLE 140% FILL (FOR REFERENCE ONLY)
<br />DESCRIPTION
<br />DIA IN.
<br />AREA SQ. IN.
<br />40% AREA
<br />1/2" EMT CONDUIT
<br />0.622
<br />0,304
<br />0.122
<br />3/4" EMT CONDUIT
<br />0.824
<br />0.533
<br />0.213
<br />I" EMT CONDUIT
<br />1.049
<br />0.664
<br />0.346
<br />1-1/4" CONDUIT
<br />1.380
<br />1.496
<br />0.598
<br />1-1/2" EMT CONDUIT
<br />1.610
<br />2.036
<br />1 0.814
<br />2" EMT CONDUIT
<br />2.067
<br />3.356
<br />_1342
<br />KEYNOTE:
<br />REFERENCE POINT-TO-POINT DEVICE DETAILS OR PRODUCT
<br />SUBMITTAL DATA SHEETS FOR BACK BOX REQUIREMENTS OF
<br />INDIVIDUAL UNITS.
<br />2O MANUAL PULL STATION INSTALLATION TO BE IN
<br />COMPLIANCE WITH IFC, ADA & JURISDICTIONAL
<br />REQUIREMENTS.
<br />FINISHED CEILING
<br />OR HIGH CEILING
<br />PER NFPA 72 AUDIO/VISUAL
<br />AND VISUAL DEVICES LOCATION.
<br />WALL MOUNTED APPLIANCES
<br />SHALL BE MOUNTED SUCH THAT
<br />THE ENTIRE LENS IS NOT LESS
<br />THAN 80" INCHES AND NOT
<br />GREATER THAN 96" INCHES
<br />ABOVE THE FINISHED FLOOR
<br />1 SITE PLAN I SEQUENCE OF OPERATIONS
<br />Op
<br />Eo C M
<br />SMOKE
<br />AUDIOVISUAL
<br />DETECTOR
<br />ON CEILING
<br />NOTIFICATION DEVICE
<br />��{ WP
<br />EiWP
<br />PULL STATION
<br />©—
<br />48" MAX TO THE HIGHEST POINT
<br />OF THE ACTIVATING HANDLE OR
<br />LEVER PER IFC REQUIREMENTS
<br />FINISHED FLOOR
<br />NOTES:
<br />1. TROUBLE CONDITIONS INCLUDING: WIRING SHORT, OPEN C
<br />GROUND FAULT, LOW BATTERY, BATTERY FAILURE, AC LOSS,
<br />DEVICE, EQUIPMENTAL FUNCTION, EQUIPMENT FAILURE.
<br />2. THIS GENERAL ALARM SEQUENCE OF OPERATIONS IS SHOVA
<br />REFERENCE ONLY. THE EXISTING SEQUENCE OF OPERATION
<br />REMAIN THE SAME. AUTHORIZED CONTRACTOR TECHNICIA
<br />BECOME FAMILIAR WITH THE EXISTING SEQUENCE OF OPER,
<br />SHALL PROGRAM THE NEW DEVICES ACCORDINGLY.
<br />CYCTFM TNPI ITC
<br />ARCHITECT:
<br />MG2
<br />1101 SECOND AVENUE, SUITE 100
<br />SEATTLE, WA. 98101
<br />PHONE: 206.962.6500
<br />WWW.MG2.COM
<br />FIRE ALARM CONSULTING FIRM:
<br />NRG FIRE CONSULTING, LLC
<br />7511 GREENWOOD AVENUE NORTH #600
<br />SEATTLE, WA 98103
<br />PHONE: 206.789.0165
<br />WWW.NRGFIRECONSULTING.COM
<br />FIRE ALARM SYSTEM DESIGNER:
<br />DESIGNER OF RECORD: SEAN E. PISONI, CET
<br />NICET #: 93223
<br />EXPIRATION DATE: DECEMBER 2020
<br />AUTHORITY HAVING JURISDICTION:
<br />CITY OF EVERETT FIRE DEPARTMENT
<br />OFFICE OF THE FIRE MARSHAL
<br />2930 WETMORE AVENUE, SUITE 7-A
<br />EVERETT, WA 98201
<br />PHONE: 425.257.8120
<br />FAX: 425.257.8139
<br />RFMARKC
<br />1
<br />SMOKE DETECTOR
<br />•
<br />•
<br />•
<br />•
<br />•
<br />•
<br />•
<br />•
<br />1
<br />2
<br />CARBON MONOXIDE DETECTOR
<br />•
<br />•
<br />•
<br />•
<br />•
<br />•
<br />•
<br />2
<br />3
<br />MANUAL PULL STATION
<br />•
<br />•
<br />•
<br />•
<br />•
<br />•
<br />•
<br />•
<br />3
<br />4
<br />DUCT DETECTOR
<br />•
<br />•
<br />•
<br />•
<br />•
<br />+
<br />4
<br />5
<br />WET SPRINKLER SYSTEM WATERFLOW SWITCH
<br />•
<br />•
<br />•
<br />•
<br />•
<br />•
<br />•
<br />•
<br />•
<br />5
<br />6
<br />WET/DRY SPRINKLER SYSTEM TAMPER SWITCH
<br />•
<br />•
<br />•
<br />•
<br />•
<br />6
<br />7
<br />DRY SPRINKLER SYSTEM ALARM PRESSURE SWITCH
<br />•
<br />•
<br />•
<br />•
<br />•
<br />•1
<br />7
<br />8
<br />DRY SPRINKLER SYSTEM HIGH/LOW PRESSURE SWITCH
<br />•
<br />•
<br />•
<br />•
<br />•
<br />8
<br />9
<br />POST INDICATOR VALVE SWITCH
<br />•
<br />•
<br />•
<br />•
<br />•
<br />9
<br />10
<br />BACKFLOW PREVENTOR
<br />•
<br />•
<br />•
<br />+
<br />•
<br />10
<br />11
<br />FIRE PUMP RUNNING
<br />•
<br />•
<br />•
<br />•
<br />•
<br />11
<br />12
<br />FIRE PUMP POWER LOSS
<br />•
<br />•
<br />+
<br />•
<br />•
<br />12
<br />13
<br />FIRE PUMP PHASE REVERSAL
<br />•
<br />+
<br />•
<br />•
<br />+
<br />13
<br />14
<br />TROUBLE SEE NOTE 1
<br />•
<br />+
<br />•
<br />•
<br />•
<br />14
<br />1. THESE DRAWINGS ARE PERFORMANCE BASED ONLY AND DO NOT SHOW ALL FIRE ALARM EQUIPMENT. IT IS THE CONTRACTOR'S RESPONSIBILITY TO VERIFY LOCATION AND
<br />CONDITION OF ALL EXISTING FIRE ALARM EQUIPMENT, CIRCUITING, CONDUITS, ETC, AND CONFIRM REQUIREMENTS OF NEW REQUIRED FIRE ALARM EQUIPMENT WITH LOCAL AHJ.
<br />CONTRACTOR IS RESPONSIBLE FOR ALL PERMITS, PLANS, CALCULATIONS, APPROVAL, ETC.
<br />2. THE FIRE ALARM SYSTEM SHALL BE MONITORED BY AN APPROVED U.L. CENTRAL STATION MONITORING SERVICE. INTERFACE WILL BE FULLY LISTED AND APPROVED FOR THIS
<br />PURPOSE.
<br />3. SIGNALING LINE CIRCUITS SHALL BE CLASS A, PER NFPA 72, CURRENT ADOPTED ADDITION. NOTIFICATION AND INITIATING CIRCUITS SHALL BE CLASS B, PER NFPA 72, CURRENT
<br />ADOPTED EDITION. A MINIMUM OF 10% EXCESS CAPACITY IS REQUIRED ON ALL NOTIFICATION CIRCUITS.
<br />4. INSTALLATION OF DEVICES SHALL BE IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS. POWER LIMITED AND NON -POWER LIMITED FIELD WIRING MUST BE INSTALLED
<br />WITHIN THE FACP ENCLOSURE IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS AND APPLICABLE ELECTRICAL CODES.
<br />5. ALL WIRE SHALL BE SOLID CONDUCTORS OR COPPER, MINIMUM SIZE OF NO.18 AWG, AND INSULATION RATED AT 600V. ALL WIRING SHALL COMPLY WITH MANUFACTURER'S
<br />RECOMMENDATIONS AND BE INSTALLED ACCORDING TO APPLICABLE ELECTRICAL CODES. ALL WIRING SHALL BE APPROPRIATELY COLOR -CODED, AND PERMANENT WIRE MARKERS
<br />SHALL BE USED TO IDENTIFY THE TERMINATIONS FOR, EACH CIRCUIT AT THE CONTROL PANEL. REFER TO 'APPLICABLE CODES & STANDARDS' FOR SPECIFIC CODE REFERENCES.
<br />6. ALL CONDUITS, BOXES, FITTINGS, ETC. WITHIN FINISHED AREAS SHALL BE CONCEALED BEHIND DRYWALL, DROP CEILING OR OTHER FINISHED SURFACES. EXPOSED WIRING IS NOT
<br />ALLOWED FOR FIRE ALARM WIRING. CONTRACTOR SHALL MAINTAIN ALL AREAS OF THE BUILDING IN A NEAT AND WORKMANLIKE MANNER.
<br />7. ALL WIRING, CONDUIT, BOXES (UNLESS OTHERWISE INDICATED), FITTINGS, COUPLINGS, CONNECTORS, STRAPS, SUPPORTS, PULL -LINES, BUSHINGS, ETC. SHALL BE PROVIDED AND
<br />INSTALLED BY A LICENSED ELECTRICAL CONTRACTOR. ALL CONDUIT SIZES AND BACK BOX SIZES SHALL BE CONFIRMED WITH THE FIRE ALARM EQUIPMENT SUPPLIER. ALL WORK SHALL
<br />MEET OR EXCEED THE REQUIREMENTS OF THE NATIONAL ELECTRICAL CODE.
<br />8. MAINTAIN THE FIRE RESISTANCE INTEGRITY OF ALL WALL, CEILING, AND ROOF ASSEMBLIES ANYTIME THAT WORK IS NOT ACTIVELY BEING PERFORMED.
<br />9. THE ELECTRICAL CONTRACTOR SHALL PROVIDE ALL LINE VOLTAGE (120 V. MAX.) AND LOW -VOLTAGE (UP TO 50 VAC/VDC) CIRCUITING IN SEPARATE CONDUIT. CONDUIT FILLS SHALL
<br />BE NOT MORE THAN 75% OF THAT ALLOWED BY THE NATIONAL ELECTRICAL CODE.
<br />10. SYSTEM OPERATION, TESTING, TURN OVER, WARRANTY, COMPLIANCE, AND AFTER MARKET SERVICE SHALL BE PROVIDED BY THE APPROVED FIRE ALARM VENDOR.
<br />11. NRG FIRE CONSULTING OR THE ENGINEER OF RECORD SHALL NOT BE RESPONSIBLE FOR THE CONTRACTOR'S FAILURE TO CARRY OUT THE CONSTRUCTION WORK IN ACCORDANCE
<br />WITH THE CONTRACT DOCUMENTS, NOR SHALL THEY BE REQUIRED TO SUPERVISE THE CONDUCT OF THE CONSTRUCTION PROCEDURES FOLLOWED BY THE CONTRACTOR,
<br />SUBCONTRACTORS, THEIR RESPECTIVE EMPLOYEES OR ANY OTHER PERSON AT THE JOB SITE OTHER THAN NRG FIRE CONSULTING, LLC REPRESENTATIVES AND/OR THE ENGINEER OF
<br />RECORD.
<br />12. THE DESIGNER AND/OR THE ENGINEER OF RECORD SHALL NOT BE RESPONSIBLE FOR UNAUTHORIZED CHANGES TO OR USE OF THESE PLANS. ALL CHANGES MUST BE IN WRITING
<br />AND MUST BE APPROVED BY THE PROJECT ARCHITECT.
<br />13. THE FIRE ALARM VENDOR AND/OR INSTALLING CONTRACTOR SHALL CONTACT THE ARCHITECT WITH COMMENTS OR EXCEPTIONS TO THE APPROVED PLANS AND SPECIFICATIONS
<br />PRIOR TO BID. THE CONTRACTOR ASSUMES RESPONSIBILITY FOR ALL WORK SHOWN ON THE APPROVED PLANS AND MODIFICATIONS SHALL NOT BE ALLOWED WITHOUT APPROVAL
<br />FROM THE PROJECT ARCHITECT.
<br />14, THE INSTALLATION CONTRACTOR SHALL COORDINATE ALL FINAL EQUIPMENT LOCATIONS WITH THE LATEST PROJECT FIXTURE PLANS PRIOR TO INSTALLATION. CONTRACTOR TO
<br />COORDINATE ALL WIRING, CONDUITS, BOXES, AND EQUIPMENT WITH OTHER SYSTEM CONTRACTORS TO AVOID POTENTIAL CONFLICTS AND EQUIPMENT OBSTRUCTIONS.
<br />15. ANY DISCREPANCIES BETWEEN PLANS WILL REQUIRE THE MORE STRINGENT TO BE BID ON AND INSTALLED.
<br />16. CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING ANY REQUIRED MECHANICAL LIFTS TO PERFORM INSTALLATION OF THE FIRE ALARM SYSTEM.
<br />17. CONTRACTOR SHALL UPDATE THE AS -BUILT DRAWING SET DAILY WITH JOB PROGRESS. RETURN THE AS -BUILT DRAWING SET TO THE BUILDING OWNER NO LATER THAN 7 DAYS
<br />AFTER FINAL TEST.
<br />18. CONTRACTOR IS RESPONSIBLE FOR REMOVING ANY OLD FIRE ALARM EQUIPMENT, PANELS, BOXES, CONDUIT, WIRING, ETC. FROM THE BUILDING PRIOR TO COMPLETION OF THE
<br />PROJECT. THESE REMOVED ITEMS SHALL BE REMOVED FROM JOB SITE AND DISPOSED OF PROPERLY ACCORDING TO THE LOCAL JURISDICTION.
<br />e
<br />7611 Greenwood Avenue, #600
<br />Seattle, WA 98103
<br />(21 6) 789-0165
<br />nr # 4econsuffin .r.om
<br />DWS5
<br />EVERETT DISTRIBUTION CENTER
<br />6617 ASSOCIATED BLVD.
<br />EVERETT, WA 98203
<br />i•
<br />•
<br />1
<br />i�
<br />i
<br />•
<br />DESCRIPTION A DATE
<br />CIA REVIEW SET 05/22/2020
<br />90% QA REVIEW SET 06/1912020
<br />PERMIT SET 09/17/2020
<br />JOB NUMBER
<br />20574401E
<br />DRAWN BY CHECKED BY
<br />DRS SEP
<br />SHEET TITLE
<br />INFORMATION SHEET -
<br />
|