General Structural Notes <br />(THE FOLLOWING APPLY UNLESS SHOWN OTHERWISE ON THE DRAWINGS.) <br />CRITERIA. <br />1. ALL MATERIALS, WORKMANSHIP, DESIGN, AND CONSTRUCTION SHALL CONFORM TO THE DRAWINGS, SPECIFICATIONS, AND THE <br />INTERNATIONAL BUILDING CODE (IBC) WITH WASHINGTON STATE ADMINISTRATIVE CODE AMENDMENTS, 2018 EDITION. <br />2. THE EXISTING STRUCTURE HAS NOT BEEN EVALUATED OR STRENGTHENED TO CONFORM TO CURRENT SEISMIC CODE REQUIREMENTS <br />AS PART OF THIS PROJECT SCOPE. THE ALTERATIONS SHOWN ARE IN CONFORMANCE WITH SECTION 503.4 OF THE <br />INTERNATIONAL EXISTING BUILDING CODE (IEBC), 2018 EDITION. <br />3. DESIGN LOADING CRITERIA: <br />RISK CATEGORY IBC TABLE 1604.5 . . . . . . . a . . . . . IV <br />ROOF SNOW LOAD . . . . . . . . . . . . . . . . . . . . . . 30 PSF (Is = 1.2) <br />ROOF DECK LIVE LOAD . . . . . . . . . . . . . . . . . . 100 PSF <br />STAIR LIVE LOAD . . . . . . . . . . . . . . . . . . . . . 100 PSF <br />GUARDRAILS/BALCONY RAILS . . . . . . . . . . . . . . . . . . 50 PEE OR 200 LB CONCENTRATED LOAD <br />EARTHQUAKE (NONSTRUCTURAL COMPONENTS) . . . . . . . . . . . SEISMIC DESIGN CATEGORY D <br />Ss = 1. 2R, Si e 0. 49, S®S = 0. B5, SDI e 0.49 <br />IP = 1.5 <br />Rp = 2.5, ap = 2.5, 40 = 2.0 <br />WIND . . . . . . . . . . . . . . . . . . . . . . . 105 MPH, EXPOSURE "B", Kzt = 1.0 <br />WIND (CLADDING/ENCLOSURE ELEMENT DESIGN PRESSURES) . . . 40/24PSF MAX. AT WALLS (LRFD/ASD) <br />WIND PRESSURES BASED ON LESS THAN 10 SQUARE FOOT TRIBUTARY AREAS NEAR WALL CORNERS OR ROOF EDGES (EXCLUDING <br />CORNER ZONES AT ROOF). REDUCED DESIGN PRESSURES MAY BE CALCULATED IN ACCORDANCE WITH ASCE 7-16 CHAPTER 30. <br />SEE DRAWINGS FOR ADDITIONAL LOADING CRITERIA <br />4. STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH ARCHITECTURAL DRAWINGS AND ALL OTHER CONTRACT DOCUMENTS <br />FOR BIDDING AND CONSTRUCTION. CONTRACTOR SHALL VERIFY DIMENSIONS AND CONDITIONS FOR COMPATIBILITY AND SHALL <br />NOTIFY ARCHITECT OF ALL DISCREPANCIES PRIOR TO CONSTRUCTION. IT IS THE CONTRACTOR'S RESPONSIBILITY TO <br />COORDINATE BUILDING LAYOUT DIMENSIONS (GRID LAYOUTS, SITE COORDINATES, ETC.) AMONGST ALL TRADES, INCLUDING <br />SHOP FABRICATED ITEMS. <br />5. CONTRACTOR SHALL VERIFY ALL EXISTING DIMENSIONS, MEMBER SIZES AND CONDITIONS PRIOR TO COMMENCING ANY WORK AND <br />PRIOR TO SUBMITTING SHOP DRAWINGS. ALL DIMENSIONS OF EXISTING CONSTRUCTION SHOWN ON THE DRAWINGS ARE <br />INTENDED AS GUIDELINES ONLY AND MUST BE VERIFIED. THE EXISTING CONDITIONS SHOWN ON THE DRAWINGS ARE BASED <br />EITHER ON SITE OBSERVATION, ORIGINAL DRAWINGS OR WERE ASSUMED BASED ON EXPECTED CONDITIONS. IF THE EXISTING <br />CONDITIONS DO NOT CLOSELY MATCH THE CONDITIONS SHOWN ON THE DRAWINGS, OR IF THE EXISTING MATERIALS ARE OF <br />QUESTIONABLE OR SUBSTANDARD QUALITY, NOTIFY THE ENGINEER PRIOR TO COMMENCING ANY WORK. <br />6. CONTRACTOR SHALL PROVIDE TEMPORARY BRACING, BOTH FOR VERTICAL LOADS AND LATERAL STABILITY, FOR THE STRUCTURE <br />AND STRUCTURAL COMPONENTS UNTIL ALL FINAL CONNECTIONS HAVE BEEN COMPLETED IN ACCORDANCE WITH THE DRAWINGS. <br />7. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL SAFETY PRECAUTIONS AND THE METHODS, TECHNIQUES, SEQUENCES OR <br />PROCEDURES REQUIRED TO PERFORM THE WORK. <br />B. CONTRACTOR -INITIATED CHANGES SHALL BE SUBMITTED IN WRITING TO THE ARCHITECT AND STRUCTURAL ENGINEER FOR <br />APPROVAL PRIOR TO FABRICATION OR CONSTRUCTION. CHANGES SHOWN ON SHOP DRAWINGS ONLY WILL NOT SATISFY THIS <br />REQUIREMENT. <br />9. DRAWINGS INDICATE GENERAL AND TYPICAL DETAILS OF CONSTRUCTION. WHERE CONDITIONS ARE NOT SPECIFICALLY <br />INDICATED BUT ARE OF SIMILAR CHARACTER TO DETAILS SHOWN, SIMILAR DETAILS OF CONSTRUCTION SHALL BE USED, <br />SUBJECT TO REVIEW AND APPROVAL BY THE ARCHITECT AND THE STRUCTURAL ENGINEER. <br />10. ALL STRUCTURAL SYSTEMS COMPOSED OF COMPONENTS TO BE FIELD ERECTED SHALL BE SUPERVISED BY THE SUPPLIER DURING <br />MANUFACTURING, DELIVERY, HANDLING, STORAGE AND ERECTION IN ACCORDANCE WITH INSTRUCTIONS PREPARED BY THE <br />SUPPLIER. <br />11. LATERAL BRACING AND/OR GRAVITY SUPPORT AND ANCHORAGE OF ALL MECHANICAL OR ELECTRICAL EQUIPMENT SHALL BE <br />DESIGNED BY A PROFESSIONAL ENGINEER REGISTERED IN THE STATE OF WASHINGTON, EXCEPT FOR ELEMENTS SPECIFICALLY <br />SHOWN AND DETAILED ON THE STRUCTURAL DRAWINGS. THE MECHANICAL/ELECTRICAL CONTRACTOR MUST HIRE THE ENGINEER <br />AND IS RESPONSIBLE FOR ALL COSTS RELATED TO THE PURCHASE AND INSTALLATION OF NECESSARY SUPPORTS, BRACING AND <br />ANCHORAGE. SEISMIC BRACING AND ANCHORAGE DESIGN AND CONSTRUCTION SHALL COMPLY WITH CHAPTER 13 OF ASCE 7-16. <br />SEE GENERAL STT UCTURAL NOTE 15 FOR ADDITIONAL INFORMATION. <br />/2\ <br />12. SHOP DRAWINGS FO REINFORCING STEEL, TRUCTURAL STEEL AND METAL DECKING SHALL BE SUBMITTED TO THE ARCHITECT <br />AND STRUCTURAL EN RIOR TO FABRICATION OF THESE ITEMS. <br />13. SHOP DRAWING REVIEW: DIMENSIONS AND QUANTITIES ARE NOT REVIEWED BY THE ENGINEER OF RECORD, AND THEREFORE <br />MUST BE VERIFIED BY THE CONTRACTOR. THE CONTRACTOR SHALL REVIEW AND STAMP DRAWINGS PRIOR TO REVIEW BY <br />ENGINEER OF RECORD. SUBMITTALS SHALL BE SUBMITTED ELECTRONICALLY IN PDF FORMAT. <br />SHOP DRAWING SUBMITTALS PROCESSED BY THE ENGINEER ARE NOT CHANGE ORDERS. THE PURPOSE OF SHOP DRAWING <br />SUBMITTALS BY THE CONTRACTOR IS TO DEMONSTRATE TO THE ENGINEER THAT THE CONTRACTOR UNDERSTANDS THE DESIGN <br />CONCEPT BY INDICATING WHICH MATERIAL IS INTENDED TO BE FURNISHED AND INSTALLED AND BY DETAILING THE INTENDED <br />FABRICATION AND INSTALLATION METHODS. IF DEVIATIONS, DISCREPANCIES, OR CONFLICTS BETWEEN SHOP DRAWING <br />SUBMITTALS AND THE CONTRACT DOCUMENTS ARE DISCOVERED EITHER PRIOR TO OR AFTER SHOP DRAWING SUBMITTALS ARE <br />PROCESSED BY THE ENGINEER, THE DESIGN DRAWINGS AND SPECIFICATIONS SHALL CONTROL AND SHALL BE FOLLOWED. <br />14. NOT USED. <br />STATEMENT OF SPECIAL INSPECTIONS (STRUCTURAL) <br />15. STATEMENT OF SPECIAL INSPECTIONS e STRUCTURAL ITEMS (SEISMIC DESIGN CATEGORY D <br />DEFINITIONS: <br />THE SEISMIC FORCE RESISTING SYSTEM FOR THIS STRUCTURE CONSISTS PRIMARILY OF EXISTING SHEAR WALLS AND <br />FLOOR/ROOF DIAPHRAGMS AS SPECIFIED ON THE DRAWINGS. SEE THE LEGEND OF PLAN SHEETS FOR ADDITIONAL INFORMATION <br />DEFINING MEMBER LOCATIONS. <br />SPECIAL INSPECTIONS AND TESTING SHALL BE PERFORMED BY THE OWNER APPOINTED INSPECTION AGENCY IN ACCORDANCE <br />WITH CHAPTER 17 OF THE IBC WITH REPORTS PER IBC SECTION 1704.2.4 SUBMITTED TO THE OWNER, ARCHITECT, <br />STRUCTURAL ENGINEER, CONTRACTOR, AND BUILDING OFFICIAL FOR EACH DAY SPECIAL INSPECTIONS OR TESTING IS <br />PERFORMED. THESE INSPECTIONS ARE IN ADDITION TO THE INSPECTIONS SPECIFIED IN !BC SECTION 110. SEE TABLES <br />BELOW FOR ADDITIONAL INFORMATION. <br />STRUCTURAL ITEMS SPECIAL INSPECTION FREQUENCY IBC REFERENCE <br />STRUCTURAL STEEL FABRICATION,ERECTION, AND NONDESTRUCTIVE TESTING* <br />SPECIAL INSPECTION AND NONDESTRUCTIVE TESTING FOR STRUCTURAL STEEL SHALL BE IN ACCORDANCE WITH THE QUALITY <br />ASSURANCE (QA) INSPECTION REQUIREMENTS OF AISC 360-16 CHAPTER N. CONTINUOUS INSPECTION SHALL BE PERFORMED AT <br />"P" TASKS DEFINED IN RISC 360-16; PERIODIC INSPECTION SHALL BE PERFORMED AT "0" TASKS DEFINED IN RISC 360-16. <br />ADDITIONAL SPECIAL INSPECTION AND TESTING REQUIREMENTS FOR THE STRUCTURAL STEEL SEISMIC SYSTEM SHALL BE PER <br />AISC 341-16 CHAPTER J AS INDICATED BELOW. <br />SHOP AND FIELD WELDING CONTINUOUS/PERIODIC (QA PER AISC 360 CH. N5.4) 1705.2.1 <br />HIGH STRENGTH BODING CONTINUOUS/PERIODIC (QA AISC 360 CH. N5.6) 1705.2.1 <br />MATERIAL VERIFICATION PERIODIC 1705.2.1 <br />(IDENTIFICATION MARKS AND MANUFACTURER'S TEST REPORTS) <br />CONCRETE (SEE GENERAL STRUCTURAL NOTE 20 FOR ADDITIONAL REQUIREMENTS** <br />CONCRETE PLACEMENT*** CONTINUOUS TABLE 1705.3 ITEM 5)6&7 <br />A2 =1705.3ITEM <br />�12 <br />REINFORCINGPLACEMENT PERIODIC AND PRIOR TO ALL POURS TABL <br />EXPANSION BOLTS, INSERTS PERIODIC INCLUDING TORQUE TESTS IN ACCORDANCE TABLE 1705.3 ITEM 4 <br />& CONCRETE SCREWS WITH APPROVED ICC-ES REPORTS <br />EPDXY GROUTED RODS OR REBAR PERIODIC INCLUDING INSPECTION OF EMBEDMENT TABLE 1705.3 ITEM 4, <br />DEPTH AND HOLE CLEANLINESS PRIOR TO ALL ACI 318®14 SECTION 17.8 <br />INSTALLATIONS (CONTINUOUS FOR UPWARDLY INCLINED ANCHORS) <br />* STRUCTURAL STEEL QUALITY ASSURANCE INSPECTIONS, EXCEPT NONDESTRUCTIVE TESTING, MAY BE WAIVED IF APPROVED BY <br />THE OWNER AND BUILDING OFFICIAL FOR WORK PERFORMED ON THE PREMISES OF A FABRICATOR REGISTERED AND APPROVED TO <br />PERFORM SUCH WORK WITHOUT SPECIAL INSPECTION IN ACCORDANCE WITH IBC SECTION 1704.2.5.1. <br />** EXCEPTIONS 1 THRU 5 PER IBC SECTION 1705.3 SHALL NOT APPLY TO CONCRETE WORK ON THIS PROJECT. <br />*** FREQUENCY OF CONCRETE LABORATORY TESTING SHALL BE IN ACCORDANCE WITH ACI 318-14 SECTION 26.12.2 UNLESS <br />OTHERWISE NOTED IN THE PROJECT SPECIFICATIONS. <br />**** THE EXCEPTION FOR SHEATHING FASTENED AT A SPACING GREATER THAN 4"®e SHALL NOT APPLY TO WOOD OR METAL <br />FRAMING ON THIS PROJECT. <br />SEISMIC DESIGN REQUIREMENTS PERIODIC SPECIAL INSPECTION <br />ARCH, MECH, & ELEC ITEMS (ASCE 7-16 CHAPTER 13) AS SPECIFIED PER IBC CHAPTER 17 <br />EXTERIOR CLADDING ASCE 7-16 SECTION 13.5.3 REQUIRED FOR WALL FRAMING, FOR <br />FASTENING OF VENEER OR CLADDING <br />EXCEEDING 5 PSF (IBC 1705.12.5) <br />LIFE SAFETY COMPONENTS INCLUDING ASCE 7-16 SECTION 13.6 AND REQUIRED FOR VERIFICATION OF <br />FIRE PUMPS, EMERGENCY GENERATORS, IBC 1705.13.2 CERTIFICATE OF COMPLIANCE LABEL <br />SMOKE EVACUATION FANS, AND ON COMPONENT (IBC 1705.12.4) <br />COMPONENTS WITH HAZARDOUS COMBUSTIBLE, <br />OR HIGHLY TOXIC CONTENTS <br />(Ip=1.5 PER ASCE 7-16 SECTION 13.1.3) <br />INSTALLATION AND ANCHORAGE OF ASCE 7-16 SECTION 13.6 AND REQUIRED (IBC 1705.12.4 & <br />1705.12.6) <br />SPRINKLER SYSTEMS, FIRE PUMPS, IBC 1705.13.2 <br />EMERGENCY GENERATORS, COMPONENTS <br />WITH HAZARDOUS, COMBUSTIBLE, OR <br />HIGHLY TOXIC CONTENTS <br />(Ip=1.5 PER ASCE 7-16 SECTION 13.1.3) <br />ALL OTHER MECHANICAL AND ASCE 7=16 SECTION 13.6 NOT REQUIRED <br />ELECTRICAL COMPONENTS <br />STRUCTURAL OBSERVATION IN ACCORDANCE WITH IBC SECTION 1704.6 WILL BE PERFORMED BY THE STRUCTURAL ENGINEER OF <br />RECORD DURING CONSTRUCTION AT SIGNIFICANT CONSTRUCTION STAGES AND AT COMPLETION OF THE STRUCTURAL SYSTEM. <br />STRUCTURAL OBSERVATION CONSISTS OF VISUAL OBSERVATION FOR GENERAL CONFORMANCE TO THE CONSTRUCTION DOCUMENTS <br />AND DOES NOT INCLUDE OR WAIVE THE RESPONSIBILITY FOR THE INSPECTIONS REQUIRED BY SECTIONS 110, 1704, OR OTHER <br />SECTIONS OF THE IBC. <br />CONTRACTOR STATEMENT OF RESPONSIBILITY: CONTRACTOR SHALL SUBMIT A WRITTEN STATEMENT OF RESPONSIBILITY IN <br />ACCORDANCE WITH IBC SECTION 1704.4 TO THE BUILDING OFFICIAL AND OWNER PRIOR TO CONSTRUCTION ACKNOWLEDGING THE <br />SPECIAL REQUIREMENTS CONTAINED IN THE STATEMENT OF SPECIAL INSPECTIONS. <br />ANCHORAGE. <br />16. EXPANSION BOLTS INTO CONCRETE SHALL BE ONE OF THE FOLLOWING INSTALLED IN STRICT ACCORDANCE WITH THE ICC-ES <br />REPORTS INDICATED AND MANUFACTURER'S INSTRUCTIONS: "KWIK BOLT TZ" AS MANUFACTURED BY HILTI, INC. (ICC-ES NO. <br />1917); OR "STRONG -BOLT 2" AS MANUFACTURED BY SIMPSON STRONG -TIE COMPANY, INC. (ICC-ES NO. 3037), OR "POWER® <br />STUD+ SD2" AS MANUFACTURED BY DEWALT (ICC-ES NO. 2502). SUBSTITUTES PROPOSED BY CONTRACTOR SHALL BE <br />SUBMITTED FOR REVIEW WITH ICC-ES REPORTS INDICATING EQUIVALENT OR GREATER LOAD CAPACITIES. IN ADDITION, <br />SUBSTITUTIONS SHALL MEET ICC-ES ACCEPTANCE CRITERIA AC193. SPECIAL INSPECTION IS REQUIRED FOR ALL EXPANSION <br />BOLT INSTALLATION. EXPANSION BOLTS SHALL NOT BE USED AS SUBSTITUTES FOR EMBEDDED ANCHOR BOLTS UNLESS <br />SPECIFICALLY APPROVED BY THE STRUCTURAL ENGINEER. NOTIFY ENGINEER IF BOLT LOCATIONS CONFLICT WITH <br />REINFORCING STEEL ® DO NOT CUT REINFORCING OR REDUCE EMBEDMENT DEPTHS WITHOUT PRIOR APPROVAL. <br />UNLESS OTHERWISE NOTED, PROVIDE THE FOLLOWING NOMINAL EMBEDMENT DEPTHS FOR EXPANSION BOLTS INTO CONCRETE: <br />HILTI KWIK BOLT TZ: <br />3/8" EXPANSION BOLTS . . . . . . . . . . . . . . . . . . . . . 2 5/16" <br />1/2" 0 EXPANSION BOLTS . . . . . . . . . . . . . . . . . . . . . 3 5/8" <br />5/8" EXPANSION BOLTS . . . . . . . . . . . . . . . . . . 4 7/16" <br />3/4" 0 EXPANSION BOLTS . . . . . . . . . . . . . . . . . . . . 5 5/16" <br />SIMPSON STRONG -BOLT 2: <br />3/8" 0 EXPANSION BOLTS . . . . . . . . . . . . . . . . . . . . . 2 7/8" <br />1/2" 0 EXPANSION BOLTS . . . . . . . . . . . . . . . . . . . . . 3 7/8" <br />5/8" EXPANSION BOLTS . . . . . . . . . . . . . . . . . . . . 5 1/8" <br />3/4" 0 EXPANSION BOLTS . . . . . . . . . . . . . . . . . . . . . 5 3/4" <br />DEWALT/POWERS POWER-STUD+SD2: <br />3/8" 0 EXPANSION BOLTS . . . . . . . . . . . . . . . . . . . . . 2 3/B" <br />1/2"0 EXPANSION BOLTS . . . . . . . . . . . . . . . . . . . 3 3/4" <br />5/8" 0 EXPANSION BOLTS . . . . . . . . . . . . . . . . . . . . 4 7/8" <br />3/4" 0 EXPANSION BOLTS . . . . . . . . . . . . . . . . . . . . . . 5 3/4" <br />17. EPDXY -GROUTED RODS OR REBAR TO CONCRETE SPECIFIED ON THE DRAWINGS SHALL DE ONE OF THE FOLLOWING INSTALLED IN <br />STRICT ACCORDANCE WITH THE ICC®ES REPORTS INDICATED AND MANUFACTURER'S INSTRUCTIONS INCLUDING MINIMUM EMBED <br />REQUIREMENTS: "SET-XP" AS MANUFACTURED BY SIMPSON STRONG -TIE COMPANY, INC. (ICC-ES NO. 2508); OR "HIT-HY 200" <br />AS MANUFACTURED BY HILTI, INC. (ICC-ES NO. 3187), "SAFE -SET" INSTALLATION WITH HOLLOW CARBIDE DRILL BIT IS <br />PERMITTED; OR "PURE110+" AS MANUFACTURED BY DEWALT (ICC-ES NO. 3298), OR "AC200+" AS MANUFACTURED BY DEWALT <br />(ICC-ES NO. 4027). SUBSTITUTES PROPOSED BY CONTRACTOR SHALL BE SUBMITTED FOR REVIEW WITH ICC-ES REPORTS <br />INDICATING EQUIVALENT OR GREATER LOAD CAPACITIES. IN ADDITION, SUBSTITUTIONS SHALL MEET ICC-ES ACCEPTANCE <br />CRITERIA AC308. SPECIAL INSPECTION OF EPDXY -GROUTED ANCHOR INSTALLATION IS REQUIRED. NOTIFY ENGINEER IF <br />ANCHOR LOCATIONS CONFLICT WITH REINFORCING STEEL e DO NOT CUT REINFORCING OR REDUCE EMBEDMENT DEPTHS WITHOUT <br />PRIOR APPROVAL. INSTALLATION OF ADHESIVE ANCHORS HORIZONTALLY OR UPWARDLY INCLINED TO SUPPORT SUSTAINED <br />TENSION LOADS SHALL BE PERFORMED BY CERTIFIED PERSONNEL IN CONFORMANCE TO ACI 318-14 SECTION 17.8.2.2. HOLES <br />SHALL BE HAMMER DRILLED AND DRY. <br />EPDXY GROUTED RODS OR REBAR SHALL NOT BE USED AS SUBSTITUTES FOR CAST -IN -PLACE ANCHOR BOLTS, THREADED RODS, <br />OR REINFORCING STEEL UNLESS SPECIFICALLY APPROVED BY THE STRUCTURAL ENGINEER. FIELD FIXES OR OTHER CONDITIONS <br />NOT ADDRESSED IN THE DOCUMENTS MUST BE SPECIFICALLY APPROVED BY THE STRUCTURAL ENGINEER, INCLUDING EMBEDMENT <br />DEPTHS. <br />UNLESS OTHERWISE NOTED, PROVIDE THE FOLLOWING EMBEDMENT DEPTHS FOR ANCHORS AT CONCRETE: <br />3/8"0 ROD OR #3 BAR . . . . . . . . . . . . . . . . . . 4" <br />1/2"0 ROD OR #4 BAR . . . . . . . . . . . . . . . . . . . . . 5" <br />5/8"0 ROD OR #5 BAR . . . . . . . . . . . . . . . . . . . 7" <br />3/4"0 ROD OR #6 BAR . . . . . . . . . . . . . . . . . . . 9" <br />7/8"0 ROD OR #7 BAR . . . . . . . . . . . . . . . . . . 12" <br />1"0 ROD OR #8 BAR . . . . . . . . . . . . . . . . . 15" <br />18. CONCRETE SCREW ANCHORS SHALL BE ONE OF THE FOLLOWING INSTALLED IN STRICT ACCORDANCE WITH THE ICC-ES REPORTS <br />INDICATED AND MANUFACTURER'S INSTRUCTIONS INCLUDING MINIMUM EMBED REQUIREMENTS: "TITEN HD" AS MANUFACTURED BY <br />SIMPSON STRONG -TIE COMPANY (ICC-ES NO. 2713); OR "KWIK HUS-EZ" AS MANUFACTURED BY HILTI, INC. (ICC-ES NO. <br />3027); OR "SCREW -BOLT+" AS MANUFACTURED BY DEWALT (ICC-ES NO. 3889). SUBSTITUTES PROPOSED BY CONTRACTOR <br />SHALL BE SUBMITTED FOR REVIEW WITH ICC-ES REPORTS INDICATING EQUIVALENT OR GREATER LOAD CAPACITIES. IN <br />ADDITION, SUBSTITUTIONS SHALL MEET ICC-ES ACCEPTANCE CRITERIA AC193. SPECIAL INSPECTION IS REQUIRED FOR ALL <br />CONCRETE SCREW ANCHOR INSTALLATION. CONCRETE SCREW ANCHORS SHALL NOT BE USED AS SUBSTITUTES FOR EMBEDDED <br />ANCHOR BOLTS OR EXPANSION BOLTS UNLESS SPECIFICALLY APPROVED BY THE STRUCTURAL ENGINEER. NOTIFY ENGINEER IF <br />SCREW ANCHOR LOCATIONS CONFLICT WITH REINFORCING STEEL ® DO NOT CUT REINFORCING OR REDUCE EMBEDMENT DEPTHS <br />WITHOUT PRIOR APPROVAL. <br />RENOVATION. <br />19. DEMOLITION: CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS BEFORE COMMENCING ANY DEMOLITION. SHORING SHALL <br />BE INSTALLED TO SUPPORT EXISTING CONSTRUCTION AS REQUIRED AND IN A MANNER SUITABLE TO THE WORK SEQUENCES. <br />DEMOLITION DEBRIS SHALL NOT BE ALLOWED TO DAMAGE OR OVERLOAD THE EXISTING STRUCTURE. LIMIT CONSTRUCTION <br />LOADING (INCLUDING DEMOLITION DEBRIS) ON EXISTING FLOOR SYSTEMS TO 40 PSF (40 PSF AT ROOFS). <br />A. ALL NEW OPENINGS THROUGH EXISTING MASONRY OR CONCRETE WALLS, SLABS, AND BEAMS SHALL BE <br />ACCOMPLISHED BY SAWCUTTING WHEREVER POSSIBLE. UNLESS OTHERWISE NOTED, ALL NEW OPENINGS SHALL <br />BE SAWCUT NEAT AND CLEAN; NO OVERCUTTING AT OPENING CORNERS SHALL BE ALLOWED. AS R€QUIR€D, <br />CORE DRILL CORNERS AND CHIP, GRIND OR CUT THE CORNERS TO PROVIDE THE REQUIRED DIMENSIONS. <br />B. CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS AND LOCATION OF MEMBERS PRIOR TO CUTTING ANY OPENINGS. <br />C. SMALL ROUND OPENINGS SHALL BE ACCOMPLISHED BY CORE DRILLING, IF POSSIBLE. HOLES UP TO 1" MAY BE <br />ROTOHAMMERED. <br />EXISTING REINFORCING SHALL BE SAVED UNLESS OTHERWISE NOTED. SAW CUTTING; DRILLING, OR CORING SHALL NOT CUT <br />EXISTING REINFORCING WHICH IS TO BE SAVED. <br />A2� CONCRETE. <br />20. CONCRETE SHALL BE MIXED, PROPORTIONED, CONVEYED AND PLACED IN ACCORDANCE WITH ACI 318-14 CHAPTER 26 AND ACI <br />301. CONCRETE SHALL ATTAIN A 28-DAY STRENGTH OF f'c = 4,500 PSI. <br />ALL CONCRETE SHALL BE EXPOSURE CLASSES F1, S0, W0, Cl PER ACI 318-14 TABLES 19.3.1.1 AND 19.3.2.1. <br />CONCRETE MIXES SHALL MEET OR EXCEED THE REQUIREMENTS SPECIFIED ABOVE. MIXES SHALL BE SUBMITTED TO THE <br />ENGINEER AND BUILDING OFFICIAL FOR APPROVAL TWO WEEKS PRIOR TO PLACING ANY CONCRETE AND SHALL INCLUDE THE <br />AMOUNTS OF CEMENT, CEMENTITOUS MATERIAL, FINE AND COARSE AGGREGATE, WATER AND ADMIXTURES, AS WELL AS THE <br />WATER -CEMENT RATIO, SLUMP, CONCRETE YIELD AND SUBSTANTIATING STRENGTH DATA IN ACCORDANCE WITH ACI 318-145 <br />CHAPTER 26 AND 27. REVIEW OF MIX SUBMITTALS BY THE ENGINEER OF RECORD INDICATES ONLY THAT INFORMATION <br />PRESENTED CONFORMS GENERALLY WITH CONTRACT DOCUMENTS. CONTRACTOR OR SUPPLIER MAINTAINS FULL RESPONSIBILITY <br />FOR SPECIFIED PERFORMANCE. <br />21. REINFORCING STEEL SHALL CONFORM TO ASTM A615, GRADE 60, fy = 60,000 PSI. <br />22. REINFORCING STEEL SHALL BE DETAILED (INCLUDING HOOKS AND BENDS) IN ACCORDANCE WITH ACI 315-18 AND 318-14. <br />LAP ALL CONTINUOUS REINFORCEMENT(5 AND SMALLER) 40 BAR DIAMETERS OR 2'4" MINIMUM. PROVIDE CORNER BARS AT <br />ALL WALL INTERSECTIONS. LAP CORNER BARS (#5 AND SMALLER) 40 BAR DIAMETERS OR 2'®0" MINIMUM. <br />NO BARS PARTIALLY EMBEDDED IN HARDENED CONCRETE SHALL BE FIELD BENT UNLESS OTHERWISE NOTED ON THE DRAWINGS OR <br />APPROVED BY THE STRUCTURAL ENGINEER. <br />23. NON -SHRINK GROUT SHALL BE FURNISHED BY AN APPROVED MANUFACTURER AND SHALL BE MIXED AND PLACED IN STRICT <br />ACCORDANCE WITH THE MANUFACTURER'S INSTRUCTIONS. GROUT STRENGTH SHALL BE AT LEAST EQUAL TO THE MATERIAL ON <br />WHICH IT IS PLACED (6,000 PSI MINIMUM). <br />GENERAL STRUCTURAL -- <br />'' r , <br />FLOORS2.05 FIFTH FRAMING <br />S2.06 SIXTH FLOOR III FRAMING � <br />S5.01 DETAILS <br />S5.02 DETAILS <br />REVISIONS <br />1 ADD. #1 07/29/2021 <br />2 ADD. #2 11/12/2021 <br />11/12 <br />Lu <br />W <br />mom <br />LLJ <br />ui <br />. <br />.00 <br />Lu <br />t <br />x< <br />CPLNO <br />S190030-09 <br />DRAWN <br />KF <br />CHECKED <br />RHC <br />DATE <br />3/12/2021 <br />11/12/2021 1:35:22 PM CARevit Local\2020\BH-5-6 FLOOR_STRUCRTURAL_R20_alejandraiWXZSS.rvt <br />