Permit#: M2101-027
<br />Site Address: 22-0 OLYMPIC RLVO
<br />ABBREVIATIONS
<br />AD
<br />ACCESS DOOR
<br />AFF
<br />ABOVE FINISHED FLOOR
<br />AHU
<br />AIR HANDLING UNIT
<br />AHJ
<br />AUTHORITIES HAVING JURISDICTION
<br />AHRI
<br />AIR COND, HTG, REFRIGERATION INSTITUTE
<br />AP
<br />ACCESS PANEL
<br />ARCH
<br />ARCHITECT OR ARCHITECTURAL
<br />ASCE
<br />AMERICAN SOCIETY CIVIL ENGINEERS
<br />ASHRAE
<br />AMERICAN SOCIETY OF HEATING,
<br />REFRIGERATION & AIR COND ENGINEERS
<br />BC
<br />VRF BRANCH CIRCUIT CONTROLLER
<br />BDD
<br />BACKDRAFT DAMPER
<br />BOD
<br />BOTTOM OF DUCT
<br />BTUH
<br />BRITISH THERMAL UNITS PER HOUR
<br />CD
<br />CEILING DIFFUSER
<br />CFM
<br />CUBIC FEET PER MINUTE
<br />CLG
<br />CEILING
<br />COND
<br />CONDENSATE
<br />COP
<br />COEFFICIENT OF PERFORMANCE
<br />DB
<br />DRY BULB
<br />DBA
<br />DECIBELS A SCALE
<br />DN
<br />DOWN
<br />DOAS
<br />DEDICATED OUTSIDE AIR SYSTEM
<br />(E)
<br />EXISTING
<br />EA
<br />EXHAUST AIR
<br />EC
<br />ELECTRICAL CONTRACTOR
<br />ECM
<br />ELECTRONICALLY COMMUTATED MOTOR
<br />ECON
<br />ECONOMIZER
<br />EER
<br />ENERGY EFFICIENCY RATIO
<br />EF
<br />EXHAUST FAN
<br />EG
<br />EXHAUST GRILLE
<br />ELEV
<br />ELEVATION
<br />ERV
<br />ENERGY RECOVERY VENTILATOR
<br />ESP
<br />EXTERNAL STATIC PRESSURE
<br />FCU
<br />FAN COIL UNIT
<br />FF
<br />FINISHED FLOOR
<br />FLA
<br />FULL LOAD AMPERAGE
<br />FPM
<br />FEET PER MINUTE
<br />FT
<br />FEET
<br />GC
<br />GENERAL CONTRACTOR
<br />GRD
<br />GRILLS, REGISTERS, DIFFUSERS
<br />HP
<br />HEAT PUMP
<br />HSPF
<br />HTG SEASONAL PERFORMANCE FACTOR
<br />HVAC
<br />HEATING, VENTILATING, AIR-CONDITIONING
<br />HZ
<br />HERTZ (FREQUENCY 60 HZ)
<br />IBC
<br />INTERNATIONAL BUILDING CODE
<br />IDU
<br />INDOOR UNIT
<br />IEER
<br />INTEGRATED ENERGY EFFICIENCY RATIO
<br />IFC
<br />INTERNATIONAL FIRE CODE
<br />IFGC
<br />INTERNATIONAL FUEL GAS CODE
<br />IMC
<br />INTERNATIONAL MECHANICAL CODE
<br />IN
<br />INCHES
<br />IN WG
<br />INCHES WATER GAUGE
<br />IOM
<br />INSTALLATION, OPERATION MANUAL
<br />KCO
<br />KING COUNTY
<br />L
<br />LOUVER (INTAKE, RELIEF OR EXHAUST)
<br />LAT
<br />LEAVING AIR TEMPERATURE
<br />M
<br />MOTOR OPERATED DAMPER
<br />MBH
<br />1,000 BTU PER HOUR
<br />MC
<br />MECHANICAL CONTRACTOR
<br />MCA
<br />MINIMUM CURRENT AMPACITY
<br />MIN
<br />MINIMUM
<br />MOCP
<br />MAX OVER CURRENT PROTECTION
<br />NEC
<br />NATIONAL ELECTRIC CODE
<br />NIC
<br />NOT IN CONTRACT
<br />NOM
<br />NOMINAL
<br />OSA
<br />OUTSIDE AIR
<br />ODU
<br />OUTDOOR UNIT
<br />PC
<br />PLUMBING CONTRACTOR
<br />PH
<br />ELEC POWER PHASE (1 0 OR 30)
<br />PN
<br />PROJECT NORTH (REFERENCE)
<br />POC
<br />POINT OF CONNECTION
<br />RA
<br />RETURN OR RELIEF AIR
<br />RCP
<br />REFLECTED CEILING PLAN
<br />REF
<br />REFERENCE
<br />RG
<br />RETURN GRILLE
<br />RH
<br />ROOF HOOD
<br />RS/RL
<br />REFRIGERANT SUCTION/LIQUID LINE
<br />RTU
<br />ROOF TOP UNIT
<br />SA
<br />SUPPLY AIR
<br />SD
<br />SMOKE DETECTOR
<br />SEER
<br />SEASONAL ENERGY EFFICIENCY RATIO
<br />SG
<br />SUPPLY GRILLE
<br />SO
<br />SCREENED OPENING
<br />SOW
<br />SCOPE OF WORK
<br />SMACNA
<br />SHEET METAL NATIONAL ASSOCIATION
<br />TA
<br />TRANSFER AIR
<br />TG
<br />TRANSFER GRILLE
<br />T-STAT
<br />THERMOSTAT
<br />TSP
<br />TOTAL STATIC PRESSURE
<br />TYP
<br />TYPICAL
<br />UNO
<br />UNLESS NOTED OTHERWISE
<br />UPC
<br />UNIFORM PLUMBING CODE
<br />V
<br />VOLTS
<br />VD
<br />VOLUME DAMPER
<br />VFC
<br />VRF FAN COIL UNIT
<br />VFD
<br />VARIABLE FREQUENCY DRIVE
<br />VHP
<br />VRF OUTDOOR UNIT
<br />VIF
<br />VERIFY IN FIELD
<br />VRF
<br />VARIABLE REFRIGERANT FLOW
<br />W
<br />WATTS
<br />WSEC
<br />2015 WASHINGTON STATE ENERGY CODE
<br />GENERAL -LEGEND
<br />GENERAL NOTES
<br />1. DRAWINGS FOR MECHANICAL WORK WITHIN THE BUILDING SPACE AND
<br />ROOFTOP ARE DIAGRAMMATIC AND INTENDED TO CONVEY SCOPE AND
<br />GENERAL ARRANGEMENT ONLY.
<br />2. THE ACCURACY AND COMPLETENESS OF THE DESIGN CONTENT ON
<br />THESE DRAWINGS REQUIRES FIELD VERIFICATION FOR ALL UNIT AND
<br />DUCTWORK LOCATIONS AND DIMENSIONS PRIOR TO START OF
<br />MECHANICAL WORK. IN GENERAL, THE MECHANICAL SCOPE OF WORK IS
<br />BOUNDED BY THE BUILDING EXTERIOR WALLS AND ROOFTOP, PER PLAN.
<br />3. COORDINATE ALL NEW WORK WITH THE STRUCTURE AND OTHER TRADES.
<br />FIELD VERIFY UNIT LOCATIONS, DROPS AND POSITIONS. HVAC EQUIPMENT
<br />WEIGHTS AND LOCATIONS SHALL BE APPROVED BY THE PROJECT
<br />STRUCTURAL ENGINEER.
<br />4. ITEMS NOTED "TYPICAL" OR "TYP" ON ANY SHEET APPLY TO THAT
<br />PARTICULAR SHEET.
<br />5. MECHANICAL EQUIPMENT SHALL NOT BE USED FOR TEMPORARY HEAT
<br />DURING CONSTRUCTION, NO EXCEPTIONS.
<br />6. HVAC SYSTEMS HAVE BEEN DESIGNED PER THE REQUIREMENTS OF THE
<br />2015 WASHINGTON STATE ENERGY CODE (COMMERCIAL), 2015
<br />INTERNATIONAL BUILDING CODE AND THE 2015 INTERNATIONAL
<br />MECHANICAL CODE. ALL CODES INCLUDE APPLICABLE WASHINGTON STATE
<br />AND CITY AMENDMENTS.
<br />7. TEMPERATURE SENSORS AND PROGRAMMABLE THERMOSTATIC CONTROLS
<br />ARE REQUIRED FOR EACH MECHANICAL UNIT. SENSORS MAY BE LOCATED
<br />NEAR RETURN AIR GRILLES OF THE UNIT SERVED. IF SENSORS ARE
<br />SURFACE MOUNTED ON THE WALLS, THEY MUST BE AT 48" MAX AFF
<br />FOR ADA ACCESSIBILITY WITH WIRING CONCEALED OR AS EXPLICITLY
<br />DIRECTED BY THE ARCHITECT. SEE MECHANICAL PLANS FOR FINAL
<br />LOCATIONS.
<br />8. ALL LINE VOLTAGE WORK SHALL BE BY A LICENSED COMMERCIAL
<br />ELECTRICIAN UNDER SEPARATE PERMIT.
<br />9. PROVIDE NEC CODE MINIMUM HORIZONTAL AND VERTICAL WORKING
<br />CLEARANCES FOR ALL ELECTRICAL PANELS AND EQUIPMENT. OFFSET
<br />MECHANICAL WORK AS REQUIRED.
<br />10. A 120-VOLT SERVICE RECEPTACLE BY ELECTRICAL CONTRACTOR SHALL
<br />BE LOCATED WITHIN 25' OF EACH PIECE OF EQUIPMENT. DISCONNECTING
<br />MEANS OF THE EQUIPMENT SHALL BE BY THE ELECTRICAL CONTRACTOR.
<br />11. SUPPLY AND RETURN AIR DUCTWORK SHALL BE LINED WITH 1" SOUND
<br />LINER WITHIN 10' OF EQUIPMENT. ON LINED DUCT, THE DIMENSIONS
<br />SHOWN ARE INSIDE CLEAR.
<br />12. MAXIMUM FLEXIBLE DUCT LENGTH SHALL BE 8'-0".
<br />13. MAINTAIN 10'-0" MINIMUM DISTANCE BETWEEN OUTSIDE AIR INTAKES
<br />AND PLUMBING VENTS, EXHAUST AND COMBUSTION AIR OUTLETS.
<br />----- 14. PIPE AND DUCT DIMENSIONS SHOWN ARE NOMINAL SIZES.
<br />PIPE TURNING UP OR TOWARD
<br />PIPE TURNING DOWN OR AWAY 15. ALL DUCTWORK SIZES SHOWN ARE INSIDE CLEAR. ADD APPROPRIATE
<br />DIMENSIONS FOR INSULATION OR DUCT LINER TO OBTAIN THE "TOTAL"
<br />7 PLUG AND/OR CAP DUCT SIZE.
<br />-CD- CONDENSATE DRAIN
<br />APPROVE COMMISSIONING - MECHANICAL
<br />-RSREFRIGERANT SUCTION PLANNING
<br />RL REFRIGERANT LIQUID DEVELO MENT DEP I. PROVIDE COMMISSIONING PER SECTION C408 OF THE WSEC COMMERCIAL
<br />G NATURAL GAS PIPING I3Y `_PROVISIONS. COPIES OF ALL EQUIPMENT DATA AND DOCUMENTATION THAT
<br />DATE s P RELATES TO COMMISSIONING, SHALL BE PROVIDED TO THE OWNER AND MADE
<br />-> -- SHUT-OFF VALVE AVAILABLE TO THE AHJ WITHIN 90 DAYS OF RECEIPT OF COO, INCLUDING:
<br />NOTICE: Screening IbEtequlred
<br />-tlU1 FLEXIBLE CONNECTION for rooftop equipment. Chec4*RhPP RMIT AND INSPECTION RECORDS.
<br />planning Department at (425) 267-873
<br />HVAC-LEGEND for permit requireme'�ts2' DUCTWORK PRESSURE TESTING REPORTS.
<br />® SUPPLY OR OSA DUCT SECTION 3. DUCTWORK AND AHU EQUIPMENT FLUSHING AND CLEANING REPORTS
<br />G RETURN, RELIEF OR EXHAUST DUCT SECTION 4. COMMISSIONING (Cx) PLAN, PRELIMINARY Cx REPORT, Cx COMPLIANCE
<br />CHECKLIST (2015 WSEC FIGURE C408.1.4.2) AND OTHER RELATED
<br />RGx-100 RETURN AIR GRILLE, NUMBER INDICATES CFM REPORTS, SUCH AS START-UP, HVAC AIR BALANCING AND
<br />Z CDx-100 SUPPLY AIR DIFFUSER, NUMBER INDICATES CFM PERFORMANCE TESTING.
<br />EGx-100 EXHAUST AIR GRILLE, NUMBER INDICATES CFM 5. RECORD DRAWINGS DEPICTING FINAL INSTALLATION CONFIGURATIONS OF
<br />Z SYSTEMS AND EQUIPMENT AS REQUIRED BY 2015 WSEC SECTION
<br />DUCT -ti-- SUPPLY, RETURN/EXH GRILLE (SIDEWALL) C103.6.
<br />-� DUCT: 1ST SIZE (IN) INDICATES SIDE SHOWN 6. IOM EQUIPMENT MANUALS SHALL INCLUDE MFG INFORMATION WITH
<br />24x12 2ND SIZE (IN) INDICATES SIDE NOT SHOWN MODEL NUMBERS AND OPTIONS, CONTROLS DATA, INCLUDING
<br />CALIBRATION AND DESIGN SETPOINT INFORMATION, AND RECOMMENDED
<br />SL SOUND LINED SHEET METAL (SLSM) MAINTENANCE SCHEDULE WITH CSUSA NW CONTACT INFORMATION.
<br />FLEXIBLE DUCTWORK 7. TRAINING OF THE MAINTENANCE STAFF SHALL BE PROVIDED, INCLUDING
<br />REVIEW OF DOCUMENTATION, HANDS-ON DEMONSTRATION OF OPERATION
<br />FSD COMBINATION FIRE/SMOKE DAMPER (FSD) AND START-UP PROCEDURES AND TRAINING COMPLETION REPORT.
<br />FD 8. WHOLE BUILDING AND COMMISSIONING OF SYSTEMS THAT ARE NOT
<br />FIRE DAMPER (FD) 1.5 HR, UNO INCLUDED IN THE MECHANICAL CONTRACTOR'S SOW SHALL BE PROVIDED,
<br />sD IN ACCORDANCE WITH 2015 WSEC SECTION C408.1, BY OTHERS.
<br />SMOKE DAMPER (SD)
<br />RELATED PERMITS
<br />UD
<br />VOLUME DAMPER (VD) 1. BUILDING PERMIT: UNDER APPLICATION (SEE ARCH PLANS)
<br />2i. MECHANICAL PERMIT: UNDER APPLICATION (BY CSNW)
<br />M
<br />MOTORIZED DAMPER (MOD) 3. PLUMBING PERMIT: UNDER APPLICATION (THIS PLAN SET)
<br />BDD 4. ELECTRICAL PERMIT: UNDER APPLICATION (BY OTHERS)
<br />BACKDRAFT DAMPER (BDD)
<br />HEAVY LINE INDICATES NEW WORK
<br />LIGHT LINE INDICATES EXISTING WORK
<br />11-A EXISTING WORK TO BE REMOVED
<br />-►-- PIPELINE - NORMAL DIRECTION OF FLOW
<br />0 KEY NOTE CALLOUT
<br />PHOTO ID CALLOUT
<br />MEDICAL OUTLET CALLOUT,
<br />SEE SCHEDULE
<br />PLUMBING FIXTURE TYPE CALLOUT,
<br />REFERENCE TO ARCHITECTURAL SHEETS
<br />POINT OF CONNECTION TO EXISTING
<br />OR TO OTHER WORK
<br />WH-1 PLUMBING FIXTURE CALLOUT,
<br />SEE SCHEDULE
<br />0 INDICATES DIAMETER OR ROUND
<br />RTU - EQUIPMENT TAG TYPE
<br />1 ---- EQUIPMENT TAG NUMBER
<br />1 -- DETAIL OR DIAGRAM NUMBER
<br />MX-X --- SHEET NUMBER WHERE DETAIL/DIAGRAM
<br />SHOWN
<br />--- SECTION LETTER
<br />A
<br />�-x -.--- SHEET NUMBER WHERE SECTION SHOWN
<br />1
<br />REVISION CLOUD AND CHRONOLOGICAL
<br />NUMBER
<br />DETAIL REFERENCE OUTLINE
<br />�- HVAC UNIT
<br />SERVICE CLEARANCE
<br />CONTROL WIRING OR TUBING
<br />Q-� THERMOSTAT
<br />Q-� RELATIVE HUMIDITY SENSOR
<br />CARBON MONOXIDE/CARBON DIOXIDE SENSOR
<br />qs DUCT SMOKE DETECTOR
<br />oc OCCUPANCY SENSOR
<br />sw SWITCH (ON/OFF OR TIMER)
<br />HVAC PIPING - LEGEND
<br />LEGAL DESCRIPTION
<br />ASSESSORS PARCEL NUMBER: 00606200004102
<br />SITUATED IN THE COUNTY OF SNOHOMISH, STATE OF WASHINGTON, AND IS
<br />DESCRIBED AS FOLLOWS:
<br />TRACT 41, VIEW RIDGE ADDITION TO EVERETT DIVISION NO. 2, ACCORDING TO
<br />THE PLAT THEREOF RECORDED IN VOLUME 12 OF PLATS, PAGE 19,
<br />RECORDS OF SNOHOMISH COUNTY, WASHINGTON;
<br />TOGETHER WITH THAT PORTION OF VACATED ELM STREET LYING WEST OF
<br />AND ADJACENT TO SAID PREMISES AND EASTERLY OF THE EAST LINE OF
<br />THE NEW ELM STREET;
<br />EXCEPT FROM THE FOREGOING THE FOLLOWING DESCRIBED TRACT:
<br />BEGINNING
<br />AT THE SOUTHEAST
<br />CORNER
<br />OF TRACT 41; THENCE WEST ON
<br />THE SOUTH LINE OF SAID LOT
<br />FOR 155
<br />FEET; THENCE NORTH PARALLEL
<br />WITH THE
<br />EAST LINE OF SAID
<br />LOT FOR
<br />125 FEET; THENCE EAST PARALLEL
<br />WITH THE
<br />SOUTH LINE OF SAID LOT FOR 155 FEET TO THE EAST LINE
<br />THEREOF;
<br />THENCE SOUTH 125
<br />FEET TO
<br />THE POINT OF BEGINNING.
<br />APPLICABLE CODES
<br />ALL CODES BELOW TO INCLUDE APPLICABLE CITY OF AMENDMENTS:
<br />1. 2015 WASHINGTON STATE ENERGY CODE (WAC CHAPTER 51-11)
<br />2. 2015 INTERNATIONAL BUILDING CODE (WAC CHAPTER 51-50)
<br />3. 2015 INTERNATIONAL MECHANICAL CODE (WAC CHAPTER 51-52)
<br />4. 2015 INTERNATIONAL FUEL GAS CODE (WAC CHAPTER 51-52)
<br />5. 2015 UNIFORM PLUMBING CODE (WAC CHAPTER 51-56)
<br />6. NATIONAL ELECTRICAL CODE (NFPA 70 - WAC CHAPTER 296)
<br />BUILDING INFORMATION
<br />PROJECT ADDRESS: VA CBOC
<br />220 OLYMPIC BOULEVARD
<br />EVERETT, WA 98203
<br />OWNER: PURPLE HEART HEROES, LLC
<br />1800 AVENUE OF THE STARS, FLOOR 12
<br />LOS ANGELES, CA 90067
<br />CONTACT: MIKE COCCO, VP CATALYST CAPITAL
<br />TEL: (973) 437-5202
<br />EMAIL: MCOCCO®CATALYSTCAP.COM
<br />ARCHITECT: ROTH SHEPPARD ARCHITECTS, LLP
<br />1900 WAZEE STREET, SUITE 100
<br />DENVER, CO 80202
<br />CONTACT: NATALIE SEIFERT, AIA, LEED AP
<br />TEL: (303) 534-7007, EXT 1120
<br />EMAIL: NSEIFERT®ROTHSHEPPARD.COM
<br />GENERAL CONTRACTOR: FOUSHEE & ASSOCIATES
<br />3260 118TH AVE SE, SUITE 1000
<br />BELLEVUE, WA 98005
<br />CONTACT: JOHN DOLENCE, OPERATIONS MANAGER
<br />TEL: (425) 957-2136
<br />EMAIL: JDOLENCE®FOUSHEE.COM
<br />CONSTRUCTION TYPES: 2-STORY, TYPE V-B, FULLY SPRINKLERED
<br />PRIMARY OCCUPANCIES: BUSINESS (B), ASSEMBLY (A-3)
<br />CONSTRUCTION: 2020 START, NEW STRUCTURE
<br />TOTAL BUILDING AREA: 29,066 GSF
<br />BUILDING HEIGHT: 2-STORY, +35'-0" PROPOSED PROJECT HEIGHT
<br />CLIMATE ZONE: 4C - SNOHOMISH
<br />NEW CONSTRUCTION OF A 29,066 GSF, TWO-STORY ABOVE GRADE
<br />COMMERCIAL STRUCTURE, PER ARCH PLANS, ENTIRE BUILDING WILL BE FOR
<br />A COMMUNITY BASED OUTPATIENT CLINIC FOR THE VETERANS ADMINISTRATION.
<br />MECHANICAL SCOPE
<br />MECHANICAL WORK TO PROVIDE ALL NEW MECHANICAL HVAC SYSTEMS IN
<br />SUPPORT OF A NEW 2-STORY ABOVE GRADE STRUCTURE, PER PLAN.
<br />MECHANICAL WORK UNDER THIS PERMIT IS FOR THE COMPLETE BUILD -OUT
<br />AND INCLUDES THE FOLLOWING:
<br />1. NEW MECHANICAL HVAC SYSTEMS AND EQUIPMENT TO PROVIDE HEATING,
<br />VENTILATION AND COOLING IN SELECT AREAS, PER PLAN. THE BASIS OF
<br />DESIGN IS THREE (3) PACKAGED VAV (GAS/DX) ROOFTOP UNITS FOR A
<br />MULTIZONE SYSTEM WITH TERMINAL REHEAT AND VAV TERMINAL BOXES.
<br />2. FOUR (4) 1.5 TON HEAT PUMPS FOR MISCELLANEOUS PROCESS LOADS.
<br />3. DIRECT EXHAUST FAN SYSTEMS SERVING ALL RESTROOMS, JANITOR
<br />CLOSETS, KITCHEN BREAKROOM AND MISCELLANEOUS STORAGE SPACES.
<br />4. GAS PIPING (2 PSIG) FROM GAS METER TO RTU'S AND WATER HEATER.
<br />5. ALL RELATED ACCESSORIES FOR A COMPLETE SYSTEM, SUCH AS
<br />GRILLES, REGISTERS, DIFFUSERS, LOW -LEAK SHUT-OFF AND VOLUME
<br />DAMPERS, SHEETMETAL DUCTWORK, INSULATION, ELECTROMECHANICAL
<br />PACKAGED CONTROLS AND PROGRAMMABLE THERMOSTATS.
<br />6. EQUIPMENT AND SYSTEMS START-UP, TESTING, CLEANING, AIR -BALANCE,
<br />PROGRAMMING AND OWNER TRAINING FOR NEW EQUIPMENT, 0&M
<br />MANUAL AND RECORD DRAWINGS.
<br />7. SEE ATTACHED STRUCTURAL DESIGNS ON M5.01 AND CALCULATIONS FOR
<br />SEISMIC ATTACHMENT OF EQUIPMENT OVER 400 LB TO STRUCTURE.
<br />VICINITY MAP
<br />SITE MAP (BY GOGGLE EARTH, NOT TO SCALE)
<br />DRAWING INDEX
<br />PAGE #
<br />SHEET #
<br />SHEET TITLE
<br />SCALE
<br />1
<br />MO.01
<br />COVER SHEET, LEGEND & NOTES
<br />N/A
<br />2
<br />MO.02
<br />SCHEDULES AND NOTES - MECHANICAL
<br />N/A
<br />3
<br />MO.03
<br />SCHEDULES AND NOTES - MECHANICAL
<br />N/A
<br />4
<br />MO.04
<br />SCHEDULES AND NOTES - MECHANICAL
<br />N/A
<br />5
<br />MO.05
<br />2015 WSEC FORMS - MECHANICAL
<br />N/A
<br />6
<br />MO.06
<br />2015 WSEC FORMS - MECHANICAL
<br />N/A
<br />7
<br />MO.07
<br />2015 WSEC FORMS - MECHANICAL
<br />N/A
<br />8
<br />MO.08
<br />HVAC LOAD CALCS
<br />N/A
<br />9
<br />MO.09
<br />HVAC LOAD CALCS
<br />N/A
<br />10
<br />MO.10
<br />HVAC LOAD CALCS
<br />N/A
<br />11
<br />MO.11
<br />HVAC LOAD CALCS
<br />N/A
<br />12
<br />MO.12
<br />HVAC LOAD CALCS
<br />N/A
<br />13
<br />MO. 13
<br />HVAC LOAD CALCS
<br />N/A
<br />14
<br />M 1.01
<br />SITE PLAN - MECHANICAL
<br />1 it = 20'-0"
<br />15
<br />M2.01
<br />FIRST FLOOR PLAN - MECHANICAL
<br />1/8" = 1'-0"
<br />16
<br />M2.02
<br />SECOND FLOOR PLAN - MECHANICAL
<br />1/8 of = 1'-0"
<br />17
<br />M2.03
<br />ROOF PLAN - MECHANICAL
<br />1 /8" = 1'-0"
<br />18
<br />M3.01
<br />ELEVATIONS - N & S - MECHANICAL
<br />1 /8" = 1'-0"
<br />19
<br />M3.02
<br />ELEVATIONS - E & W - MECHANICAL
<br />1/8 of = 1'-0"
<br />20
<br />M4.01
<br />MECHANICAL DETAILS
<br />N/A
<br />21
<br />M4.02
<br />SEQUENCE OF OPERATION - MECHANICAL
<br />N/A
<br />22
<br />M5.01
<br />RTU ANCHORAGE PLANS & DETAILS
<br />3/16" = 1'-0"
<br />Owner:
<br />CATALYST CAPITAL
<br />Tenant:
<br />VA OUTPATIENT CLINIC
<br />App.Date:
<br />1/11/2021
<br />Proposed Use: NEW COMMERCIAL
<br />Description:
<br />MECH FOR NEW VA OUTPATIENT CLJ
<br />Reviewed By: Date:
<br />A�
<br />Office Set Job Site Set Fire/Plannin
<br />rKtvtN I UNAUTHORIZED COPYING,
<br />PUBLICATION OR USE OF THIS
<br />LAYOUT/DESIGN AND TO OBTAIN
<br />DAMAGES THEREFORE.
<br />0
<br />CD
<br />w �
<br />� w
<br />m
<br />Cn N =
<br />Qo v o
<br />I- N O Q
<br />=c o�
<br />w ¢ oO W
<br />W WI-
<br />C� -� W W
<br />0
<br />W =W CK
<br />L oo QU_
<br />zm o
<br />�M sCN
<br />00
<br />0 >0 p
<br />001 z
<br />SIGNED: 12/11 /2020
<br />W
<br />W
<br />Q
<br />~
<br />W
<br />Q
<br />LJJ
<br /><C
<br />LY-
<br />>
<br />W
<br />ACV
<br />W
<br /><C
<br />W
<br />�
<br />a
<br />'
<br />U
<br />U
<br />>°°Q
<br />W
<br />U
<br />Z
<br />,
<br />U
<br />°°ory
<br />Q
<br />>
<br />CG'
<br />0,
<br />>
<br />N
<br />W
<br />W
<br />REVISIONS
<br />1. PERMIT SET 12-11-2020
<br />2. - -
<br />3. - -
<br />5. - -
<br />DESIGNED
<br />CSUSA NW / SL / EE
<br />CHECKED
<br />CSUSA NW / SL / EE
<br />DATE
<br />7-24-2020
<br />JOB NUMBER
<br />120019
<br />SHEET SIZE
<br />ARCH D: 24" x 36"
<br />SHEET TITLE
<br />COVER SHEET,
<br />LEGEND & NOTES
<br />SHEET NUMBER
<br />M0001
<br />SHEET 1 OF 22