MOTORIZED DAMPER <br />SCHEDULE <br />AIRFLOW <br />MAX AIRFLOW <br />60HZ <br />POWER <br />TAG <br />SYSTEM <br />MANUFACTURER - MODEL <br />DESCRIPTION <br />LOCATION <br />APPLICATION <br />DIRECTION <br />(CFM) <br />ACTUATOR <br />POWER <br />(W) <br />NOTES: <br />MD-1 <br />EF-1 <br />RUSKIN, <br />VCDR-53 <br />WSEC <br />LOW <br />LEAK <br />DAMPER <br />CLASS 1 <br />DUCT <br />MOUNTED <br />SHUT-OFF <br />EXHAUST <br />300 <br />120VAC/10 <br /><20 <br />W <br />1, 2, <br />3, <br />4 <br />MD-2 <br />EF-2 <br />RUSKIN, <br />VCDR-53 <br />WSEC <br />LOW <br />LEAK <br />DAMPER <br />CLASS 1 <br />DUCT <br />MOUNTED <br />SHUT-OFF <br />EXHAUST <br />300 <br />120VAC/10 <br /><20 <br />W <br />1, 2, <br />3, <br />4 <br />MD-3 <br />EF--3 <br />RUSKIN, <br />VCDR-®53 <br />WSEC <br />LOW <br />LEAK <br />DAMPER <br />CLASS 1 <br />DUCT <br />MOUNTED <br />SHUT-OFF <br />EXHAUST <br />500 <br />120VAC/10 <br /><20 <br />W <br />1, 2, <br />3, <br />4 <br />MD-4 <br />EF-4 <br />RUSKIN, <br />VCDR-53 <br />WSEC <br />LOW <br />LEAK <br />DAMPER <br />CLASS 1 <br />DUCT <br />MOUNTED <br />SHUT-OFF <br />EXHAUST <br />200 <br />120VAC/10 <br /><20 <br />W <br />1, 2, <br />3, <br />4 <br />NOTES: <br />1. EQUIPMENT MAY BE SUBSTITUTED, REFER TO APPROVED EQUIPMENT SUBMITTALS FOR FINAL SELECTIONS. <br />2. MOTORIZED DAMPERS PROVIDED AT THE BUILDING ENVELOPE AS REQUIRED BY THE WSEC. <br />3. PROVIDE WITH BELIMO TWO POSITION ACTUATOR, POWER OPEN, SPRING CLOSE. <br />4. ACTUATOR TIED TO THE THE EXHAUST FAN AND OPENS WHEN THE FAN RUNS. <br />TERMINAL UNIT <br />SCHEDULE <br />MINIMUM <br />MAXIMUM <br />INLET <br />60 HZ ELECTRICAL <br />PRIMARY <br />PRIMARY <br />SIZE <br />_ <br />TAG <br />MAKE <br />& MODEL <br />UNIT SIZE <br />DESCRIPTION <br />SERVES <br />ASSOCIATED <br />RTU <br />AIR (CFM) <br />AIR (CFM) <br />(INCHES) <br />VOLT PH AMPS MOCP CONTROLS <br />WT (LBS) <br />NOTES <br />TU-1 <br />NAILOR <br />D30RE <br />7 <br />VARIABLE <br />VOLUME <br />INTERIOR <br />ZONE <br />(L1) <br />RTU-1 <br />130 <br />650 <br />7"0 <br />- DIGITAL <br /><150 <br />1, 2, <br />3 <br />TU-2 <br />NAILOR <br />D30RE <br />8 <br />VARIABLE <br />VOLUME <br />INTERIOR <br />ZONE <br />(L1) <br />RTU-1 <br />160 <br />900 <br />8"0 <br />- <br />DIGITAL <br /><150 <br />1, 2, <br />3 <br />TU-3 <br />NAILOR <br />D30RE <br />7 <br />VARIABLE <br />VOLUME <br />INTERIOR <br />ZONE <br />(0) <br />RTU-1 <br />130 <br />650 <br />7"0 <br />- <br />- <br />DIGITAL <br /><150 <br />1, 2, <br />3 <br />TU-4 <br />NAILOR <br />D30RE <br />7 <br />VARIABLE <br />VOLUME <br />INTERIOR <br />ZONE <br />(L1) <br />RTU--1 <br />120 <br />600 <br />7"0 <br />- <br />- <br />- <br />DIGITAL <br /><150 <br />1, 2, <br />3 <br />TU-5 <br />NAILOR <br />D30RE <br />6 <br />VARIABLE <br />VOLUME <br />INTERIOR <br />ZONE <br />(L1) <br />RTU-2 <br />100 <br />500 <br />6"0 <br />- <br />DIGITAL <br /><150 <br />1, 2, <br />3 <br />TU-6 <br />NAILOR <br />D30RE <br />6 <br />VARIABLE <br />VOLUME <br />INTERIOR <br />ZONE <br />(L1) <br />RTU-2 <br />90 <br />450 <br />6" 0 <br />- <br />- <br />DIGITAL <br /><150 <br />1, 2, <br />3 <br />TU-7 <br />NAILOR <br />D30RE <br />7 <br />VARIABLE <br />VOLUME <br />INTERIOR <br />ZONE <br />(L1) <br />RTU-2 <br />120 <br />600 <br />7"0 <br />- <br />- <br />- <br />_ <br />DIGITAL <br /><150 <br />1, 2, <br />3 <br />TU-6 <br />NAILOR <br />D30RE <br />7 <br />VARIABLE <br />VOLUME <br />INTERIOR <br />ZONE <br />(L1) <br />RTU-2 <br />110 <br />550 <br />7"0 <br />- <br />DIGITAL <br /><150 <br />1, 2, <br />3 <br />TU-9 <br />NAILOR <br />D30RE <br />7 <br />VARIABLE <br />VOLUME <br />INTERIOR <br />ZONE <br />(L1) <br />RTU-2 <br />125 <br />625 <br />7"0 <br />- <br />- <br />DIGITAL <br /><150 <br />1, 2, <br />3 <br />TU-10 <br />NAILOR <br />D30RE <br />7 <br />VARIABLE <br />VOLUME <br />INTERIOR <br />ZONE <br />(L1) <br />RTU-2 <br />120 <br />600 <br />7"0 <br />- <br />- <br />- <br />DIGITAL <br /><150 <br />1, 2, <br />3 <br />TO -11 <br />NAILOR <br />D30RE <br />6 <br />VARIABLE <br />VOLUME <br />INTERIOR <br />ZONE <br />(L2) <br />RTU-3 <br />100 <br />500 <br />6"0 <br />- <br />- <br />DIGITAL <br /><150 <br />1, 2, <br />3 <br />NOTES: <br />1. EQUIPMENT MAY BE SUBSTITUTED FOR EQUAL OR BETTER MANUFACTURER. <br />2. TERMINAL UNIT PROVIDE VARIABLE AIR FLOW TO INTERIOR WITHOUT THE ADDITION OF AUXILIARY HEAT. <br />3. ONLY ELECTRICAL REQUIRED IS FOR CONTROLS (ACTUATOR POWER). <br />a <br />rLoffi <br />i s'll <br />TAG <br />MANUFACTURER AND MODEL <br />APPLICATION <br />SIZE (IN) <br />WxHxD <br />CAPACITY <br />(WATTS) <br />60 HZ ELECTRICAL <br />MOUNTING <br />WEIGHT <br />LBS <br />NOTES <br />VOLT <br />PH <br />AMPS <br />MOCP <br />EWH-1 <br />KING WALL HEATER PAW 1215 <br />VESTIBULE 100 <br />14x8x4.5 <br />500 <br />120 <br />1 <br />4.2 <br />15 <br />SURFACE MOUNT <br />9.5 <br />1, 2, 3 <br />EWH-2 <br />KING WALL HEATER PAW 1215 <br />STAFF ENTRY 112 <br />14x8x4.5 <br />500 <br />120 <br />1 <br />4.2 <br />15 <br />SURFACE MOUNT <br />9.5 <br />1, 2, 3 <br />EWH---3 <br />EWH-4 <br />EWH-5 <br />KING WALL HEATER PAW 1215 <br />KING WALL HEATER PAW 1215 <br />KING WALL HEATER PAW 1215 <br />SERVICE VESTIBULE 127.1 <br />FIRE RISER RM 170 <br />BUILDING SERVICES 172 <br />14x8x4.5 <br />1460.5 <br />14x8x4.5 <br />250 <br />250 <br />1,000 <br />120 <br />120 <br />120 <br />1 <br />1 <br />1 <br />2.1 <br />2.1 <br />8.4 <br />15 <br />15 <br />15 <br />RECESSED WALL <br />RECESSED WALL <br />RECESSED WALL <br />9.5 <br />9.5 <br />9.5 <br />1, 2, 3 <br />1, 2, 3 <br />1, 2, 3 <br />EWH-6 <br />KING UNIT HEATER KBP1230 <br />OTHER TENANT 216 <br />11x13.5x11 <br />2,500 <br />120 <br />1 <br />24 <br />15 <br />WALL/CEILING MOUNT <br />26 <br />1, 2, 3 <br />NOTES: <br />1. EQUIPMENT MAY BE SUBSTITUTED. REFER TO APPROVED EQUIPMENT SUBMITTALS FOR FINAL SELECTIONS. <br />2. PROVIDE UNIT WITH MANUFACTURER'S STANDARD INTEGRAL THERMOSTAT CONTROL. <br />3. ELECTRIC WALL HEATERS SIZED FOR 6 BTUH/SF FOR SEMI -HEATED OCCUPANCY, THE UNITS SELECTED ARE THE SMALLEST READILY <br />AVAILABLE SIZES, REFERENCE SEMI -HEATED SPACE CALCULATIONS. <br />GRILLES, <br />REGISTERS <br />AND <br />DIFFUSERS SCHEDULE <br />FACE SIZE <br />THROW <br />TAG <br />MAKE/MODEL <br />TYPE <br />(IN) <br />PATTERN <br />MATERIAL <br />COLOR <br />MOUNTING <br />REMARKS <br />SD-1 <br />TITUS OMNI <br />CEILING <br />SUPPLY <br />2424 <br />4 WAY <br />STEEL <br />WHITE <br />T-BAR <br />1, 2 <br />SD-2 <br />TITUS OMNI <br />CEILING <br />SUPPLY <br />12x12 <br />4 WAY <br />STEEL <br />WHITE <br />SURFACE (HARD LID) <br />1, 2 <br />LD®1 <br />TITUS FL-10 <br />CEILING <br />SUPPLY <br />48x 10 <br />1 WAY <br />ALUM <br />WHITE <br />T-BAR <br />1, 2, 3 <br />RG- 1 <br />TITUS 50F <br />CEILING <br />RETURN <br />2412 <br />- <br />ALUM <br />WHITE <br />T-BAR <br />1, 4 <br />RG-2 <br />TITUS 50F <br />CEILING <br />RETURN <br />2424 <br />ALUM <br />WHITE <br />T-BAR <br />1, 4 <br />EG- 1 <br />TITUS 350RL <br />CEILING <br />EXHAUST <br />12x 12 <br />STEEL <br />WHITE <br />SURFACE (HARD LID) <br />1, 2 <br />EG-2 <br />TITUS 350RL <br />CEILING <br />EXHAUST <br />2424 <br />- <br />STEEL <br />WHITE <br />T-BAR <br />1, 2 <br />NOTES: <br />1. GRDS MAY BE SUBSTITUTED. SEE APPROVED SUBMITTALS FOR FINAL SELECTION. <br />2. DIFFUSER NECK SIZE TO MATCH CONNECTING DUCT AS SHOWN ON THE MECHANICAL FLOOR PLANS. <br />3. TWO SLOT EACH SLOT 1" WIDE, PROVIDE PLENUM, TITUS FBPI-10. <br />4. PROVIDE WITH SOUND LINED BOOT, SEE MECHANICAL DETAILS. <br />2. HEATING, COOLING AND VENTILATION SYSTEMS HAVE BEEN <br />SIZED IN ACCORDANCE WITH STANDARD ENGINEERING <br />PRACTICES AND AS REQUIRED BY THE 2015 WSEC <br />SECTIONS C403.2.1 AND C403.2.2 FOR CLIMATE ZONE 4C <br />(EVERETT, WA IN SNOHOMISH COUNTY). OUTPUT CAPACITIES <br />OF ALL EQUIPMENT IS NOTED IN THE EQUIPMENT <br />SCHEDULES INCLUDED WITH THIS PLAN SET. <br />3. HVAC LOAD AND VENTILATION CALCULATIONS SHOWN ON <br />SHEETS MO.OB, MO.09, MO.10 AND MO.11. <br />4. HEATING AND COOLING LOAD CALCULATIONS USE THE <br />FOLLOWING BUILDING DESIGN CONDITIONS AND <br />TEMPERATURES IN ACCORDANCE WITH PROJECT PLANS AND <br />THE 2015 WSEC SECTIONS C302.1, C302.2 AND TABLE <br />C-1 FOR INTERIOR AND EXTERIOR OUTDOOR DESIGN <br />CONDITIONS FOR EVERETT, WA: <br />SITE COORDINATES: <br />FLOOR ELEVATION: <br />liffamiffiml <br />SUMMER DESIGN TEMP <br />WINTER DESIGN TEMP: <br />INDOOR DESIGN TEMP: <br />LAT 47.95°N, LON 122.23°W <br />+303.50' (FF REF +0' 0") <br />ZONE 4C - SNOHOMISH CO <br />EVERETT PAINE AP (APP. C) <br />72®F DB HEATING (MAXIMUM) <br />75®F DB COOLING (MINIMUM) <br />SUPPLY AIR HEATING: 95®F MAX <br />SUPPLY AIR COOLING: 55®F MIN <br />5. VENTILATION PROVIDED IN ACCORDANCE WITH IMC CHAPTER <br />4, WAC 51-52 (WA STATE AMENDMENTS) AND ASHRAE <br />STANDARDS. <br />6. EQUIPMENT SELECTION IS BASED ON THE SMALLEST <br />UNITS AVAILABLE THAT MEETS THE CALCULATED LOADS <br />PER EACH ZONE. <br />7. HEAT PUMP CONTROLS SHALL BE CAPABLE OF MINIMIZING <br />THE USE OF SUPPLEMENTAL HEAT AS DESCRIBED IN 2015 <br />WSEC SECTION C403.2.4.1.1. SUCH CONTROLS SHALL BE <br />CAPABLE OF PREVENTING SUPPLEMENTAL HEATING AT <br />OUTDOOR TEMPERATURES OVER 40®F AND SHALL BE <br />INITIALLY SET TO 32°F, EXCEPTING DEFROST CYCLES. <br />8. CONTROLS SHALL BE CAPABLE OF PROVIDING 5 DEGREE <br />DEAD BAND AS REQUIRED BY 2015 WSEC SECTION <br />C403.2,4.1.2. <br />9. TEMPERATURE SENSORS AND PROGRAMMABLE THERMOSTATIC <br />CONTROLS ARE REQUIRED FOR EACH MECHANICAL UNIT. <br />CONTROLS SHALL BE CAPABLE OF PROVIDING SEVEN (7) <br />DAY PROGRAMMABLE TEMPERATURE SETTINGS, AUTOMATIC <br />SETBACK AND SHUTOFF AND OPTIMUM START PER 2015 <br />WSEC SECTION C403.2.4.2. <br />10. VOLUME DAMPERS ARE SHOWN IN THE PLANS AND <br />SHALL BE USED TO PROVIDE THE DESIGN AIRFLOW AT <br />THE DEVICES FOR WHICH THEY ARE INSTALLED PER <br />WSEC C408.2.2.1. <br />11, THE REQUIRED TWO ADDITIONAL EFFICIENCY PACKAGE <br />OPTIONS ARE PER C406.3 (REDUCED LIGHTING POWER) <br />AND C406.4 (ENHANCED DIGITAL LIGHTING CONTROLS), <br />PROVIDED BY OTHERS. <br />12. CERTAIN SMALL HEAT PUMP SYSTEMS ARE PROVIDED <br />WITHOUT ECONOMIZER AS ALLOWED BY THE WSEC SECTION <br />C403.3, EXCEPTION 10A OF THE WSEC FOR HEAT PUMP <br />SYSTEMS THAT PROVIDE COOLING TO ELECTRONIC AND <br />PROCESS/EQUIPMENT ROOMS. <br />13. CLASS 1 LOW LEAK MOTORIZED DAMPERS SHALL BE <br />PROVIDED AT ALL BUILDING ENVELOPE DUCT PENETRATIONS <br />AS REQUIRED BY THE 2015 WSEC SECTION C403.2.4.3, <br />DAMPER ACTUATORS SHALL BE CONFIGURED TO CLOSE <br />DURING UNOCCUPIED HOURS AND WITH THE EQUIPMENT <br />OFF. <br />14. THIS PROJECT IS A COMMUNITY BASED OUTPATIENT CLINIC <br />(B OCC, EXAM ROOMS, MEDICAL OFFICES, LABS AND <br />CONFERENCE ROOMS). PER STATE BUILDING CODE COUNCIL <br />INTERPRETATION NO. 17-09 (Q4), MEDICAL OFFICE <br />BUILDINGS OR AREAS ARE NOT REQUIRED TO COMPLY WITH <br />THE 2015 WASHINGTON STATE ENERGY CODE, SECTION <br />C403.6 (DOAS). <br />SIGNED: 12/11/2020 <br />Lu <br />REVISIONS <br />1. PERMIT SET 12-11-2020 <br />2. <br />3. o <br />4. o <br />,, jo <br />. We <br />u; <br />SHEET 2 OF 22 <br />