Laserfiche WebLink
E <br />ct 111�11RS�ONIIAKIE_V_a <br />RETT WA3-31-22 <br />reASSOCIATES <br />Air ,stem InfrinTiation <br />Air System Name __ ...... <br />.... _........ _SOH <br />Number of zones - <br />Equipment Class .-..... ..._... __... <br />PKG ROOF <br />Floor Area <br />__._.1059.0 ft' <br />Air System Type._.-_ <br />_ SZCAV <br />Location ..___.... __._ <br />._ ____ Seattle iAP, Washington <br />Sizing Calt;ulatiorl Inf rnri a?son <br />Calculation Months.. ........... <br />to Dec <br />Zone CFM Sizing ............._._.._--Sum <br />of space airflow rates <br />Sizing Data...__.____.______.....__._._...._.._.....__.... <br />Calculated <br />Space CFM Sizing __._.-:_._...Jndividual <br />peak space loads <br />Contra? Cooling Co Azincd P t <br />Total coil load - .___._. - . <br />...... ........_..2.5 Tons <br />Load occurs at.. ................. <br />._........ ...._..._ Aug 1400 <br />Total coil Toad _ _...._.:._ <br />.. ......_.30.6 MBH <br />CA IDS / WB__ <br />_............._..._.__ 84.5164.8 'F <br />Sensible coil load ...._... <br />MBH <br />Entering IDS /WB .._ <br />_... _____.- __._..,77.2163.6 'F <br />Coil CFM at Aug 1400 . - _._.. _._:__......_..... <br />1258 CFM <br />Leaving DB 1 W B <br />- ....._.. 5&51 55.2 'F <br />Max block CFM.. - <br />FM......_ ....... .. <br />-...... - .._..1258 CFM <br />Coil ADP_ . . .. .... <br />.___ ..........:._. 54.2 'F <br />Sum of peak zone CFM-:-.__.- <br />..._____-.1258 CFM <br />Bypass Factor.. <br />.._.. .. ...._. . __... 0.100 <br />Sensible heat ratio...... <br />_.._ 0.904 <br />Resulting RH -.. - _ -..__. <br />___. ._ _._.. .__50 % <br />CFM/Ton <br />493.8 <br />Design supply temp <br />_ _ 55.0 'F <br />ft'/Ton .._.. __. <br />.... ..415.7 <br />Zone T-stat Check <br />...._ ..._ ..._ .1 of 1 OK <br />BTU/(hr ft) _. <br />28.9 <br />Max zone temperature deviation _- 0.0 'F <br />Water flow @ 10.0 'F rise ....___.__....._.-...__-..___._...__. <br />N/A <br />r. r." rul He ating Cods S12410, Gcitn <br />Max coil load - ........ ......... ._...-.12.7 <br />MBH <br />Load occurs at.. <br />__ _ _ : _._._-._-Des Htg <br />Coil CFM at Des Htg:. ..._._. -.. <br />- ._:. ...,. 1258 CFM <br />BTU/(hr-ft�) ___ _ - <br />-.-- -:._- - ..._....__ 12.0 <br />Max coil CFM __. <br />1258 CFM <br />Ent. IDS / Lvg DB <br />...- ... _ -.. 64.6174,1 'F <br />Water flow @ 20.0'F drop ..... <br />___ _._ NIA <br />Supply 'an Sizing Data <br />Actual mar CFM <br />__....-.. _1258 CFM <br />Fan motor SHP .......... <br />__ ___ 0.34 BHP <br />Standard CFM .- _ - - .... ... <br />-... .... ___...1238 CFM <br />Fan motor kW ._ <br />..... 0.27 kW <br />Actual max CFM/ft2... _ <br />1,19 CFM/ft, <br />Fan static-, ........... <br />_.__.. 1.00 in wg <br />Outdoor ,,reni lation Air Data <br />Design airflow CFM.... ...._.._ __ __ . _......... <br />..........143 CFM <br />CFM/person....... ............. <br />_9.51 CFM/person <br />CFM/ft2 <br />0.13 CFM1ft' <br />Project Name: cg2022-0327 PV EVERETT WA 3-31-22 <br />Precared by: THORSON, BAKER & ASSOCIATES <br />3. "tt3r;r;7tr, <br />Ventilation Sizing Method _-- - .__ -. <br />Sum of Space OAAirflows <br />Design Ventilation Airflow Rate.. - <br />:_.__ - ......._ ........... <br />....._.143 CFM <br />Zone Name / Space Name <br />Mult, <br />Floor Area <br />ft' <br />Maximum <br />Occupants <br />Maximum <br />Supply Air <br />CFM` <br />Required <br />Outdoor Air <br />(CFM/person <br />Required <br />Outdoor Air <br />CF I/ft2 <br />Required <br />'Outdoor Air <br />CFM <br />Required <br />Outdoor Air <br />% of su 6 <br />Uncorrected <br />Outdoor Air <br />CFM <br />Zone 1 <br />102 CONTACT LENS <br />1 <br />132.0 <br />2.0 <br />111.9 <br />5.00 <br />0.06 <br />0.0 <br />0.0 <br />17.9 <br />103OFFCE <br />1 <br />47.0 <br />1.0 <br />43.7 <br />5.00 <br />0.06 <br />0.0 <br />0.0 <br />7.8 <br />104 RR <br />1 <br />50.0 <br />0.0 <br />44.6 <br />0.00 <br />0.00 <br />0.0 <br />0.0 <br />- 0.0 <br />105 BOH <br />1 <br />182.0 <br />2.0 <br />314.5 <br />5.00 <br />0.12 <br />0.0 <br />0.0 <br />31.8 <br />106 PRETEST <br />1 <br />82.0 <br />2.0 <br />87.1 <br />5.00 <br />0.06 <br />0.0 <br />0.0 <br />14.9 <br />107 ELEC ROOM <br />1 <br />53.0 <br />0.0 <br />78.7 <br />0.00 <br />0.00 <br />0.0 <br />0.0 <br />0.0 <br />108 LARGE EXAM <br />1 <br />129.0 <br />3.0 <br />135.1 <br />5.00 <br />0.06 <br />0.0 <br />0.0 <br />22.7 <br />109 SMALL EXAM <br />1 <br />114.0 <br />3.0 <br />124.0 <br />5.00 <br />0,06 <br />0.0 <br />0.0 <br />21.8 <br />111 OD RECEPTION <br />1 <br />260.0 <br />Z01 <br />318.4 <br />5.00 <br />0.06 <br />0.0 <br />0.0 <br />25.6 <br />Totals (incl. Space Sluitipiiers) <br />1 <br />1258.1 <br />142.7 <br />ct Name: cg2022-0327 PV EVERETT WA 3.31-22 <br />ared by: THORSON. BAKER &ASSOCIATES <br />Asr Gyjtain informatitni <br />Air System Name.,-.,, <br />__..... _,SALES <br />Number of zones <br />...... .. ..........._.1 <br />Equipment Class ...-.... -. __ <br />PKG ROOF <br />Floor Area __... <br />_-.._. __-_. .__ 1080.0 ft2 <br />Air System Type __._._ _.._.---.__ <br />Y Yp <br />_.:...SZCAV <br />Location __:._.__ <br />___. ...SaattlelAP,Washington <br />`:i3 ,ei,� C3'si uLation Informata3n <br />Calculation Months .__._ - .__._.. _.____.Jan <br />to Dec <br />Zone CFM Sizing . <br />_____Sum of space airflow rates <br />Sizing Data ___._ _..____._ _ _- _...__ <br />Calculated <br />Space CFM Sizing - . _.____ <br />Individual peak space loads <br />Central C.Tioling Coil Sizing Data <br />Total coil load _.._- ...-.._ <br />_....._ ......... ....5.3 Tons <br />Load occurs at . <br />_._. - __...-.-.._... Jun 1500 <br />Total coil [cad ...__ ...__. <br />_._.... __._ 64.0 MBH <br />CA DB / W B .-.... <br />..__ 84.0 165.0 'F <br />Sensible coil load.. . .............. <br />_......-59.3 MBH <br />Entering DB!WB .. <br />.._._ _.. ...............__...772/63.1 'F <br />Coil CFM at Jun 1500.. <br />._._.., 2626 CFM <br />Leaving DB / WB ..._......._........._ <br />_.- .._-__ ..56.0 / 54.6 'F <br />Max black CFM_ _.__._. _ ... ........ <br />........... ...2626 CFM <br />Coil ADP ..-.-.. ................... <br />............. _ 53.6 'F <br />Sum of peak zone CFM ........._ ... <br />_._..._..-_..2626 CFM <br />Bypass Factor..... <br />... _....- 0.100 <br />Sensible heat ratio . <br />....0.926 <br />Resulting RH ....... <br />.._ ..... ___ .._.47 % <br />CFM/Ton .. _ _.. ...__ <br />........ ._.492.1 <br />Design supply temp <br />-. __.-...... - _... 55.0 'F <br />ft2fTon ..-... ........- ..._.... <br />_ _....____ 202.4 <br />Zone T-stat Check <br />_....... ....._. .___..._ 1 of 1 OK <br />BTU/(hr-ft') .._.__ ____..._... .._..__........_..59.3 <br />Max zone temperature deviation 0.0 'F <br />Water flow @ 10.0'F rise ...:.........:.........___........__...-...:.. <br />NIA <br />Carkral Heating' ol! SiAng Dii a <br />Max coil load ....-._ .. _.. <br />...__-_.._._ 30.7 MBH <br />Load occurs at.. - <br />....... .. .._. - . -... .. Des Rig <br />Coil CFM at Des Htg _.. -. -_. .... <br />_.-. ...... 2626 CFM <br />BTU/(hr-ft') <br />._........ 28.4 <br />Max coil CFM.....,... ..... <br />____ __.2626 CFM <br />Ent. DB / Lvg DB _.____ <br />__ _ _______ 64.7 175.7 'F <br />Water flow @ 20.0'F drop .... <br />.._.._. ___. NIA <br />vi:.!oply] Fan S 3ing Data <br />Actual max CFM-.-____ .. ..._..._...._......2626 <br />CFM <br />Fan motor BHP.- ........... <br />_..._....- .._._........0.72 BHP <br />Standard CFM .-___-..-.-.. <br />_........ .._ 2583 CFM <br />Fan motor kW ... <br />..._._. ......... .......... 0.57 kW <br />Actual mar CFM/ft'..-_. , <br />........ 2.43 CFMlft' <br />Fan static .__. <br />_..... ...._ ....... 1.00 in wg <br />Okitdoor a entilat' on Air Daia <br />Design airflow CFM - <br />280 CFM <br />CFM/person...................._.........._.._...._.._......_.__..._....._._._.... <br />13.98 CFM/person <br />CFM/ft2-__. - ....._ ._.... <br />....---___.0.26 CFM/ft2 <br />Project Name: cg2022-0327 PV EVERETT WA 3-31-22 <br />Prepared by: THORSON BAKER & ASSOCIATES <br />,..Stamnaary <br />Ventilation Sizing Method _..___...____..._...___............_ <br />Sum of Space OA Airflows <br />Design Ventilation Airflow Rate .................... <br />_-........... .......-..-__...__...._.-.....__................ <br />280 CFM <br />2. Soo".a 1f.x±WH iix)n Anllv-d <br />Zone Name I Space Name <br />Mult. <br />Floor Area <br />ft' <br />Maximum <br />__occupants <br />Maximum <br />Supply Air <br />CFM <br />Required <br />Outdoor Air <br />CFM/person <br />Required <br />Outdoor Air <br />(CFM/ft') <br />` Required <br />Outdoor Air <br />(CFM <br />Required <br />Outdoor Air <br />(% of suppIV) <br />Uncorrected <br />Outdoor Air <br />(CFM) <br />Zone <br />101 RETAIL SALES <br />1 <br />1080.0 <br />20.0 <br />2625.6 <br />7.50 <br />0.12 <br />0.0 <br />0.0 <br />279.6 <br />Totals(inct. Space Multipliers) <br />2625.6 <br />>279.6 <br />THERMOSTAT PROCUREMENT INSTRUCTIONS <br />HONEYWELL TH8321WF1O01, A.K.A. THE HONEYWELL VISION PRO 8000 WI-FI <br />THERMOSTAT WITH WIRELESS REMOTE SENSORS AS REQUIRED. <br />PROCURE FROM HABEGGER CORP <br />CONTACT INFO. <br />HABEGGER CACORDI@HABEGGERCORP.COM <br />ANDYCUNNINGHAM ANDREWCUNNINGHAM@HABEGGERCORP.COM; <br />513-612-4776 <br />PETE DOYLE PETEDOYLE@HABEGGERCORP.COM; <br />513-612-4712 <br />THERMOSTAT INSTALLATION INSTRUCTIONS <br />NOTIFY ENERGY SERVICES (ENERGY.SERVICES@ LUXOTTICARETAILCOM) AND COPY THE PROJECT <br />MANAGER IF THE WI-FI NETWORK IS NOT AVAILABLE AT THE TIME OF INSTALLATION. <br />HVAC CONTRACTOR: <br />1. TAKE A PHOTO OF THE BACK OF EVERY WI-FI T-STAT THAT IS INSTALLED, SHOWING THE <br />MAC ADDRESS, CRC ID, AND 4 DIGIT PASSCODE (DATE CODE), AND EMAIL (WITH PROJECT <br />MANAGER IN COPY) TO (ENERGY.SERVICES@LUXOTTICARETAIL.COM). <br />2. WHEN INSTALLATION IS COMPLETED, EMAIL A LIST OF THE THERMOSTATS SHOWING THE <br />AREA OF THE STORE WHERE EACH T-STAT IS INSTALLED, AND EACH T-STAT'S MAC ADDRESS, <br />CRC ID AND 4 DIGIT DATE CODE. <br />3. A STICKER WITH THE MAC ID AND CRC ID OF EACH T-STAT IS PACKED WITH THE T-STAT, <br />AND IS TO BE PLACED ON THE BACK OF THE T-STAT, NOT ON THE FACEPLATE. E-MAIL THE <br />LIST AND THE PHOTOS IN FOR EACH STORE IN ONE E-MAIL TO <br />ENERGY.SERVICES LUXOTTICARETAIL.COM WITH THE NEXTORE PROJECT MANAGER PIED. <br />( @ ) G CO <br />ONE PHOTO PER T-STAT IS REQUIRED, AND IT IS IMPORTANTTO PHOTOGRAPH THE BACK OF <br />THE T-STAT, WITH THE MAC ID, CRC ID, AND DATE CODE SHOWING. <br />THE THERMOSTAT MUST BE CONNECTED TO OUR WI-FI NETWORK DURING <br />INSTALLATION. TO PERFORM THIS STEP, YOU MUST USE THE FOLLOWING <br />INFORMATION: <br />THE NETWORK NAME (A.K.A. AN SSID) = CNFLT <br />® A PASSPHRASE (A.K.A. THE PASSWORD) FOR CONNECTING THE T-STAT TO <br />OUR VVI-Fi NETWORK. <br />0 THE PASSPHRASE WILL BE SENT TO YOU IN SEPARATE E-MAIL. <br />O DO NOT GIVE THE PASSPHRASE TO ASSOCIATES - IT IS <br />CONFIDENTIAL AND TO BE KEPT THAT WAY. <br />0 DO NOT GIVE THE 4 DIGIT DATE CODE TO ASSOCIATES - IT IS ALSO <br />CONFIDENTIAL AND TO BE KEPT THAT WAY <br />THERMOSTAT SET POINT INSTRUCTIONS <br />FOR ALL LOCATIONS: FAN TO RUN CONTINUOUSLY DURING OCCUPIED PERIOD. <br />ALL OTHER BRANDS <br />OCCUPIED <br />COOLING SET -POINT ALL AREAS (EXCEPT LAB) = 72*F <br />HEATING SET -POINT ALL AREAS (EXCEPT LAB) = 68* F <br />TIME PERIOD BEGINS 1HOUR BEFORE STORE OPENS FOR BUSINESS I <br />OVERRIDE ADJUSTMENTS=+/-2*F FROM PROGRAMMED SET -POINTS <br />OVERRIDE ADJUSTMENTS OF PROGRAMMED SET -POINT = 4 HRS. <br />ALL OTHER BRANDS <br />UNOCCUPIED <br />HEATING = 60 DEGREES (LABS 60 DEGREES) <br />COOLING = 80 DEGREES (LABS 78 DEGREES) <br />TIME PERIOD BEGINS AT STORE CLOSING TIME <br />OVERRIDE ADJUSTMENTS = +/-2*F FROM PROGRAMMED SET -POINTS <br />OVERRIDE ADJUSTMENTS OF PROGRAMMED SET -POINT = 4 HRS. <br />ass <br />e <br />ECCENTRIC REDUCER <br />RECTANGULAR TO ROUND <br />"BUCKLEY FITTING" <br />RECTANGULAR <br />DUCTWORK <br />ARIES <br />MINIMUM <br />OLLAR <br />ME= <br />DUCT +T DETAIL <br />DUES TO REGTANOULAR DUGT ONLY - RC <br />rSHALL EQUAL <br />R BE GREATER <br />HAN 1/3W. <br />SHORT RADIUS ELBOW WITH ONE VANE <br />kLL EQUAL <br />:GREATER <br />W. <br />STANDARD RADIUS ELBOW <br />FM-0-1-0 RADIUS ELBOW DETAIL <br />SUPPLY DUCT <br />BRANCH DUCT <br />BALANCING <br />DAMPER <br />45° LATERAL FITTING <br />ROUND <br />DUCTWORK <br />BALANCING --' <br />DAMPER <br />CONICAL FITTING <br />t SHALL EQUAL <br />)R BE GREATER <br />'HAN 116W. <br />SHORT RADIUS ELBOW WITH TWO VANES <br />BCW CASING AND STAINLESS WIRE - 50FT <br />MAXIMUM <br />A. THE CONTRACT DOCUMENTS REFLECT A SYSTEM DESIGNED AROUND SPECIFIC REFERENCE PRODUCTS, THE <br />SELECTION OF WHICH HAS IMPACTED THE DESIGNS OF OTHER TRADES. IF ALTERNATE MANUFACTURERS ARE <br />SUBMITTED OR BID, IT IS THE RESPONSIBILITY OF THIS G.C. TO COORDINATE ALL DIFFERENCES AND IMPACTS <br />WITH ALL TRADES PRIOR TO BID, INCLUDING COSTS ASSOCIATED WITH REQUIRED CHANGES TO OTHER TRADES. <br />NO EXTRAS WILL BE ALLOWED FOR CHANGES REQUIRED TO OTHER TRADES IF ALTERNATE EQUIPMENT IS BID OR <br />INSTALLED AT THE G.C.'S OPTION. <br />B. EXISTING MECHANICAL INFORMATION IS BASED ON LIMITED EXISTING BUILDING DRAWINGS AND FIELD WORK, <br />THE G.C. SHALL FIELD VERIFY THE EXISTING CONDITIONS FOR ACCURACY, NO ADDITIONAL COMPENSATION <br />SHALL BE ALLOWED FOR REVISIONS TO THE DESIGN TO CORRECT FOR EXISTING CONDITIONS NOT AS <br />INDICATED ON THE PLANS. <br />C. G.C. SHALL NOTIFY TENANT, ARCHITECT AND ENGINEER OF ANY SITUATIONS THAT MODIFY OR INCREASE THE <br />SCOPE OF WORK FROM WHAT IS DESCRIBED IN THE DOCUMENTS. <br />D. G.C. SHALL BE RESPONSIBLE FOR ALL CUTTING/PATCHING RELATED TO THEIR WORK. <br />E. IF SPACE ABOVE CEILING IS INDICATED TO BE A RETURN AIR PLENUM, CONSTRUCTION MATERIALS ABOVE <br />CEILING SHALL BE NONCOMBUSTIBLE, OR HAVE A MAXIMUM 25 FLAME SPREAD AND 50 SMOKE DEVELOPMENT <br />FINISH RATING. WIRING SHALL BE LABELED PLENUM RATED TYPE PER NFPA 70. <br />F. COORDINATE LOCATION AND ELEVATION OF MECHANICAL WORK WITH ALL DUCTWORK, LIGHT FIXTURES, AND <br />OTHER CEILING BUILT-IN FIXTURES. CONTACT ENGINEER OR ARCHITECT IMMEDIATELY SHOULD ANY CONFLICT <br />ARISE. <br />G. MOUNTING OF ALL EQUIPMENT, DUCTWORK AND PIPING MUST BE DONE PER BUILDING GUIDELINES AND LOCAL <br />CODES AND INDUSTRY STANDARDS, COORDINATE INSTALLATION OF EQUIPMENT SUPPORT WITH BUILDING <br />MANAGER AND NEXTORE REPRESENTATIVE. <br />H. NO PVC PIPING ALLOWED IN PLENUM AREAS. <br />I. DUCT SIZES INDICATED REPRESENT CLEAR INTERIOR SHEET METAL DIMENSIONS. <br />J. r <br />ALL DUCTWORK r- I DUC 0 CONCEALED ABOVE CEILINGS AND ALL I N OUTSIDE AIR DUCTS,SHALL BE EXTERNALLY INSULATED. IF DUCTWORK IS RUN IN A NON -CONDITIONED SPACE ALL DUCTWORK MUST BE INSULATED WITH 2" FIBERGLASS <br />INSULATION AND VAPOR BARRIER. <br />K. BRANCH DUCTS SERVING DIFFUSERS SHALL BE SIZED TO MATCH DIFFUSER NECK SIZE INDICATED. <br />L. ALL ROUND DUCT ELBOWS SHALL BE LONG SWEEP, 1-1/2 TIMES THE CENTERLINE RADIUS, <br />M. G.C. MUST REPLACE ALL AIR FILTERS IN HVAC UNITS WITH NEW CLEAN FILTERS BEFORE AIR BALANCING AND <br />PRIOR TO FINAL TURNOVER TO TENANT. <br />N. IT IS THE G.C.'S RESPONSIBILITY TO ENSURE THAT THE MECHANICAL COMPONENTS ARE INSTALLED AT <br />LOCATIONS AND ELEVATIONS WHICH MAKE THEM READILY AND SAFELY ACCESSIBLE FOR ROUTINE <br />MAINTENANCE WITHOUT REQUIRING ANY EXTRAORDINARY MEASURES. <br />O. THE TENANT RESERVES THE RIGHT TO CHECK CONSTRUCTION COMPLIANCE WITH PLANS AND SPECIFICATIONS. <br />SHOULD THE TENANT FIND CORRECTIVE WORK NECESSARY, HE WILL NOTIFY G.C. OF SUCH WORK IN WRITING <br />AND EXPECT COMPLIANCE PERFORMED WITH DUE DILIGENCE. IF ANY CORRECTIVE WORK IS DEEMED TO BE <br />NECESSARY, THE COST OF REINSPECTIONS WILL BE BORNE BY THE G.C. IF WORK IS REQUIRED BY TENANT IN <br />ORDER TO IMPROVE, CHANGE OR CORRECT AIR CONDITIONING OPERATIONAL CONDITIONS DUE TO: PART <br />MALFUNCTION, WARRANTY OR OTHER INABILITY TO PROVIDE THE COMFORT CONDITIONS REQUIRED BY THE <br />STORE, G.C. SHALL BE DIRECTED BY TENANT TO ADDRESS THIS WORK IN A TIMELY MANNER. IF IT BECOMES <br />EVIDENT THAT THE G.C. CAN NOT ACCOMPLISH THE TASK, THEN AFTER 72 HOURS OF WRITTEN NOTICE, THE <br />TENANT MAY AT HIS DISCRETION TAKE OVER SUCH WORK AND BACK CHARGE THE G.C. FOR ANY CORRECTIVE <br />WORK THAT WAS REQUIRED DUE TO LACK OF PERFORMANCE, WORKMANSHIP AND/OR ADHERENCE TO PLANS <br />AND SPECIFICATIONS. <br />P. DUCTWORK SHALL NOT BE ROUTED OVER ELECTRIC PANELS AND TRANSFORMER. <br />HVAC SYMBOLS <br />q <br />SUPPLY AIR DIFFUSER - ARROWS INDICATE <br />PATTERN. NO PATTERN SHOWN EQUALS 4-WAY. <br />OR AS NOTED <br />RETURN AIR OR EXHAUST GRILLE (SEE TAG) <br />12 ROUND DUCTWORK. DIAMETER IN INCHES. <br />20X12 RECTANGULAR DUCTWORK. SIZE IN INCHES, <br />FIRST NUMBER IS SIDE SHOWN. <br />DIFFUSER/GRILLE LABEL: <br />A A - TYPE/DESIGNATION <br />B B - AIRFLOW (CFM) <br />POINT OF CONNECTION - NEW TO EXISTING <br />MANUAL VOLUME DAMPER <br /># SHEET KEYNOTE REFERENCE <br />VOLUME DAMPER TO BE <br />WITHIN 12" OF MAIN DUCT <br />LOCKING GEAR <br />ACOUSTICAL <br />CONTROLLER <br />CEILING <br />HVAC DETAIL NOTES: <br />1. SEE HVAC DRAWINGS FOR DUCT <br />SIZES <br />DUCT CONNECTION DETAIL <br />SUPPLY AIR DUCT, INSULATE <br />PER SPEC. <br />HIGH EFFICIENCY FITTING <br />INSULATED RIGID ROUND DUCTWORK, INSULATION TO <br />HAVE FOIL FACING (TYP,) <br />INSULATED FLEX, DUCT (5 FEET <br />MAX.) <br />SHALL BE 1.5 x R, INSULATED 90 <br />DEGREE SHEET METAL ELBOW <br />DRAW BAND (TYP.) <br />CEILING DIFFUSER <br />STORE 06261 <br />EVERETT MALL - 910 CENTER <br />910 SE EVERETT BALL WAY <br />FVFRETT, <br />WA 98208 <br />Construction for: <br />0 <br />0 <br />9- O <br />OLn <br />Ln <br />� o <br />v0 <br />O Cf <br />O <br />0 <br />e <br />� <br />oCID <br />LAJ <br />v X <br />� J <br />vt O <br />CD <br />d CD <br />CL <br />Mark Date <br />1 ---- -- ---- -- <br />Architect Job No.: <br />33N2022 <br />Nextore Store Design Revision No.: <br />Nextore Project <br />Number 86841 <br />Brand Desicln Type: <br />SKI <br />Title <br />MECHANICAL DETAILS <br />AND TS <br />_-_-..- -----_ <br />Date Sheet <br />04/19/2022 <br />Drawn By <br />TBA <br />Checked By ---- <br />TBA <br />f�1 <br />