Laserfiche WebLink
df , , minimum h ' ". <br /> radii paved must beriving 35sur feetace. Outsideexclusive turn of radiishoulders mustwith be 55a feetmini foru ladder clear apparatus heigtof13 Slope6 approachInsideturn and <br /> departure angles must not exceed 8 degrees. Fire lane grade must not exceed 10 percent. Fire <br /> lane construction must comply with AASHTO H30 load capacity (74,000 GVW). Fire Lanes will be <br /> posted and maintained as required by the Fire Department. Unorthodox access which meets code <br /> requirements but is too unusual for crews, will not be allowed. Call Fire Marshal's Office for <br /> apparatus specifications. <br /> a. Turnarounds Required - Roads with a length of 0-150 feet must be 20 feet wide; no turnaround <br /> required, 60'-diameter cul-de-sac is permitted. <br /> b. Turnarounds Required - Roads with a length of 151-500 feet must be 20 feet wide; 96'-diameter <br /> cul-de-sac, 120' Hammerhead or Y and 120'Tee is required. <br /> c. Turnarounds Required - Roads with a length of 501-750 feet must be 26 feet wide; 96-'diameter <br /> cul-de-sac, 120' Hammerhead or Y and 120' Tee is required. <br /> d. Turnarounds Required - Roads with a length over 750 feet- Special Approval Required. <br /> 49. Access - O.K. as shown on the site plan reviewed. <br /> 50. The Everett Municipal Code and the 2015 International Fire Code, Appendix C, table C102.1, <br /> requires that fire hydrants be provided within a maximum distance and of sufficient number and <br /> spacing to all new construction. The distance and number of hydrants varies based on type of <br /> construction and occupancy of the structure. New road needs fire hydrant placement every 200 <br /> feet. <br /> /1 <br />