NOZZLE SCHEDULE
<br />PROJ. FROM TOP/SIDE OF
<br />MK.
<br />SIZE (NPS)
<br />TYPE
<br />DESCRIPTION
<br />INNERxOUTER TANK TO PE/FF
<br />REMARKS/REQUIRED ACCESSORIES
<br />6' X 8"
<br />THREADED x FLANGED
<br />INLET
<br />19-1/2" x 15'
<br />SPARE/PROVIDE THREADED 6" PLUG
<br />6"
<br />FLANGED
<br />INLET
<br />11' FROM INNER
<br />PIW 0400/PROVIDE MATING W SLIP FLANGE
<br />6"
<br />FLANGED
<br />INLET
<br />17" FROM INNER
<br />PIW 0500/PROVIDE MATING 6" SLIP FLANGE
<br />4
<br />6"
<br />FLANGED
<br />INLET
<br />11' FROM INNER
<br />PIW 0300/PROVIDE MATING 8- SLIP FLANGE
<br />-Cr
<br />X It
<br />PE x FLANGED
<br />OUTLET
<br />1-1/ x ff
<br />PUMP SUCTION/MATING lt SLIP FLANGE
<br />6' X 12"
<br />PE x FLANGED
<br />OUTLET
<br />12-1/2" x 6"
<br />TANK OVERFLOW/MATING 12" SLIP FLANGE
<br />—
<br />— --
<br />PROVIDE FLANGED 36' GOOSENECK WITH BIRD
<br />�
<br />< 0
<br />SCREEN AND HINGED CAP FOR MOISTURE
<br />4"
<br />150# FLANGED
<br />OUTER VENT
<br />13"
<br />CONTROL
<br />PROVIDE FLANGED 3689 GOOSENECK WITH BIRD
<br />4 "
<br />150 FLANGED
<br />INNER VENT
<br />,®
<br />1S
<br />SCREEN
<br />-
<br />PROVIDE MATING BLIND FLANGE WITH 3" SS
<br />MALE CAMLOCK. SENSOR PROVIDED BY
<br />3"
<br />150# FLANGED
<br />LEVEL SENSOR
<br />15,
<br />CONTRACTOR,
<br />PROVIDE MATING BLIND FLANGE WITH 3" SS
<br />0
<br />LEVEL FLOAT
<br />MALE CAMLOCK. FLOAT PROVIDED BY
<br />3"
<br />150# FLANGED
<br />TREE
<br />15,
<br />CONTRACTOR
<br />11
<br />- --
<br />-
<br />BALL VALVE PROVIDED BY CONTRACTOR.
<br />2"
<br />THREADED
<br />DRAIN
<br />4"
<br />SCHED 60S. FABRICATOR PROVIDE BALL VALVE
<br />PROVIDE 1 BLIND FLANGE BORED TO 4!.
<br />12
<br />NOZZLE SCHED S FABRICATOR PROVIDED
<br />" x 4�
<br />FLANGED
<br />DRAIN
<br />611
<br />BALL VALVE.
<br />_
<br />PROVIDE MANWAY COVERS, HANDLES, AND
<br />1
<br />OUTER LID DAVIT SYSTEM, PROVIDE TWO
<br />24" x 42"
<br />- -
<br />FLANGED
<br />MANWAY
<br />9" x 12"
<br />HANDLES ON INNER COVER.
<br />1
<br />—
<br />TOP MANWAY. PROVIDE SPRING ASSISTED
<br />COVER OPENING MIN 95 DEGREES, LID TO
<br />3Y'
<br />FLANGED
<br />MANWAY
<br />11,
<br />OPEN AT MIN 2.5 PSIG PER UL 142 SEC, 8.8
<br />1
<br />PROVIDE MATING 10" FLANGE CAP AND 4"
<br />BLIND FLANGE. CONTRACTOR PROVIDED
<br />4' x 10f'
<br />FLANGED
<br />TANK HEATER
<br />16" x 17'
<br />HEATER
<br />CONTRACTOR PROVIDED LEAK DETECTOR.
<br />2"
<br />FLANGED
<br />LEAK SENSOR
<br />13" FROM OUTER
<br />PROVIDE 2" SCHED 60S 304L 10'-8"
<br />TANK REQUIREMENTS
<br />DESIGN CRITERIA
<br />MAXIMUM CAPACITY:
<br />9,50 GALLONS TO OVERFILL INVERT
<br />FLOODED CAPACITY:
<br />10,249 GALLONS
<br />VESSEL TYPE AND
<br />"ATMOSPHERIC TANK'
<br />CODE REQUIREMENT
<br />UL 142
<br />LOCATION:
<br />OUTDOORS
<br />CODE STAMP:
<br />NONE
<br />TANK DESIGN BASISO
<br />FLOODEDTANK 1 S®Ga
<br />INTERNAL PRESSURE
<br />® 4.33 PSIG
<br />(MAX. ALLOWABLE WORKING
<br />PRESSURE):
<br />TANK OPERATING
<br />TEMPERATUREBASIS:
<br />2(YF TO 1 ` 9F
<br />FLUID SERVICE /
<br />WASTEWATER /TRACE OILS,
<br />CONTENTS
<br />KETONES, AND SOLIDS.
<br />pH®7.0'-8.0
<br />LIQUID SPEC GRAVITY
<br />DESIGN FOR S.G. ® 1.0
<br />(S.G.) — RANGE
<br />INNER WALL PLATE
<br />MINIMUM 1 /4" (SHELL)
<br />THICKNESS (DESIGN):
<br />MINIMUM 5 16" HEADS
<br />OUTER WALL PLATE
<br />MINIMUM 3/16" (SHELL)
<br />THICKNESS (_DESIGN):
<br />MINIMUM 1 ! HEADS
<br />MIN. CORR. ALLOWANCE:
<br />1 "
<br />JOINT EFF,
<br />0.85 OR BETTER
<br />MANWAY COVER PLATE
<br />ROOF 30" DIA. 3/16'
<br />THICKNESS
<br />SIDE 24' DIA. ® 3/8"
<br />SIDE 42" DIA. ® 9/16"
<br />�� ;
<br />304L
<br />STAINLESS
<br />STEEL
<br />SAME
<br />MATERIAL
<br />AS ITS SHELL
<br />INNERA240,
<br />— ANK
<br />HEADS:
<br />—
<br />,OUTER TANK
<br />SHELL-
<br />.A240,
<br />304L
<br />STAINLESS
<br />STEEL
<br />ASTM
<br />A193 Gr.
<br />B8, CLASS 2
<br />OUTER TANK
<br />HEADS:
<br />'jA240,
<br />304L
<br />STAINLESS
<br />STEEL
<br />111111mirkil . . . . . .
<br />304L
<br />STAINLESS
<br />STEEL
<br />INOZZLE NECKS:304L
<br />STAINLESS
<br />STEEL
<br />NOZZLE FLANGES:
<br />OR
<br />SO,
<br />304L SS,
<br />ANSI 150
<br />BI IND FI ANGES AT
<br />SPARE NOZZLE&
<br />'TYPE
<br />304L, ANSI
<br />CLASS 150
<br />m
<br />SOUTH END ELEVATION
<br />SCALE:
<br />SYM REVISION BY APPROVED
<br />ORIG PIW UPGRADES ADDENDUM A J# 208084681 KJ I JMF
<br />DATE SYM
<br />01.25.21
<br />No
<br />A
<br />NORTH END ELEVATION
<br />1 " CLEARANCE
<br />(TYP OF 2)
<br />P LAN
<br />SCALE: 1 /2" =l'-Y'
<br />' TOP OF PLATFORM
<br />GRATING
<br />co
<br />l
<br />�I
<br />1 12" 1 Z' 20"
<br />OVERFLOW @ 103" - 9,650 GAL
<br />LSHH @ 72" - 6,700 GAL
<br />Is
<br />112' � � TANK SADDLE -
<br />INSIDE TO CENTERLINE 16" CLEARANCE
<br />(TYP OF 2)
<br />SIDE ELEVATION
<br />SCALE: 1 /2° = t'-0"
<br />ACCEPTABILITY
<br />Jim lo
<br />THIS DESIGN AND/ORSPECIFICATION IS APPROVED
<br />APPRWED BY DATE
<br />_
<br />AVIT -DESIGN
<br />BY FABRICATOR
<br />µ`.;w*,=1. 1VMOM�N
<br />Dfi r! 0
<br />'I
<br />re,� r....,r,�r_>"- .. n,,,�,._. . , ,;..-.'»*r, .c ,. are,;,-".`"; 3�� ���„ .� e-...:��r=.....�. .ti. •� ,� �:s
<br />TANK GENERAL NOTES;
<br />1 REFER TO SPECIFICATION 43 21 23 FOR ADDITIONAL
<br />DESIGN AND OPERATING INFORMATION AND
<br />REQUIREMENTS, INCLUDING TANK NAMEPLATE LABEL.
<br />AFFIX NAMEPLATE TO LOWER MANHOLE,
<br />2, TANK TYPE: DUAL CONTAINED VESSEL, DOUBLE -WALL
<br />STYLE, HORIZONTAL CYLINDRICAL, WITH TANK SUPPORT
<br />SADDLES. SEE SPECIFICATIONS FOR COMPLETE
<br />INFORMATION. VESSEL SHALL BE DESIGNED,
<br />FABRICATED, AND TESTED PER APPLICABLE SECTIONS
<br />OF UL 142, AND SHALL ALSO COMPLY WITH DESIGN
<br />FEATURES SHOWN IN THIS DRAWING.
<br />3. VESSEL LAYOUT AS SHOWN IS WITH RESPECT TO
<br />GENERAL CONFIGURATION. FABRICATOR SHALL SUBMIT
<br />SHOP/FIELD FABRICATION DRAWINGS FOR OWNER
<br />APPROVAL PRIOR TO TANK CONSTRUCTION,
<br />4. THE FABRICATOR SHALL PROVIDE STAMPED
<br />CALCULATIONS FOR THIS TANK IN ACCORDANCE WITH
<br />THE PROCUREMENT SPECIFICATIONS.
<br />5. ALL ELEVATIONS IN THIS SHEET ARE REFERENCED TO
<br />THE TANK OUTER BOTTOM PLANE ELEVATION OF 0'-0
<br />UNLESS NOTED OTHERWISE. TANK SADDLES DESIGNED
<br />BY FABRICATOR WITH MAXIMUM HEIGHT AS SHOWN.
<br />6, NOZZLES 6' NOMINAL DIAMETER AND LESS SHALL BE
<br />DESIGNED TO RESIST AN EXTERNAL LOAD OF 100 LBF
<br />IN ANY DIRECTION AND 120 FT -LB CUMULATIVE
<br />MOMENT. NO��LES OVER C NOMINAL DIAMETER SHALL
<br />BE DESIGNED TG RESIST AN EXTERNAL LOAD OF 350
<br />LBF IN ANY DIRECTION AND 400 FT -LB CUMULATIVE
<br />MOMENT,
<br />7. PROJECTION LENGTHS ARE MEASURED FROM THE OUTSIDE
<br />OF THE INTERNAL OR OUTER TANK WALLS TO THE FLANGE
<br />OR NO77LE OUTER FACE.
<br />6, FABRICATOR SHALL PROVIDE MATING SLIP�ON OR
<br />BLIND FLANGES AS SHOWN,
<br />9. TANK FABRICATOR SHALL PROVIDE, LOCATE, SIZE, TANK
<br />ANCHORAGE POINTS AND STRUCTURE TO MEET SEISMIC
<br />ANCHORING REQUIREMENTS. DESIGN AND INSTALLATION
<br />OF ANCHORS BY OTHERS.
<br />10, PROVIDE TANK WITH LIFTING LUGS (NOT SHOWN),
<br />11. FABRICATOR SHALL PROVIDE GOOSENECK VENT WITH
<br />BIRD SCREEN, 50% OPEN AREA. USE SAME MATERIAL
<br />AS THE TANK.
<br />12. FABRICATOR SHALL PROVIDE GASKETS FOR
<br />MANWAYS/HATCHES/COVERS, ACCESS OPENINGS, AND
<br />SPARE NOZZLES. SEE NOZZLE SCHEDULE, PROVIDE
<br />EPDM GASKETS OR EQUAL, CHEMICALLY SUITABLE FOR
<br />THE SERVICE CONDITIONS.
<br />11 PROVIDE DAVIT FOR OUTER COVER OF MANWAY 13
<br />OPENING TO SIDE SHOWN A MINIMUM 95 DEGREES.
<br />MANWAY 14 SHALL BE SPRING -ASSISTED FOR
<br />OPENING, FABRICATOR TO DESIGN LID FOR EMERGENCY
<br />VENTING WITH AT MAXIMUM 2.5 PSIG IN ACCORDANCE
<br />WITH UL 142 SECTION 8.8.
<br />14. PROVIDE DROP PIPE FOR NOZZLE 5 WITH MINIMUM 6'
<br />DISTANCE FROM FLOOR AS SHOWN,
<br />15. PROVIDE SUPPORT FOR HEATER. COORDINATE WITH
<br />HEATER SUPPLIER FOR REQUIREMENTS.
<br />CONSTRUCTION OTE
<br />1 FABRICATOR TO PROVIDE BLIND FLANGE DRILLED 3"
<br />MALE CAM AND GROOVE FITTING THREADED OR
<br />WELDED.
<br />2 FABRICATOR TO PROVIDE 6" MATING FLANGE WITH
<br />WELDED SS CAP 9" IN LENGTH. MINIMUM
<br />THICKNESS 3/16".
<br />3 FABRICATOR TO PROVIDE BLIND FLANGE DRILLED 2"
<br />MALE CAM AND GROOVE FITTING THREADED OR
<br />WELDED,
<br />4 FABRICATOR TO PROVIDE W FLANGED SS CAP FOR
<br />TANK HEATER 15-3/4' LENGTH AND MINIMUM 0.25'
<br />THICKNESS.
<br />6 DAVIT FOR OUTER MANHOLE 13 COVER SHALL
<br />ALLOW MANHOLE TO PIVOT WHILE OPENING, CONFIRM
<br />OPENING DOES NOT INTERFERE WITH TANK STAIRS.
<br />6 FABRICATOR TO PROVIDE 10" BLIND FLANGED BORED
<br />OUT AND WELDED TO 4' CONTAINMENT PIPE, 10"
<br />FLANGED CAP, AND 2" WARREN 3—PIECE SS BALL
<br />VALVE MODEL 1030 OR EQUAL. REMOVE BALL VALVE
<br />HANDLE AND PLACE IN CAP. SUPPORT NOZZLE
<br />FROM TANK.
<br />CURRENT REVISION SYMBOL ®ATE
<br />20808468 04.30.21
<br />SHEET
<br />M538-01
<br />JOB NO. Comp NO.
<br />20�OB46B
<br />DWG NO. 40-YD-M538-01
<br />
|