Laserfiche WebLink
TOLCO <br />SWAY <br />PIPING <br />PER PLAN <br />PIPING PER MECHANICAL <br />PROVIDE GUIDES PER 5/MXXX-1 <br />AS INDICATED ON PLAN <br />1 99 <br />MIN 7I <br />HSS4x4x1/4 <br />1/4 <br />1/4 <br />0)) /j / <br />PS-1 GRAVITY SUPPORT DETAIL <br />1 /2" DIA. ANCHOR EMBEDDED <br />3" IN ADHESIVE INTO EXISTING <br />CONCRETE PER G.S.N. <br />TOLCO FIG. 960 SWAY <br />BRACE ATTACHMENT <br />w <br />B—LINE B22 LONGITUDINAL <br />STEEL EMBED AT <br />NEW TRENCH <br />3/4" DIA. EPDXY ANCHORS <br />AT (E) TRENCH PER G.S.N., <br />TYP. (2 PER SUPPORT 4 <br />PER PLATE) <br />EMBED 4" TYP. <br />MXXX M538-02 <br />2 <br />_ <br />PER B®LINE <br />38T THREADED <br />STAND <br />maxUA& I <br />PS-lA STANCHION SUPPORT DfG411 <br />2'- <br />1 99 <br />1'®10 1/2" <br />- 4 <br />EMBED <br />e7�T <br />PORT IS <br />L STEEL INSTEAD <br />0 <br />TE, PROVIDE <br />1 ET WELD THREE <br />SIDES TO SUPPORT <br />1 -- <br />SEE TRANSVERSE <br />BRACING VIEW FOR <br />ANCHORAGE <br />RS®3B LONGITUDINAL BRACING <br />PS-PS-3 PIPE HAI'N'GER BRACING DETAIL <br />SCALE. 399 0 l,0(Y9 <br />FACE OF <br />CONCRETE <br />B—LINE B3062 — <br />ADJUSTABLE ROD <br />ATTACHMENT <br />B—LINE B3100 <br />CLEVIS <br />NOTES: <br />1. PROVIDE SEISMIC BRACING PER <br />DETAIL 3/M563-03 AS <br />L INDICATED ON PLAN. <br />2, PROVIDE HANGER ROD <br />STIFFENERS AT 2'—Y' O.C. (2 <br />MIN.) WHERE SEISMIC BRACING <br />IS ATTACHED WITHIN 4" OF <br />HANGER. ROD STIFFENER SYSTEM <br />SHALL BE BY EATON B®LINE OR <br />APPROVED EQUIVALENT. <br />—3/4' DIA. THREADED ROD <br />2,—U' <br />1 1 /29, 4 1 /299 4 1 /299 1 /2991 1 /299 4 1 /2y' 4 1-2 1 1 /2" <br />PIPING .PER PLAN AND ANCHOR na <br />PER DETAIL 1 /M53B®04 <br />� Q d <br />PIPING PER PLAN AS HSS4x4x1/4 <br />OCCURS, NOT TO HAVE HORIZONTAL BRACE <br />GUIDE OR ANCHOR ATTACHED <br />TO SAME SUPPORT <br />d ° a <br />1/4 BRACE TO 4 <br />° d 4 <br />1/4 <br />CANTILEVER ° -- — <br />4 <br />C-4LJ <br />1/4 BRACE TO d ° ° ° Q A. ° ° <br />1/4 CANTILEVER a d <br />HSS4x4x1/4 CANTILEVER WITH 1/4 SHOP WELDED q ° <br />END PLATE AT FREE END <br />4 <br />1 /2%12%127 PLATE <br />1/4 ° <br />TYP. <br />e d <br />3/4" DIA. ANCHORS <br />SIDE VIEW <br />PS-4 PIPE ANCHOR DETAIL <br />SCALE: 1 1 /2" = 1'm0" <br />1/27xl�'027 PLATE WITH 4 <br />ANCHORSDD <br />INTO ADHESIVE PER G.S.N., TYP. <br />'LIPING PER PLAN <br />wROVIDE GUIDES PER -- <br />AS INDICATED ON PLAN <br />CANTILEVER <br />OP WELDED <br />PLATE.._ ENIE <br />RECTLY TO <br />_D- <br />1 f\!ik- wl %d V19Vl%t=16 %"I% <br />STEEL EMBED PLATE <br />PS-5 CANTILEVER PIPE SUPPORT DETAIL <br />SCALE: 1 1 /2" = 1 °-0'° <br />SYm REVISION BY APPROVED I DATE SYM REVISION BY APPROVED DATE <br />ORIG PIW UPGRADES ADDENDUM A J# 20608466 KJ JMF 01,25.21 <br />- HSS4x4x1/4 CANTILEVER <br />WITH 1/4' SHOP WELDED <br />END PLATE AT FREE END <br />EMBEDDED 4°' INTO 1/27x12"x12" PLATE <br />ADHESIVE PER G.S.N., FRONT VIEW AT WALL <br />TYP. (4 PER PLATE) <br />PIPING PER <br />MECHANICAL <br />1 /W CLR. CONTAINMENT PIPE RADIUS PLUS <br />TYP, <br />1 /2" x 2 1 /2" WIDE (MIN.) x 1 /2" <br />THICK PINE EACH SIDE OF PIPE <br />WITH 1/4!' RADIUS AT EDGE OF <br />PLATE IN CONTACT WITH PIPE <br />1/4 <br />1 /4 li TYP. <br />HISS STEEL SUPPORTL <br />CL 1/4!' RADIUS AT INSIDE EDGE OF <br />PLATE IN CONTACT WITH PIPE BOTH <br />ENDS (TYP) <br />CIA <br />PS-5 W/ PIPE GUIDE DETAIL <br />SCALE. 399 e l'—Y' <br />` I <br />-, � i, -, wo. <br />ACCEPTABILITYTHIS <br />DESIGN AND/OR <br />SPECIFICATION APPROVED <br />- <br />+ R <br />GENERAL STRUCTURAL NOTES <br />CODES AND REFERENCES <br />2016 EDITION OF THE INTERNATIONAL BUILDING CODE (IBC), WITH STATE OF WASHINGTON AND CITY OF EVERETT <br />AMENDMENTS AND SUPPLEMENTED WITH ASCE 7-16. ALL CODE REFERENCES SHALL CORRESPOND TO THE FOLLOWING <br />EDITIONS, U.N.O.: <br />MATERIAL CODE EDITION <br />STRUCTURAL STEEL 15TH EDITION OF STEEL CONSTRUCTION MANUAL (AISC SCM) INCLUDING <br />THE SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS, (AISC 360)-16. <br />STRUCTURAL STEEL WELDING STRUCTURAL WELDING CODE -STEEL, (AWS D1.1)-15. <br />STAINLESS STRUCTURAL STEEL WELDING STRUCTURAL WELDING CODE -STEEL, (AWS 01.6)-17, <br />PIPE SUPPORTS LOADS: <br />WEIGHT OF SUPPORTED PIPING. <br />SEISMIC LOADS: <br />IMPORTANCE FACTOR le = 1.0. <br />LATITUDE = 47.9237; LONGITUDE =-122,2765. <br />Ss 0 1,446, S1 = 0.550, SEISMIC SITE CLASS = C. <br />Sds 0.964, Sd1 = 0,484, SEISMIC DESIGN CATEGORY = D. <br />ANALYSIS PROCEDURE USED = EQUIVALENT LATERAL FORCE PROCEDURE. <br />STRUCTURAL STEEL: <br />ALL CONSTRUCTION SHALL BE PER AISC—SCM. <br />ALL MILD STEEL SHALL BE AS FOLLOWS: <br />HOLLOW SQUARE OR RECTANGULAR STEEL A.S.T.M. A500, GRADE B FY = 46 KSI <br />ALL OTHER STRUCTURAL STEEL SHAPES A.S.T.M. A36 FY = 36 KSI <br />ALL STAINLESS STEEL SHALL BE AS FOLLOWS: <br />ALL PLATES, BARS AND SHAPES SHALL BE TYPE 304L, UNLESS NOTED OTHERWISE. STAINLESS STEEL SHAPES SHALL <br />BE IN ACCORDANCE WITH ASTM A276. STAINLESS STEEL PLATES SHALL COMPLY WITH ASTM A240. ALL STAINLESS STEEL <br />THREADED RODS SHALL BE ASTM F503 GRADE 304, <br />ADHESIVE ANCHORS IN CONCRETE: <br />ALL ADHESIVE ANCHORS SHALL HAVE CURRENT ICC APPROVAL FOR MATERIAL INTO WHICH INSTALLATION TAKES PLACE, <br />SUCH AS HILTI HY200—R (ICC ESRm3167) OR APPROVED EQUIVALENT. THREADED RODS SHALL BE ASTM F1554 GRADE <br />36 GALVANIZED OR ASTM F503 GRADE 304 STAINLESS STEEL. <br />EXPANSION BOLTS IN CONCRETE: <br />ALL EXPANSION BOLTS SHALL HAVE CURRENT ICC APPROVAL FOR MATERIAL INTO WHICH INSTALLATION TAKES PLACE, SUCH AS <br />HILTI KWIK BOLT TZ (ICC ESR— 1017) OR APPROVED EQUIVALENT, BOLTS SHALL BE GALVANIZED OR STAINLESS STEEL. <br />WELDING: <br />WELDERS HOLDING VALID W.A.B.O. CERTIFICATES AND HAVING CURRENT EXPERIENCE IN THE TYPE OF WELD SHOWN ON <br />THE DRAWINGS OR NOTES SHALL PERFORM ALL WELDING. CERTIFICATES SHALL BE THOSE ISSUED BY AN ACCEPTED <br />TESTING AGENCY. <br />ALL WELDING OF MILD STEEL SHALL BE DONE BY E70 SERIES LOW HYDROGEN RODS, U.N.O. ALL WELDING OF <br />STAINLESS STEEL SHALL BE DONE BY E306L RODS, U.N.O. ALL WELDING SHALL BE PER LATEST AWS STANDARDS. <br />THESE DRAWINGS DO NOT DISTINGUISH BETWEEN SHOP AND FIELD WELDS, THE CONTRACTOR MAY SHOP WELD OR FIELD <br />WELD AT THEIR DISCRETION. SHOP WELDS AND FIELD WELDS SHALL BE SHOWN ON THE SHOP DRAWINGS SUBMITTED <br />FOR REVIEW. ALL FULL/COMPLETE PENETRATION WELDS SHALL BE TESTED AND CERTIFIED BY AN INDEPENDENT TESTING <br />LABORATORY. <br />STRUT CHANNEL FRAMING: <br />STRUT CHANNEL FRAMING MEMBERS AND CONNECTORS SHALL BE STAINLESS STEEL BY UNISTRUT OR EATON B—LINE U.N.O., OR <br />ACCEPTED SUBSTITUTION. PART NUMBERS INDICATED ON THE DRAWINGS ARE UNISTRUT OR B—LINE NUMBERS U.N.O. CONNECTIONS <br />SHALL CONSIST OF 1/2" DIAMETER BOLTS/CHANNEL NUTS U.N.O. TIGHTEN BOLTS FOR RESISTANCE TO SLIP PER MANUFACTURER'S <br />SPECIFICATIONS. ALL CONNECTED COMPONENTS SHALL BE PROVIDED BY A SINGLE MANUFACTURER. <br />PROTECTIVE COATINGS FOR STEEL: <br />ALL STRUCTURAL AND MISCELLANEOUS MILD STEEL AND FASTENERS SHALL RECEIVE POLYAMIDE EPDXY COATING WITH <br />ALIPHATIC ACRYLIC POLYURETHANE TOPCOAT UNLESS NOTED OTHERWISE. USE TNEMEC SERIES 66 HI —BUILD EPDXOLINE <br />WITH TNEMEC ENDURA—SHIELD SERIES 73 TOPCOAT OR APPROVED EQUAL. EPDXY —POLYURETHANE COATING SHALL BE <br />INSTALLED PER MANUFACTURER RECOMMENDATIONS. COORDINATE COLOR WITH OWNER. <br />FIELD REPAIR: FIELD REPAIR OF DAMAGED EPDXY -POLYURETHANE COATING SHALL BE DONE IN ACCORDANCE WITH <br />MANUFACTURER RECOMMENDATIONS. <br />HANDLING: AFTER SHOP FABRICATION AND COATING, STRUCTURAL STEEL MEMBERS SHALL BE HANDLED WITH SUFFICIENT <br />CARE TO MINIMIZE DAMAGE DURING SHIPMENT. SUFFICIENT DUNNAGE SHALL BE USED TO PREVENT ANY RUBBING OF <br />STEEL TO STEEL, <br />DRYPACK: <br />DRYPACK SHALL BE 5,000 PSI NON -SHRINK GROUT, FIVE STAR OR EQUIVALENT. INSTALL DRYPACK UNDER BEARING <br />PINES BEFORE FRAMING MEMBER IS INSTALLED, <br />SPECIAL STRUCTURAL INSPECTION: <br />SPECIAL INSPECTION IS TO BE PROVIDED FOR THE ITEMS LISTED BELOW IN ADDITION TO THE INSPECTIONS CONDUCTED BY THE <br />BUILDING SAFETY DEPARTMENT. "SPECIAL STRUCTURAL INSPECTION" SHALL NOT RELIEVE THE OWNER OR THEIR AGENT FROM <br />REQUESTING THE CITY INSPECTIONS REQUIRED BY IBC SECTION 110.3. SPECIAL INSPECTION IS REQUIRED PER SECTIONS 1704 <br />AND 1705 FOR THE FOLLOWING: <br />1. POST —INSTALLED ANCHORS (PER IBC TABLE 1705.3): <br />A) CONTINUOUS INSPECTION DURING THE PLACEMENT OF ALL ADHESIVE ANCHORS INSTALLED IN <br />HORIZONTALLY OR UPWARDLY INCLINED ORIENTATIONS. <br />B) PERIODIC INSPECTION OF ALL OTHER ADHESIVE AND MECHANICAL ANCHORS. <br />2. WELDING (PER AISC 360 CHAPTER N): <br />A) VISUAL INSPECTION OF ALL FIELD WELDS. <br />3. DUTIES AND RESPONSIBILITIES OF THE SPECIAL INSPECTOR: <br />A) THE SPECIAL INSPECTOR SHALL OBSERVE THE WORK ASSIGNED TO BE CERTAIN IT CONFORMS TO THE APPROVED <br />DESIGN DRAWINGS AND SPECIFICATIONS. <br />0) PER IBC SECTION 1704.2.4: THE SPECIAL INSPECTOR SHALL FURNISH INSPECTION REPORTS TO THE BUILDING OFFICIAL <br />AND TO THE ENGINEER OF RECORD. ALL DISCREPANCIES SHALL BE BROUGHT TO THE ATTENTION OF THE CONTRACTOR <br />FOR CORRECTION, THEN, IF UNCORRECTED TO THE DESIGN AUTHORITY AND THE BUILDING OFFICIAL. SUBMIT A FINAL <br />REPORT AS REQUIRED. <br />C) UPON COMPLETION OF THE ASSIGNED WORK, THE ENGINEER SHALL COMPLETE AND SIGN THE APPROPRIATE FORMS <br />CERTIFYING THAT, TO THE BEST OF THEIR KNOWLEDGE, THE WORK IS IN CONFORMANCE WITH THE APPROVED PLANS, <br />SPECIFICATIONS AND THE APPLICABLE WORKMANSHIP PROVISIONS OF THE CODE. <br />FOR ADDITIONAL INFORMATION ON SPECIAL STRUCTURAL INSPECTIONS, CONTACT STRUCTURAL ENGINEER PRIOR TO START OF <br />CONSTRUCTION. <br />JOB NO. 20808468 come <br />EVERETT, WA DWG NO. 40—YD—M538®02 <br />mm <br />