Laserfiche WebLink
GENERAL NOTES: <br />1. DESIGN 1S BASED ON THE INTERNATIONAL BUILDING CODE, IBC 2018 AND THE STATE OF WASHINGTON AMENDMENTS. <br />ALL MATERIALS AND WORKMANSHIP SHALL COMPLY WITH PROJECT DRAWINGS AND <br />2. SPECIFICATIONS. <br />THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS, CONNECTIONS, EMBED PLATE <br />3. AND ANCHOR BOLT LOCATIONS FROM EQUIPMENT MANUFACTURER'S APPROVED <br />DRAWINGS AND STEEL FABRICATOR'S ANCHOR BOLT AND EMBED PLATE SETTING <br />PLANS, WHICH HAVE BEEN APPROVED BY THE ARCHITECT/ENGINEER. <br />THE CONTRACTOR SHALL WORK STRUCTURAL DRAWINGS TOGETHER WITH <br />4. ARCHITECTURAL, MECHANICAL, PLUMBING, ELECTRICAL AND CIVIL DRAWINGS TO <br />LOCATE RECESSED SLABS, SLOPES, DRAINS, EAGLES, BOLT SETTINGS, GRADES, ETC. <br />ANY DISCREPANCIES SHALL BE CALLED TO THE ATTENTION OF THE <br />ARCHITECT/ENGINEER BEFORE PROCEEDING WITH THE WORK. <br />THE STRUCTURAL INTEGRITY OF THE COMPLETED STRUCTURE DEPENDS UPON THE <br />5. INTERACTION OF VARIOUS CONNECTED COMPONENTS. PROVIDE ADEQUATE BRACING, <br />SHORING, AND OTHER TEMPORARY SUPPORTS AS REQUIRED TO SAFELY COMPLETE THE <br />WORK. <br />THE CONTRACTOR SHALL VERIFY ALL EXISTING DIMENSIONS AND CONDITIONS PRIOR TO <br />6. ORDERING ANY MATERIALS AND SHALL NOTIFY THE ARCHITECT/ENGINEER IF DIFFERENT <br />FROM WHAT IS SHOWN ON THE DRAWINGS. <br />THE CONTRACTOR SHALL REVIEW THESE DRAWINGS AND VISIT THE PROJECT SITE BEFORE <br />7. CONSTRUCTION BEGINS TO COMPARE ALL EXISTING CONDITIONS WITH WHAT IS SHOWN ON <br />THESE DRAWINGS. IF THERE ARE CONDITIONS WHICH ARE DIFFERENT FROM WHAT IS SHOWN, <br />THE STRUCTURAL ENGINEER OF RECORD SHALL BE NOTIFIED. <br />THE CONTRACTOR SHALL ARRANGE A PRE -CONSTRUCTION MEETING WITH THE <br />8. ARCHITECT/ENGINEER TO ENSURE THAT THE CONTRACTOR'S UNDERSTANDING OF THESE <br />DRAWINGS AND PLAN FOR THE WORK IS IN ACCORDANCE WITH THE DESIGN INTENT AND TO <br />CLARIFY ANY QUESTIONS THAT THE CONTRACTOR MAY HAVE. <br />SECTIONS AND DETAILS ARE SHOWN TO INDICATE SPECIFIC CONDITIONS. WHERE SECTIONS ARE NOTED TO BE <br />9. TYPICAL, THESE SECTIONS OR DETAILS SHALL APPLY TO OTHER SIMILAR LOCATIONS. ANY LOCATION IN QUESTION <br />SHALL BE BROUGHT TO THE ATTENTION OF THE STRUCTURAL ENGINEER. <br />THE STRUCTURAL ENGINEER OF RECORD SHALL NOT BE RESPONSIBLE FOR THE MEANS, METHODS, TECHNIQUES, <br />% SEQUENCES, NOR PROCEDURES OF CONSTRUCTION SELECTED BY THE CONTRACTOR, OR THE SAFETY <br />PRECAUTIONS AND PROGRAMS INCIDENTAL TO THE WORK OF THE CONTRACTOR. THE STRUCTURAL ENGINEER <br />SHALL NOT BE RESPONSIBLE FOR THE FAILURE OF THE CONTRACTOR TO PERFORM THE CONSTRUCTION WORK IN <br />ACCORDANCE WITH THESE DRAWINGS. <br />THE INTENT OF SITE VISITS ARE FOR THE STRUCTURAL ENGINEER TO BECOME FAMILIAR WITH THE QUALITY OF THE <br />11. CONSTRUCTION AND TO DETERMINE IN GENERAL IF THE CONSTRUCTION IS PROCEEDING IN ACCORDANCE WITH THE <br />CONSTRUCTION DOCUMENTS. <br />ELEVATIONS: <br />FINISHED GROUND FLOOR EL = 100'-0" <br />FINISHED GROUND FLOOR REF EL = 548'-Q" N.G.V.D. (SEE CIVIL DWGS) <br />CONCRETE <br />1. ALL CONCRETE WORK SHALL COMPLY WITH PROVISIONS OF ACI 318-14, ACI 315=18, AND ACI 301-16, AND THE <br />2018 INTERNATIONAL BUILDING CODE <br />2. CONCRETE SHALL BE NORMAL WEIGHT CONCRETE. <br />CONCRETE STRENGTHS (AT 28 DAYS) SHALL BE AS FOLLOWS: <br />PEDESTRIAN AND UTILITY TUNNELS <br />Pc <br />(BASE SLAB,WALLS, ANDROOF)------------------ <br />--- - - -- -- 5000PSI <br />SLABS -ON -GRADE---.=.-------------- -- - - - - <br />- - - - - - - - - 5000PSI <br />SLABS -ON -GRADE MODULUS OF RUPTURE AT 28 DAYS = 625 PSI <br />WHEN TESTED IN ACCORDANCE WITH ASTM C78 - - - - - - - --- - -- - - - <br />- - - - - - - - - 6000PSI <br />FOUNDATIONS - - - - - - - - - - - - - --- - - - - - - <br />- - 5000PSI <br />ALL OTHER CONCRETE <br />3. CALCIUM CHLORIDE SHALL NOT BE USED IN ANY FORM. <br />4. CONCRETE PROTECTION FOR REINFORCING BARS: <br />STRUCTURAL ELEMENT <br />CLEAR COVER <br />FOOTINGS, (CAST AGAINST & ---------------------- <br />- -- -- 31NCHES <br />PERMANENTLY EXPOSED TO EARTH) <br />FOOTINGS AND WALLS(CAST-IN-FORMS----------------- - <br />- - - -- 21NCHES <br />PERMANENTLY EXPOSED TO EARTH) <br />SLABS (IN CONTACT WITH EARTH) '------------------`--- <br />2INCHES <br />SLABS EXPOSED TO WEATHER) - - - - - - - - - - - - - - - - - - - - - -- <br />- -- 11/2 INCHES <br />SLABS ABOVE GRADE - --- - - - - - - - - - - - - - - - - - - <br />- - - - - 3/4 INCHES <br />5. ALL WELDED WIRE FABRIC SHALL CONFORM TO ASTM A185 AND SHALL BE LAPPED ONE FULL MESH PANEL PLUS <br />2 INCHES AT SIDES AND ENDS AND WIRED TOGETHER. <br />6. ALL REINFORCING STEEL SHALL BE PLACED WITHIN TOLERANCES SPECIFIED IN <br />SECTIONS 7.5.2.1 AND 7.5.3.3 IN ACI 315-99 <br />7. ALL REINFORCING STEEL REBAR SHALL CONFORM TO ASTM A615 GRADE 60. <br />- SLAB ON GRADE SCHEDULE -- <br />MARK THICKNESS REINFORCEMENT* JOINT TYPE VAPOR RETARDER DESIGN LOADS <br />S1 <br />12" <br />5@12" OC TOP &BOT <br />ARMORED** <br />YES <br />* USE OF EQUIVALENT ENGINEERED <br />STRUCTURAL WELD REINFORCING (ESWR), <br />GRADE 80 WILL BE ACCEPTABLE <br />LAP SPLICE LENGTH (400Q PSI CONCRETE) - NORMAL WEIGHT, NO EPDXY <br />BAR SIZES (#) <br />LEAST CONCRETE <br />COVER AT BAR <br />3 <br />4 <br />5 <br />6 <br />7 <br />8 <br />9 <br />10 <br />11 <br />3" <br />12" <br />20" <br />25" <br />29" <br />43" <br />49" <br />55" <br />6511 <br />801' <br />2" <br />12" <br />20" <br />25" <br />29" <br />43" <br />49" <br />60" <br />74" <br />891' <br />0 <br />11/2'° <br />1511 <br />2011 <br />25' <br />it <br />29 <br />4811 <br />6111 <br />75II <br />" <br />91 <br />l <br />1091 <br />3!4" <br />15" <br />30" <br />36" <br />49" <br />78°' <br />97" <br />117" <br />141" <br />165 <br />3" <br />12" <br />151' <br />19" <br />23" <br />33" <br />37" <br />42" <br />50" <br />62" <br />2" <br />12" <br />15" <br />191" <br />23" <br />33" <br />37" <br />46" <br />57" <br />68" <br />UJ <br />0 <br />11/2" <br />12" <br />15" <br />19" <br />23" <br />37" <br />47" <br />58" <br />70" <br />84" <br />3/4" <br />14" <br />20" <br />27" <br />37" <br />60" <br />74" <br />90" <br />108" <br />127" <br />LAP SPLICE LENGTH (5000 PSI CONCRETE) - NORMAL WEIGHT, NO EPDXY <br />BAR SIZES (#) <br />LEAST CONCRETE <br />COVER AT BAR <br />3 <br />4 <br />5 <br />6 <br />7 <br />8 <br />9 <br />10 <br />11 <br />3" <br />13" <br />18" <br />22" <br />26" <br />38" <br />43" <br />49" <br />58" <br />72" <br />2" <br />13" <br />18°° <br />22" <br />26" <br />42" <br />54" <br />69" <br />87" <br />107" <br />1112." <br />13" <br />18" <br />22" <br />33" <br />55" <br />72" <br />92" <br />116" <br />143" <br />I <br />3/4" <br />13" <br />22" <br />32" <br />65" <br />95°' <br />108" <br />122" <br />137" <br />152" <br />3" <br />12" <br />14" <br />17" <br />20" <br />29" <br />33" <br />38" <br />45" <br />55" <br />2" <br />12" <br />14" <br />17" <br />20" <br />32" <br />42" <br />53" <br />67°' <br />83" <br />0 <br />11/2" <br />12" <br />14" <br />1 18" <br />25" <br />43" <br />56" <br />71" <br />89" <br />110" <br />3/4" <br />13" <br />2T <br />35" <br />50" <br />73" <br />83" <br />94" <br />105" <br />117" <br />LAP SPLICE LENGTH 6000 PSI CONCRETE) - NORMAL WEIGHT, NO EPDXY <br />BAR SIZES (#) <br />LEAST CONCRETE <br />COVER AT BAR 3 4 5 6 7 8 9 10 11 <br />3" <br />12" <br />16" <br />20`° <br />24" <br />35'° <br />40" <br />45" <br />53" <br />66" <br />2„ <br />12" <br />16" <br />20" <br />24"35"40" <br />49" <br />61 °° <br />73" <br />< <br />-- <br />o <br />11/2" <br />12°" <br />16" <br />20" <br />24" <br />39" <br />501' <br />61" <br />75" <br />89" <br />3/4" <br />12" <br />20" <br />29" <br />40" <br />64" <br />79" <br />96" <br />1151, <br />135" <br />--J <br />3" <br />12" <br />13" <br />16" <br />191" <br />27" <br />31" <br />35" <br />41" <br />51 <br />Lu <br />2" <br />12" <br />13" <br />16" <br />19" <br />27" <br />31" <br />38" <br />47" <br />56" <br />® <br />11/2" <br />12" <br />13" <br />16" <br />191" <br />30" <br />38 <br />47" <br />58" <br />69" <br />3/4" <br />12" <br />16" <br />23" <br />31" <br />49" <br />61°' <br />741" <br />1 88" <br />104" <br />NOTE: <br />MINIMUM C/C BAR SPACING v 2 X COVER + (1) BAR DIAMETER FOR LAPS INDICATED <br />9. IT IS PERMITTED TO SUBSTITUTE MECHANICAL SPLICES (MEETING THE REQUIREMENTS OF <br />SECTION 12.6 IN ACI 318-11) FOR LAP SPLICES AT NO ADDITIONAL COST. MECHANICAL <br />SPLICES SHALL DEVELOP 125%® (MIN) OF THE YIELD STRENGTH OF THE REBAR IN TENSION <br />OR COMPRESSION. <br />10. ALL REINFORCEMENT SHALL BE SENT COLD. REINFORCEMENT PARTIALLY EMBEDDED IN <br />CONCRETE SHALL NOT BE FIELD BENT UNLESS APPROVED BY THE STRUCTURAL ENGINEER <br />OF RECORD. HOOKS SHALL BE ACI STANDARD HOOKS IN ACCORDANCE WITH ACI 318, CHAPTER 7. <br />11. REINFORCING FOR CONTINUOUS FOUNDATIONS SHALL BE CONTINUOUS AT CORNERS AND INTERSECTIONS. <br />PROVIDE CORNER BARS AT ALL CORNERS AND INTERSECTIONS. CORNER BARS SHALL HAVE LAP LENGTHS EQUAL <br />TO THE STRAIGHT BAR LAP LENGTHS ON BOTH ENDS OF THE CORNER BARS. <br />12. AT THE TIME CONCRETE IS PLACED, REINFORCEMENT SHALL BE FREE FROM MUD, OIL OR OTHER NONMETALLIC <br />COATINGS THAT DECREASE BOND. <br />SYM <br />REVISION <br />BY <br />APPROVED <br />DATE SYM REVISION BY APPROVED DATE <br />0 <br />IFC - HBL EXPANSION - POSITIONS 5 & 6 <br />KKB <br />BLS <br />06/30/22 <br />1. DESIGN, FABRICATION AND ERECTION OF ALL STRUCTURAL STEEL SHALL BE IN ACCORDANCE WITH THE <br />RISC STEEL CONSTRUCTION MANUAL; 15TH EDITION. THE STRUCTURAL FRAME FABRICATOR SHALL BE AISC <br />CERTIFIED FOR STEEL BUILDING STRUCTURES (STD) OR INCLUDE, AT THE FABRICATORS EXPENSE, <br />INSPECTION SERVICES NECESSARY TO INSURE THAT THE SHOP PROCEDURES AND FABRICATION <br />COMPLIES WITH DRAWINGS AND SPECIFICATIONS. SPECIFICALLY, ALL WELDED CONNECTIONS SHALL BE <br />INSPECTED AND TESTED BY A CERTIFIED TESTING AGENCY. <br />2. ALL STRUCTURAL STEEL SHALL HAVE THE FOLLOWING ASTM SPECIFICATION AND YIELD STRENGTHS UNO: <br />W&WTSHAPES -- - - - - - - - - - - -- - -- - -- FY = 50 KSI (A992, GRADE 50) <br />RECTANGULAR & SQUARE HSS - - - - - - - -- - - - FY = 46 KSI (A500, GRADE B) <br />ROUND HSS - - - - --- - - - - - - - - - - - - - - - - - - - - FY = 42 KSI (A500, GRADE B) <br />ALL OTHER SHAPES & PLATES (U.N.O.) - - - - - - - - - - - - - - - - - - FY = 36 K81(A36) <br />3. ALL DETAILING, FABRICATION AND ERECTION SHALL CONFORM TO THE LATEST EDITION OF THE AISC STEEL CONSTRUCTION <br />MANUAL AND THE FLORIDA BUILDING CODE. <br />4. ALL WELDING ELECTRODES SHALL BE E70XX, UNO. ALL WELDING SHALL BE PERFORMED <br />BY AWS CERTIFIED WELDERS AND SHALL CONFORM TO AWS D1.1/D1.1M STRUCTURAL <br />WELDING CODE - STEEL, LATEST EDITION. <br />5. ALL FILLET WELDS SHALL BE 3/16" UNO, BUT NOT LESS THAN AISC MINIMUM, SEE CHART BELOW: <br />MINIMUM SIZE FOR FILLET WELDS <br />MATERIAL THICKNESS OF <br />THINNER PART JOINED (INCHES) <br />MINIMUM SIZE OF <br />FILLET WELD (INCHES) <br />TO 1/4" INCLUSIVE <br />1/8" <br />OVER 1/4" TO 1/2" <br />3/16" <br />OVER 1/2" TO 3/4" <br />1/4" <br />OVER 3/4" <br />5116" <br />6. THE FABRICATOR SHALL FURNISH A STRUCTURAL SUBMITTAL WHICH SHALL BE CHECKED <br />BY THE CONTRACTOR FOR COMPLETENESS AND CONTENT PRIOR TO SUBMITTAL TO THE <br />STRUCTURAL ENGINEER OF RECORD FOR REVIEW. THE SUBMITTAL SHOULD INCLUDE <br />FABRICATION AND ERECTION DRAWINGS. FABRICATION SHALL NOT COMMENCE UNTIL THIS <br />REVIEW IS COMPLETED. <br />7. CUTS, HOLES AND THEIR REINFORCEMENT (REQUIRED BY OTHER TRADES) SHALL BE <br />SHOWN ON THE STRUCTURAL STEEL SHOP DRAWINGS AND SHALL BE MADE IN THE <br />SHOP. FIELD BURNING OF HOLES & CUTS IN STRUCTURAL STEEL SHALL NOT BE <br />PERMITTED EXCEPT BY WRITTEN PERMISSION FROM THE STRUCTURAL ENGINEER OF <br />RECORD, UNLESS NOTED OTHERWISE ON THE DRAWINGS. <br />8. SIZE AND SHAPE OF STRUCTURAL STEEL SHALL BE AS SHOWN ON DRAWINGS. <br />9. AFTER ERECTION, ALL STEEL SHALL BE CLEANED OF ALL RUST, LOOSE MILL,M SCALE, AND OTHER FOREIGN MATERIAL. <br />SCUFFS AND ABRASIONS SHALL BE FIELD TOUCHED -UP, <br />10. ALL FIELD CONNECTION ARE TO BE PAINTED TO MATCH ATTACHED COMPONENTS. <br />11. WELDED SHEAR STUDS SHALL BE 1/2" DIA x 6" LONG ASTM Al08 HEADED STUDS. <br />FOUNDATIONS <br />1. FOUNDATION DESIGN IS BASED ON INFORMATION AND RECOMMENDATIONS <br />PROVIDED IN THE GEOTECHNICAL REPORT 0120-294-02 PREPARED BY GEO <br />ENGINEERS, DATED JUNE 15, 2022. SHALLOW FOUNDATIONS ARE DESIGNED FOR A <br />MAXIMUM ALLOWABLE SOIL BEARING CAPACITY OF 4000 PSF AND ALLOWABLE SOIL <br />MODULUS OF 475 PCI, <br />2. SUB -GRADE FOR ALL FOUNDATIONS SHALL BE PREPARED AND <br />COMPACTED IN ACCORDANCE WITH RECOMMENDATIONS STATED IN THE <br />GEOTECHNICAL REPORT REFERENCED ABOVE. <br />3. EXCAVATION FOR FOUNDATIONS SHOWN ON DRAWINGS SHALL NOT BE LARGER <br />THAN THE INDICATED FOUNDATION SIZE BY MORE THAN 3" EACH DIRECTION <br />ADHESIVE ANCHORS: <br />1. FOR POST -INSTALLED ADHESIVE ANCHORS INTO CONCRETE, PRODUCTS SHALT® HAVE <br />BEEN TESTED AND QUALIFIED FOR USE IN ACCORDANCE WITH AC1355.4 AND ICC-ES <br />AC303.':PRE-APPROVED ADHESIVES INCLUDE: <br />A. SIMPSON STRONG -TIE "SET XP" (ICC-ES ESR-2508) <br />B. ;HILTI HIT-HY200 ADHESIVE ANCHORING SYSTEM (ICC-ERS-3187) <br />2. FOR POST -INSTALLED ADHESIVE ANCHORS INTO MASONRY, PRODUCTS SHALL <br />HAVE BEEN TESTED AND QUALIFIED FOR USE IN ACCORDANCE WITH ICC-ES AC58. <br />PRE -APPROVED ADHESIVES INCLUDE: (ALL MASONRY CELLS TO RECEIVE <br />ANCHORS SHALL BE GROUTED SOLID) <br />A. SIMPSON STRONG -TIE "SET" (ICC-ES ESR-1772) <br />B. 'HILTI HIT-HY 150 MAX (ICC-ES ESR-1917) <br />C. HILTI HIT -RE 500 V3 (ICC-ES ESR-3814) <br />3. SUBSTITUTION REQUESTS FOR PRODUCTS OTHER THAN THOSE LISTED ABOVE <br />MAY BE SUBMITTED BY THE CONTRACTOR TO THE ENGINEER=OF-RECORD (EOR) <br />FOR REVIEW, SUBSTITUTIONS WILL ONLY BE CONSIDERED FOR PRODUCTS <br />HAVING:A CODE REPORT RECOGNIZING THE PRODUCT FOR THE APPROPRIATE <br />APPLICATION. SUBSTITUTION REQUESTS SHALL INCLUDE CALCULATIONS <br />DEMONSTRATING THE SUBSTITUTION IS THE EQUIVALENT CAPABLE OF ACHIEVING <br />PERFORMANCE VALUES OF THE PRE -APPROVED PRODUCTS. <br />4. ADHESIVE ANCHORS SHALL BE INSTALLED PER THE MANUFACTURER'S <br />INSTRUCTIONS. THE CONTRACTOR SHALL CONTACT THE MANUFACTURER FOR <br />PRODUCT INSTALLATION TRAINING. <br />5. MINIMUM EMBEDMENT FOR ADHESIVE ANCHORS SHALL BE AS FOLLOWS, UNO: <br />1/2" DIA = 41/2" 3/4" DIA = 6 3/4" <br />5/8ti DIA = 5 5/8" 1" DIA 9 <br />x, <br />THIS DESIGN - <br />rr <br />SPECIFICATION IS APPROVED <br />- <br />1. DEAD LOADS: <br />A. UPPER MACHINE PLINTHS 500,000 LBS PER POSITION EVENLY DISTRIBUTED OVER <br />PLINTH FOOTPRINT (125,000 LBS PER PLINTH LINE) . <br />B. FDAJ COLUMNS (SEE DRAWING 3849-50-0001 FOR DEAD LOADS) (FDAJ112W0000-9/-10). <br />C. LOWER ROBOT BEDS 80,000 LBS EVENLY DISTRIBUTED ACROSS 4 BED LINES (20,000 <br />LBS PER INDIVIDUAL BED LINE). <br />D. ALL MACHINE TRANSPORT COLUMN BASES VARY AS SHOWN BELOW <br />0.83 KLF 1 0.60 KLF <br />TRANSPORTER DEAD LOADS <br />ASSUME ALL COLUMNS <br />E. FME DECKING (NOT SHOWN) 400,000 LBS ACROSS *TBD* SUPPORT LEGS <br />(FME 112WOO®0=9/-10). <br />2. LIVE LOADS: <br />A. UPPER GANTRY MACHINES 48,000 LBS PER MACHINE, 4 MACHINES PER CELL, 8 <br />MACHINES PER POSITION MAX. LOADS CARRIED THROUGH PLINTH FLOOR PLATES (A). <br />UP TO 27,000 LBS PER MACHINE LEG, MINIMUM SPACING OF IN". X - Y LIVE LOADS <br />MINIMAL: <br />B. LOUVER:ROI30TS 20,000 LBS PER ROBOT 4 ROBOTS PER CELL, 8 ROBOTS PER <br />POSITION, 60" SPANS, 24-10" ON CENTER, MINIMUM. <br />C. LOWER ROBOT ON TRANSPORTER 35000 LBS, 2 LINE LOADS OF 17,500 LBS 15, LONG. <br />D. ALL MACHINE TRANSPORT COLUMN BASES VARY AS SHOWN BELOW. <br />1.64 KLF 2.29 KLF <br />0.37 KLF 0.52 KLF <br />TRANSPORTER LIVE LOADS i ]� <br />50% LOADING TRANSPORTER LIVE LOADS <br />E. ACV 20,000 LBS. 70% LOADING <br />F. RSM (HEAVIEST CART)120,000 LBS DISTRIBUTED OVER TRANSPORT CART WHEEL <br />PATH (PME112W0000-9/-10). <br />G. AIRCRAFT PART WEIGHTS LOADED ONTO STANCHIONS. SEE 3849-50-000`I FOR LOADS <br />APPLIED AS COMPONENTS ARE ASSEMBLED. <br />H. UPPER COVER FRAME LOADS 11 KIP ON ROOT END POSTS, 4.5 KIP ON TIP END POSTS <br />(FDAJ I12W0000-91-10). <br />I. PULSE FRAME 100 KIP, 70 ON ROOT END WHEEL SET, 30 ON TIP. ENTERS AND LEAVES <br />CELL FROM ROOT END (MAX 1080 PSI WHEEL LOAD). <br />3. DEFLECTIONS UNDER LIVE LOADS: <br />A. UNDER THE LIVE LOADS FROM THE UPPER MACHINES AND TRANSPORT COLUMNS, THE <br />PLINTH FLOOR PLATES CANNOT DEFLECT MORE THAN .0035" IN THE Z RELATIVE TO EACH <br />OTHER (RISE AND FALL), ADDITIONALLY, LINE "A" CANNOT DEFLECT MORE THAN .0004" IN Z <br />FROM LINE"B" OVER ANY 12'-0" LENGTH IN X (TWISTING). <br />B. THE ROBOT LIVE LOAD IS APPLIED ANYWHERE BETWEEN THE ROBOT BEDS. UNDER THE <br />LIVE LOADS FROM THE LOWER ROBOTS, LINE "C" CANNOT DEFLECT MORE THAN .0005" IN Z <br />FROM LINE "D" OVER ANY 24'-0°" LENGTH. <br />C. FDAJ STANCHIONS (FDAJ112W0000-9/-10). REDUCED REQUIREMENTS (HATCHED AREA <br />ONLY) NEAR THE GANTRY TRANSPORTER OF .0015" LINE A TO B DIFFERENTIAL. SEE SHEET <br />S451. <br />4. THE MAXIMUM LOAD ON A SINGLE WHEEL SHALL NOT EXCEED 16,000 POUNDS FOR GROUP <br />ACTION, WHEEL DISTRIBUTED LOAD ON THE FLOOR SLAB SHALL NOT EXCEED 500 POUNDS PER <br />SQUARE FOOT (PSF). <br />5. ALL LOADS ARE PROVIDED AT NET VALUES. NO FACTORS ARE INCLUDED. APPROPRIATE <br />SAFETY FACTORS SHOULD DE APPLIED DEPENDING ON CODE OR PERFORMANCE <br />REQUIREMENTS. <br />6. MACHINE DEFLECTION BUYOFF PROCEDURE: LASER TRACKER NESTS WILL BE PLACED AT THE <br />FLOOR SURFACE NEAR THE MACHINE BEDS AND PLINTHS. THE MACHINES WILL BE DRIVEN IN X <br />AND THE VERTICAL DISPLACEMENT OF THE FLOOR WILL BE MEASURED, DIFFERENCES IN LEVEL <br />BETWEEN ONE SIDE OF THE PLINTH AND/OR BED SHALL BE COMPARED TO THE DEFLECTION <br />REQUIREMENT. <br />7. STANCHION DEFLECTION BUYOFF PROCEDURE: TBD <br />8. SEISMIC AND ANCHOR PULLOUT REQUIREMENTS (PRELIMINARY: TO BE SPECIFIED FOR EACH LOCATION) <br />A. 1.25" X 15" EPDXIED INTO 1.375" CORED HOLE: 25 KIP MINIMUM PULLOUT <br />FORCE AT 30" SPACING (ALONG PLINTH LINES). 1" X 12" EPDXIED INTO 1.125" <br />CORED HOLE: 15 KIP MINIMUM PULLOUT FORCE AT 24" SPACING. <br />B. LOWER ROBOT:SPECIFIC REQUIREMENTS (C): 5 KIP PULL UP ON ANCHORS SET <br />AT 12" CENTERS (1" ANCHORS). PLINTH SPECIFIC REQUIREMENTS (A): 25 KIP <br />PULL UP ON 1.25" ANCHORS SET AT 30" SPACING. FDAJ STANCHION SPECIFIC <br />REQUIREMENTS (B) 20 KIP ON CORNER OF EACH STANCHION PAD. <br />9. TRENCH COVERS, WALLS, AND FOUNDATIONS WORST CASE OF THE FOLLOWING: <br />A. 500 PSF APPLIED UNIFORMLY <br />B. HS-2Q TRUCK LOADING (AASHTO) <br />C. 30,000PSF APPLIED TO 12"xl2°" AREA <br />MITIGATION:DEBRIS <br />1. CONTRACTOR SHALL COORDINATE WITH OWNER FOR DEBRIS MITIGATION AND CLEAN-UP REQUIREMENTS FOR ALL <br />CONSTRUCTION ACTIVITIES AFFECTING AREAS WITHIN THE EXISTING OPERATIONAL BUILDING. <br />FLOOR FLATNESS REQUIREMENTS. - <br />NO STEPS SHALL BE LARGER THAN 0.125" <br />2. SEE DETAIL BELOW FOR FINISHED SURFACE FLATNESS <br />LU <br />10' x 10' SQUARE t I I P <br />IN CRITICAL AREAS (A) FF60 IN <br />GLOBAL <br />NON CRITICAL AREAS (B) FF40 <br />FINISHED SURFACES FLATNESS <br />AND LEVEL REQUIREMENTS <br />3. FLOOR FLATNESS REQUIREMENTS: <br />FF OVERALL = 60 <br />FF MINIMUM LOCAL VALUE = 40 <br />GENERAL CONFORMITY TO DESIGN GRADE: <br />FINISHED FLOOR ELEVATION OF EACH CELL <br />SHALL FALL WITHIN <br />x gim <br />pg <br />+/- .5 INCH OF DESIGN ELEVATION <br />�t � <br />`#` > ,VER <br />RL !EWE FOR PERMIT <br />,TE SUBTITLE - <br />06/30/22 <br />GENERALNOTES <br />06/30/22 <br />TITLE HBL EXPANSION - POSITIONS 5 & 0 <br />06/30/22 <br />STRUCTURAL MASTER EVERETT,WA <br />W <br />LU <br />www.brph.com <br />o2022 <br />Architects Engineers, <br />Inc" <br />19020 33rd Ave W, Suite #500 <br />State of Washington <br />Certifieate of Authorization <br />Lynnwood, Washington, 90036 <br />Architecture No. 603235512 <br />425-921-3500 <br />Engineering No. 3137 <br />CURRENT REVISION <br />SYMBOL <br />DATE <br />6123 <br />06/30/22 <br />SHEET <br />S2n-a <br />-200 <br />- <br />JOB NO. WO 15/2899-200 <br />c®MP NO. <br />DWG No. <br />0s023-S2n-214-a <br />cc <br />CS <br />5® <br />GG <br />C <br />