, GENERAL POWER AND CONTROL
<br />FLAG NOTE, IN CONSTRUCTION NOTE.
<br />BOAT NOTE, IN GENERAL NOTE,
<br />DETAIL NUMBER
<br />1
<br />1 10 E5 ' DETAIL SHEET
<br />CALLOUT SHEET
<br />101 DOOR TAG
<br />DISTRIBUTION SYSTEM
<br />I=
<br />DISTRIBUTION PANELBOARD 480Y/277V
<br />POWER PANEL, 208Y/120V
<br />E:=
<br />SPECIAL PANEL AS NOTED
<br />O
<br />GROUND ROD, "TW" INDICATES TEST WELL
<br />TW
<br />(4)#1,G,1-1 /2"C
<br />I'V N
<br />HOME RUN -PANEL- CIRCUIT (EXAMPLE 2V57) CROSS MARKS
<br />2V57- 4BMA10/2,4,6
<br />PNL-CKT
<br />INDICATE QUANTITY OF CONDUCTORS (SIZE NOTED) LONGER SLASH
<br />INDICATES NEUTRAL WIRE (IF REQUIRED). IF UNMARKED INSTALL 3#12 AWG
<br />IN 3/4 " CONDUIT. REVERSED SLASH INDICATES GROUND WIRE.
<br />CONDUIT EXPOSED (RIGID METAL)
<br />CONDUIT EMBEDDED IN CONCRETE OR BELOW GRADE
<br />—�/
<br />FLEXIBLE METAL OR LIQUIDTIGHT FLEX METAL CONDUIT AS NOTED
<br />-
<br />CONDUIT TURNING UP
<br />CONDUIT TURNING DOWN
<br />G
<br />GROUND WIRE (SIZE AS NOTED)
<br />G
<br />GROUND WIRE WITH EXOTHERMIC WELD CONNECTION
<br />E
<br />EMERGENCY CIRCUIT
<br />L
<br />EXPOSED LIGHTNING PROTECTION CONDUCTOR
<br />ETBj
<br />JUNCTION BOX, SPECIAL (SIZE NOTED, "WP"-WEATHERPROOF)
<br />PB
<br />PULL BOX (SIZE NOTED, "WP"-WEATHERPROOF)
<br />®
<br />FIELD TERMINAL BOX
<br />E-1/01
<br />REMOTE 1/0 RACK
<br />PM I
<br />POWER MONITOR DEVICE
<br />SYM
<br />A
<br />B
<br />® TRANSFORMER (CAPACITY, PHASE & VOLTAGE AS NOTED)
<br />NON -FUSED DISCONNECT SWITCH (ENCLOSED BREAKER OR MOLDED
<br />XX/Y CASE SWITCH WHERE FAULT CURRENT EXCEEDS 1 OKA)
<br />FF NN EXP XX- SWITCH RATING
<br />(ZMM6nZW�4<DB
<br />EXP - EXPLOSION PROOF (CLASS I / DIV I UNLESS NOTED OTHERWISE)
<br />ENCLOSED CIRCUIT BREAKER
<br />STARTER
<br />(M) MOTOR (SIZE AS NOTED)
<br />O GENERATOR, ALTERNATING CURRENT (VOLTAGE, KVA,
<br />PHASES, FREQUENCY AS NOTED)
<br />RECEPTACLE 20 AMP DUPLEX, 2 POLE, 3 WIRE
<br />r@E20 CLASS I, DIVISION I EXPLOSION PROOF GFCI 125V, 20A, 2P, 3W
<br />EXP INTERLOCKING RECEPTACLE. GROUSE HINDS CPS152 (RECEPTACLE)
<br />AND GFS-1 (GFI MODULE) OR APPROVED ALTERNATE.
<br />ABOVE COUNTER RECEPTACLE 20 AMP DUPLEX, 2 POLE, 3 WIRE
<br />SIG ISOLATED GROUND RECEPTACLE, 20AMP, DUPLEX, 2 POLE, 3 WIRE
<br />j aGFI
<br />GROUND FAULT INTERRUPT RECEPTACLE, 20AMP, DUPLEX, 2 POLE, 3WIRE
<br />WP
<br />WP INDICATES WEATHER PROOF
<br />RECEPTACLE 20AMP 4-PLEX, 2 POLE, 3 WIRE
<br />RECEPTACLE, NEMA CONFIGURATION AS INDICATED.
<br />L6-20R
<br />RECEPTACLE, 4801 20A SINGLE, 3P, 4W LOCKING TYPE NEMA L6-20
<br />GROUNDING
<br />RECEPTACLE, 208V/1 PH, 30A SINGLE, 2P, 3W LOCKING TYPE NEMA L6-30
<br />GROUNDING
<br />Q
<br />JUNCTION BOX, FIELD SIZED PER NEC.
<br />0FSD
<br />JUNCTION BOX, 120V CONNECTION FOR FIRE -SMOKE DAMPER
<br />QMOD
<br />JUNCTION BOX, 120V CONNECTION FOR MOTOR -OPERATED DAMPER
<br />CONNECTION TO EQUIPMENT AS INDICATED.
<br />MECHANICAL EQUIPMENT TAG.
<br />$M
<br />MOTOR RATED SWITCH
<br />POKE THRU DEVICE - REFER TO DETAIL 3 ON SHEET E508-02-46
<br />PT_X
<br />PT-1 - 6" POWER/DATA/AV POKE THRU DEVICE
<br />PT-2 - 8" POWER/DATA/AV POKE THRU DEVICE
<br />REVISION
<br />BY
<br />APPROVED
<br />777X CWC NEW BUILDING - RECORD WBS 2548317
<br />JMG
<br />DFC
<br />PFP SPAR PAINT BOOTH 1 AND 2 - XXX W5983281
<br />HG
<br />RLT
<br />I
<br />Y12
<br />MEDIUM VOLTAGE CIRCUIT BREAKER DRAWOUT TYPE
<br />v
<br />FUSE
<br />AF
<br />LOW VOLTAGE CIRCUIT BREAKER.
<br />AMP FRAME/AMP TRIP,
<br />25
<br />SYNCHRONISM - RELAY
<br />27
<br />UNDER VOLTAGE RELAY
<br />TINSTANTANEOUS/TIME
<br />OVERCURRENT
<br />RELAY
<br />51 N
<br />INSTANTANEOUS/TIME NEUTRAL
<br />MR
<br />PM
<br />AS
<br />VS
<br />Myl
<br />OVERCURRENT RELAY
<br />POWER FACTOR CORRECTION CAPACITORS
<br />(FUSED)
<br />CONTROL POWER TRANSFORMER
<br />"• ,_1 101 •1mu;
<br />MULTI-RATIOALLEN-BRADLEY POWER MONITOR 5000
<br />ANALOG AMMETER
<br />AMMETER SWITCH
<br />VOLTMETER SWITCH REIJ
<br />ANALOG VOLTMETER
<br />SYSTEM GROUND
<br />lin In •"" a •
<br />MOTOR STARTER (MANUAL)
<br />SOLENOID VALVE
<br />[Eil REMOTE CONTROL STATION (TYPE AS NOTED)
<br />0 EMERGENCY POWER SHUTDOWN
<br />T 3-COMPARTMENT POWER POLE WIRE MOLD 30TP-4
<br />PF
<br />2-COMPARTMENT POWER POLE WIRE MOLD 30TP-3
<br />SOB
<br />SWITCH BYPASS DEVICE
<br />CB
<br />MANUAL CONTROLLER
<br />TB
<br />TEST BLOCK
<br />LOW VOLTAGE CIRCUIT BREAKER.
<br />0
<br />v
<br />DRAWOUT TYPE
<br />`_`_J
<br />ELECTRICALLY OPERATED
<br />.J
<br />UNIT SUBSTATION TRANSFORMER
<br />49
<br />OVERLOAD RELAY
<br />86
<br />LOCKOUT RELAY
<br />G1 G2
<br />KIRK KEY INTERLOCKS. SEE BOEING
<br />27
<br />STANDARDS
<br />UNDERVOLTAGE RELAY
<br />46
<br />REVERSE PHASE CURRENT RELAY
<br />47
<br />PHASE SEQUENCE VOLTAGE RELAY
<br />25
<br />SYNCHRONIZING DEVICE
<br />LIGHTNING ARRESTER
<br />PRIMARY MEDIUM VOLTAGE FUSED
<br />SWITCH
<br />MEDIUM VOLTAGE CABLE TERMINATION
<br />GF
<br />GROUND FAULT MONITOR
<br />SP®
<br />SURGE PROTECTIVE DEVICE
<br />SG
<br />STATIC GROUND RECEPTACLE
<br />MOTOR LOAD
<br />WELDING RECEPTACLE
<br />DATE SYM REVISION
<br />01/03117
<br />XX.XX,XX
<br />BY I APPROVED
<br />DATE
<br />LIGHTING FIXTURES: UPPER CASE ALPHA -NUMERIC CHARACTER INDICATES FIXTURE TYPE.
<br />LOWER CASE ALPHA -NUMERIC CHARACTER INDICATES CIRCUIT NUMBER AND PHASE FED FROM.
<br />UPPER CASE ALPHA -NUMERIC CHARACTER IN PARENTHESIS INDICATES RELAY NUMBER.
<br />LOWER CASE LETTER INDICATES SWITCH LEG.
<br />"NL" INDICATES NIGHT LIGHT OPERATION (CIRCUIT NOT SWITCHED),
<br />STRUCTURE MOUNTED LED HIGH BAY FIXTURE. EACH FIXTURE SHALL INCLUDE
<br />A QUICK DISCONNECT AND IN -LINE FUSE.
<br />STRUCTURE MOUNTED LED HIGH BAY FIXTURE (EMERGENCY). EACH FIXTURE
<br />SHALL INCLUDE A QUICK DISCONNECT AND IN -LINE FUSE.
<br />i-�—I INDUSTRIAL FLUORESCENT/LED LIGHTING FIXTURE.
<br />INDUSTRIAL FLUORESCENT/LED LIGHTING FIXTURE (EMERGENCY)
<br />WALL/RECESSED/SURFACE MOUNTED FLUORESCENT/LED LIGHTING FIXTURE.
<br />WALURECESSED/SURFACE MOUNTED FLUORESCENT/LED LIGHTING FIXTURE (EMERGENCY)
<br />3 I�
<br />PHASE
<br />4801 VAC POWER CABLES
<br />A -PHASE (LEFT BUS IN PNL)
<br />BROWN
<br />B-PHASE (CENTER BUS IN PNL)
<br />ORANGE
<br />C-PHASE (RIGHT BUS IN PNL)
<br />YELLOW
<br />NEUTRAL
<br />GRAY
<br />EQUIPMENT GROUND
<br />GREEN
<br />ISOLATED GROUND
<br />GRN/YEL*
<br />* GREEN WITH YELLOW
<br />TRACER
<br />LIGHTING CONTROL SWITCHES AND OCCUPANCY SENSORS: ADDITIONAL LOWER CASE
<br />LETTER INDICATES SWITCH LEG.
<br />SINGLE POLE TOGGLE WALL SWITCH
<br />$3 THREE-WAY TOGGLE WALL SWITCH
<br />$OS LINE -VOLTAGE OCCUPANCY SENSOR WALL SWITCH
<br />$ WP SINGLE POLE TOGGLE WALL SWITCH, WEATHERPROOF
<br />XX $LV LOW -VOLTAGE, 2-BUTTON ON/OFF WALL SWITCH. SWITCH TO TIE
<br />INTO GE LIGHTSWEEP LIGHTING CONTROL PANEL(S) SERVING
<br />RESPECTIVE AREA. REFER TO GE LIGHTING LIGHTSWEEP CONTROL
<br />DRAWINGS FOR MORE INFORMATION
<br />WHERE SHOWN)FIRST DIGIT REPRESENTS FLOOR (U - 2ND FLOOR, V - 3RD FLOOR)
<br />SECOND DIGIT SPECIFIES LIGHTING CONTROL ZONE. SEE CONTROL ZONE PLANS 2E8
<br />AND 3E8 FOR ADDITIONAL INFORMATION.
<br />OC CEILING MOUNTED, LOW -VOLTAGE, DUAL TECHNOLOGY OCCUPANCY SENSOR WITH POWER PACK
<br />LCP POWER PACK: HUBBELL #UVPP OR APPROVED EQUAL (FOR EACH OCCUPANCY SENSOR)
<br />ROOMS: HUBBELL #OMNI-DT-500/100 OR APPROVED EQUAL (500/1000 SQ. FEET)
<br />CORRIDORS/TUNNELS: HUBBELL #OMNI-DT-2000 OR APPROVED EQUAL (2,000 SQ, FEET)
<br />SUBSCRIPT INDICATES LOW VOLTAGE OCCUPANCY SENSOR WIRED BACK TO GE LIGHTING CONTROL PANEL
<br />INDICATED.
<br />BUILDING MOUNTED PHOTOCELL.
<br />ZONE X $H13
<br />LOW -VOLTAGE, 2-BUTTON HIGH BAY LIGHTING WALL SWITCH WITH
<br />DESIGNATED ZONE. SWITCH TO TIE INTO GE LIGHTSWEEP LIGHTING
<br />CONTROL PANEL(S) SERVING RESPECTIVE ZONES. BUTTONS SHALL
<br />INCLUDE:'OVERRIDE' AND'UNASSIGNED'. REFER TO GE LIGHTING
<br />LIGHTSWEEP CONTROL DRAWINGS FOR MORE INFORMATION,
<br />$ T
<br />120 MINUTE TIMER WALL SWITCH
<br />$D
<br />SINGLE -POLE DIMMER WALL SWITCH
<br />ALUMINUM LADDER TYPE CABLE TRAY. SIZE & HEIGHT AS NOTED ON DRAWINGS.
<br />12" CABLE RUNWAY,
<br />CE
<br />COMMUNICATIONS ENCLOSURE.
<br /><#
<br />2-PORT MODULAR STAINLESS STEEL FACEPLATE WITH (1) CAT 5e CABLE FROM"CE" OR "CR, INDICATED AND
<br />(1) RJ-45 CONNECTOR FOR DATA OUTLET. PROVIDE BLANK COVER FOR UNUSED PORT. SUBSCRIPT
<br />INDICATES NUMBER OF ACTIVE JACKS IF GREATER THAN 1.
<br />E
<br />STAINLESS STEEL FACEPLATE WITH MOUNTING STUD SCREWS, (1) CAT 5e UTP CABLE FROM 110 PUNCH -
<br />DOWN BLOCKS INDICATED AND (1) RJ-45 CONNECTOR FOR ANALOG EMERGENCY PHONE OUTLET. MOUNT
<br />OUTLET AT 48" AFF, LION. COORDINATE EXACT LOCATION WITH OWNERS FIRE SAFETY REPRESENTATIVE
<br />PRIOR TO ROUGH -IN.
<br />(�)
<br />CCTV OUTLET FOR INTERIOR CAMERA: SURFACE MOUNTED BOX INSTALLED ABOVE CEILING ON TILE BRIDGE
<br />�-✓
<br />WITH 1-PORT MODULAR FACEPLATE WITH (1) CAT 5e UTP CABLE AND (1) RJ-45 CONNECTOR. ROUT CAT5e
<br />CABLE BACK TO "CE" OR "CR" INDICATED. CAMERA PROVIDED BY OTHERS.
<br />2-PORT MODULAR STAINLESS STEEL FACEPLATE WITH (1) CAT 5e UTP CABLE FROM "CE" OR "CR" INDICATED
<br />AND (1) CAT 5e CABLE FROM 110 PUNCHDOWN BLOCKS INDICATED AND (2) RJ-45 CONNECTORS.
<br />PB
<br />PULLBOX. SIZE AND TYPE AS NOTED ON DRAWINGS.
<br />NOW PAINTED FIRE RETARDANT PLYWOOD BACKBOARD.
<br />110
<br />110 STYLE PUNCHDOWN BLOCKS.
<br />CCVT
<br />CCTV ENCLOSURE FOR EXTERIOR CAMERA.
<br />AMS
<br />AMS PANEL.
<br />BR
<br />BADGE READER,
<br />BR
<br />PREPPED DOOR AND BADGE READER
<br />P
<br />IS
<br />SUBSTATION POWER MONITOR NETWORK POINT OF CONNECTION. COORDINATE WITH OWNER FOR EXACT
<br />LOCATION WITHIN SUBSTATION,
<br />CEILING MOUNTED VOICE/DATA OUTLET WITH (1) CAT 5e CABLE AND (1) RJ-45 CONNECTOR TO "CE" OR "CR"
<br />INDICATED. LOCATE ADJACENT TO PROJECTOR POWER RECEPTACLE.
<br />2-PORT MODULAR OUTLET WITH (1) CAT 5e CABLE FROM "CE" OR "CR" INDICATED AND (1) RJ-45 CONNECTOR
<br />FOR DATA OUTLET. OUTLET IS MOUNTED WITHIN MULTI -PURPOSE POKE-THRU/ FLOORBOX. REFER TO
<br />208/120V POWER DRAWINGS FOR POKE THRU/ FLOORBOX LOCATIONS. PROVIDE BLANK COVER FOR
<br />UNUSED PORT. SUBSCRIPT INDICATES NUMBER OF ACTIVE JACKS IF GREATER THAN 1.
<br />DMS
<br />DOOR MONITORING SYSTEM.
<br />VENTILATION SYSTEM EMERGENCY SHUTOFF SWITCH.
<br />XE 4 V58-3A M A2-1-D
<br />208Y/120 VAC POWER CABLES
<br />BLACK
<br />RED
<br />BLUE
<br />WHITE
<br />GREEN
<br />GRN/YEL*
<br />**TI BUILDOUT ONLY - PROVIDE
<br />NEETRAL WITH COLOR TRACER TO
<br />MATCH PHASE
<br />ule
<br />LSUFFIX "D" INDICATES DISTRIBUTION PANEL
<br />SUFFIX "-1, -2, ETC." USED TO INDICATE MULTIPLE PANELS AT SAME LOCATION WITH SAME VOLTAGE AND FED FROM SAME VAULT
<br />NEAREST COLUMN INTERSECTION
<br />LOCATION OF PANEL WHEN NOT ON FIRST FLOOR:
<br />TN1 = TUNNEL LEVEL 1
<br />TN2 = TUNNEL LEVEL 2
<br />P = AUTOCLAVE PIT
<br />M = MEZZANINE
<br />U = LEVEL 2
<br />V = LEVEL 3
<br />C = CATWALK
<br />RF = ROOF
<br />VAULT
<br />VOLTAGE:
<br />4 = 480V, 3PH, 3W
<br />3 = 480Y/277V, 3PH, 4W
<br />2 = 208Y/120V, 3PH, 4W OR 120/24OV,1 PH, 3W
<br />Sam
<br />(BLANK) = NORMAL POWER PANEL
<br />"I" = ISOLATED GND PANEL
<br />"Z" = 400 HZ PANEL
<br />"XF" = EMERGENCY PANEL
<br />"XL" = LEGALLY REQUIRED STANDBY PANEL
<br />"XS" = OPTIONAL STANDBY PANEL
<br />"'XU" = UPS SYSTEM
<br />ACCEPTABILITY
<br />THIS DESIGN AND/OR
<br />JKAWN
<br />RER
<br />CHECKED
<br />UAIt SUBTITLE
<br />12105/14
<br />ELECTRICAL LEGEND
<br />SPECIFICATION IS APPROVED
<br />RFW
<br />12/05114
<br />APPROVED BY DEPT. DATE
<br />ENGINEER
<br />DFC
<br />TITLE
<br />12/05/14
<br />PEP SPAR PAINT BOOTH 1 AND 2
<br />CHECKED
<br />BUILDING 40-058
<br />APPROVED
<br />0
<br />DRAWN: NH
<br />ENGINEER: EOF
<br />CHECKED: MWD
<br />CURRENT REVISION SYMBOL
<br />W5953281
<br />SHEET
<br />JOB No.
<br />EVERETT, WA DWG No.
<br />00-
<br />Our difference
<br />is engineered.
<br />www.harrisgroup.com
<br />REVISION °C" ONLY
<br />PROJECT NO: 0012630.06
<br />PROJ MGR: RLT
<br />APPROVED: RLT
<br />DATE: XX.XX.XX
<br />XX.XX.XX
<br />COMP NO.
<br />ELECTRICAL MASTER
<br />
|