<br />EXISTING I a
<br />FACTORY
<br />E
<br />^P�Sl
<br />P ° I
<br />FLOOR
<br />°
<br />I I I 0 i
<br />I ° e
<br />h °
<br />I I �
<br />4
<br />s
<br />a
<br />°
<br />EPGA
<br />e I°
<br />° ®M
<br />°
<br />� E
<br />�M
<br />s
<br />° I M:
<br />°
<br />°
<br />I
<br />SCALE, 1/3"=V-0"
<br />H-3
<br />® PAINT STORAGE
<br />442SFO.L.=5
<br />2 EXITS REQUIRED
<br />I
<br />s
<br />PAINT MIX
<br />487 SF O.L. = 5
<br />2 EXITS REQUIRED
<br />H-3
<br />GUN CLEANING
<br />233 SF O.L.=3
<br />1 EXIT REQUIRED
<br />E-1
<br />CHANGE ROOM 1
<br />128 SF O.L. =2
<br />1 EXIT REQUIRED
<br />E-1
<br />® CHANGE ROOM 2
<br />123SFO.L.=2
<br />1 EXIT REQUIRED
<br />AO
<br />#,AINT STORAGE
<br />1AZARDOUS ""'M"'LIANCE PLAN
<br />SCALE: 1/0"=V-0"
<br />''- --
<br />ROOM SHALL BE POSTED:
<br />MAXIMUM QUANTITIES OF CLASS IB e
<br />FLAMMABLE LIQUIDS SHALL NOT
<br />EXCEED:
<br />60 GALLONS IN OPEN USE
<br />240 GALLONS IN CLOSED USE
<br />UNDER 240 GALLONS CLASS IB
<br />FLAMMABLE LIQUIDS TOTAL IN M
<br />STORAGE AND USE ® NO VESSEL EXCEEDS 55 GALLONS
<br />AGGREGATE CAPACITY OF
<br />VESSELS SHALL BE UNDER 1,000 �-
<br />GALLONS
<br />PAINT MIX
<br />HAZARDOUS COMPLIANCE PLAN
<br />SCALE: 1/8"=l'-0"
<br />SCALE: 1 /8"44'
<br />SYM REVISION BY APPROVED DATE
<br />REVISION
<br />BY
<br />APPROVED
<br />DATE SYM
<br />A
<br />PFP SPAR PAINT BOOTH 1 AND 2 - IFC W5983281
<br />HG
<br />RLT
<br />11.19.19
<br />B
<br />PFP SPAR PAINT BOOTH 1 AND 2 - IFP W5983281
<br />HG
<br />RLT
<br />11.19.19
<br />AT
<br />ASH
<br />[IBC TABLE 307.1(1)]
<br />CLASS 1B FLAMMABLE LIQUIDS
<br />UNDER 60 GALLONS CLASS IB FLAMMABLE LIQUIDS IN USE OPEN SYSTEM
<br />UNDER 240 GALLONS CLASS IB FLAMMABLE LIQUIDS IN USE CLOSED SYSTEM
<br />UNDER 240 GALLONS IN STORAGE
<br />UNDER 240 GALLONS (OPEN USE +CLOSED USE +STORAGE)
<br />NO CLASS IB FLAMMABLE LIQUIDS IN USE OPEN SYSTEM
<br />NO CLASS IB FLAMMABLE LIQUIDS IN USE CLOSED SYSTEM
<br />UNDER 240 GALLONS IN STORAGE
<br />UNDER 240 GALLONS (OPEN USE +CLOSED USE +STORAGE)
<br />NO VESSEL EXCEEDS 55 GALLONS
<br />AGGREGATE CAPACITY OF VESSELS UNDER 1,000 GALLONS
<br />CURRENT ANTICIPATED HAZARDOUS MATERIALS QUANTITIES FOR THIS ROOM ALLOW AN F-1
<br />OCCUPANCY. BOEING HAS ELECTED TO DESIGN THE PAINT STORAGE ROOM AS AN H-3
<br />OCCUPANCY.
<br />OCCUPANCY GROUP H-3
<br />ALLOW FOR OVER 240,GA.LL NS IN STORAGE
<br />NO VESSEL EXCEEDS 55 GALLONS
<br />AGGREGATE CAPACITY OF VESSELS UNDER 1,000 GALLONS
<br />H OCCUPANCY COMPLIANCE
<br />SEE GENERAL NOTES
<br />HAZARDOUS MATERIALS COMPLIANCE
<br />NO EXPLOSION CONTROL CONTROL REQUIRED FOR CLASS IB FLAMMABLE LIQUIDS IN STORAGE.
<br />(IFC 5704.2.5, IFC 911.1, FOOTNOTE c)
<br />NO SPILL CONTROL OR SECONDARY CONTAINMENT REQUIRED FOR CLASS IB FLAMMABLE
<br />LIQUIDS IN STORAGE WHEN INDIVIDUAL VESSELS ARE UNDER 55 GALLONS AND AGGREGATE IS
<br />UNDER 1,000 GALLONS. (IFC 5004.2)
<br />2
<br />A
<br />1
<br />UNDER 60 GALLONS CLASS IB FLAMMABLE LIQUIDS IN USE OPEN SYSTEM
<br />UNDER 240 GALLONS CLASS IB FLAMMABLE LIQUIDS IN USE CLOSED SYSTEM
<br />UNDER 240 GALLONS CLASS IB FLAMMABLE LIQUIDS TOTAL IN STORAGE AND USE
<br />NO VESSEL EXCEEDS 55 GALLONS
<br />AGGREGATE CAPACITY OF VESSELS UNDER 1,000 GALLONS
<br />HAZARDOUS MATERIALS QUANTITIES FOR THIS ROOM ALLOW AN F-1 OCCUPANCY. BOEING
<br />HAS ELECTED TO DESIGN THE PAINT STORAGE ROOM AS AN H-3 OCCUPANCY BUT MAINTAIN
<br />THE LIMITS OF HAZARDOUS MATERIALS TO BELOW LIMITS SET IN IBC TABLE 307.1(1). H
<br />OCCUPANCIES SHALL BE IN ACCORDANCE WITH IBC SECTION 307,415 AND THE
<br />INTERNATIONAL FIRE CODE. THE DISPENSING, USE OR STORAGE OF HAZARDOUS
<br />MATERIALS SHALL COMPLY WITH (IBC 414) AND THE IFC.
<br />01 " enowa=11
<br />H OCCUPANCY COMPLIANCE
<br />SEE GENERAL NOTES
<br />HAZARDOUS MATERIALS COMPLIANCE
<br />NO EXPLOSION CONTROL REQUIRED FOR CLASS IB FLAMMABLE LIQUIDS WHEN QUANTITIES
<br />DO NOT EXCEED THE MAXIMUM AMOUNT PER TABLE 5003.1.1(1). IFC 5705.3.5.
<br />NO SPILL CONTROL REQUIRED FOR CLASS IB FLAMMABLE LIQUIDS WHEN QUANTITIES DO
<br />NOT EXCEED THE MAXIMUM AMOUNT PER TABLE 5003.1.1(1). IFC 5705.3.5.
<br />NO SECONDARY CONTAINMENT REQUIRED WHEN QUANTITIES DO NOT EXCEED THE
<br />MAXIMUM AMOUNT PER TABLE 5003.1.1(1). IFC 5705.3.5.
<br />SEE GENERAL NOTES FOR ADDITIONAL COMPLIANCE
<br />GUN CLEANING ROOM AO
<br />UNDER 60 GALLONS CLASS IB FLAMMABLE LIQUIDS IN USE OPEN SYSTEM
<br />UNDER 240 GALLONS CLASS IB FLAMMABLE LIQUIDS IN USE CLOSED SYSTEM
<br />UNDER 240 GALLONS CLASS IB FLAMMABLE LIQUIDS IN STORAGE
<br />OVER 240 GALLONS CLASS IB FLAMMABLE LIQUIDS TOTAL IN STORAGE AND USE
<br />NO VESSEL EXCEEDS 55 GALLONS
<br />AGGREGATE CAPACITY OF VESSELS UNDER 1,000 GALLONS
<br />OCCUPANCY GROUP H-3
<br />H OCCUPANCY COMPLIANCE
<br />SEE GENERAL NOTES
<br />HAZARDOUS MATERIALS COMPLIANCE
<br />NO EXPLOSION CONTROL, SPILL CONTROL OR CONTAINMENT REQUIRED FOR OPEN USE,
<br />CLOSED USE OR STOARGE WHEN QUANTITIES UNDER IBC TABLE 307.1(1)
<br />OVER 240 GALLONS IN STORAGE
<br />® SPILL CONTROL NOT REQUIRED INDIVIDUAL VESSEL DOES NOT EXEED 55 GALLONS AND
<br />AGGREGATE CAPACITY OF VESSELS DOES NOT EXCEED 1000 GALLONS (IFC 5004.2.1,
<br />5703.4)
<br />® SECONDARY CONTAINMENT NOT REQUIRED. INDIVIDUAL VESSEL DOES NOT EXCEED 55
<br />GALLONS AND AGGREGATE CAPACITY OF VESSELS DOES NOT EXCEED 1000 GALLONS (IFC
<br />5004.2.2, 5703.4)
<br />® EXPLOSION CONTROL NOT REQUIRED (IFC TABLE 911.1 FOOTNOTE c)
<br />3 FT CLEAR SPACE BETWEEN BOOTHS AND STORAGE OR COMBUSTIBLE CONSTRUCTION.
<br />BOOTHS ARE PERMITTED AGAINST WALLS. (IFC 2404.3.2.5). SEPARATED 3 FT FROM OTHER
<br />OPERATIONS, MULTIPLE CONNECTED SPRAY BOOTHS SHALL NOT BE CONSIDERED "OTHER
<br />OPERATIONS". (NFPA 33 SECTION 5.3) o
<br />5174
<br />REGISTERED
<br />ARCHITECT
<br />ROBERTA L. GaFGLIANO
<br />STATE OF WASHIINGTON
<br />11 /21 /2019
<br />EXISTING BUILDING
<br />OCCUPANCY: SPECIAL INDUSTRIAL
<br />F-1 /S-1 /B/H-3
<br />TYPE OF CONSTRUCTION: TYPE IIB FULLY SPRINKLERED
<br />AREA/HEIGHT/NUMBER OF STORIES:
<br />ACTUAL ALLOWED
<br />AREA UNLIMITED
<br />1ST FLOOR 1,217,869
<br />MEZZANINE 50,848 2/3 OF FLOOR AREA OF ROOM
<br />2ND MEZZANINE 94,007
<br />3RD MEZZANINE 94,007
<br />EQUIPMENT PLATFORMS MEZZ PLUS EQUIP >2/3RD OF ROOM
<br />BUILDING AREA: 1,217,869
<br />FIRE AREA (1ST FLOOR PLUS MEZZANINES): 1,456,731
<br />ACTUAL ALLOWED
<br />HEIGHT 11T-8" AT PARAPET UNLIMITED
<br />14T-4" AT STAIR TOWER
<br />NUMBER OF STORIES 1 3
<br />NUMBER OF MEZZANINES 3 3
<br />DESCRIPTION OF WORK FOR PAINT SUPPORT ROOMS
<br />THIS PROJECT REMODELS 1,522 SF OF EXISTING F1 FACTORY FLOOR AREA INTO A PAINT STORAGE ROOM,
<br />PAINT MIX ROOM, GUN CLEANING ROOM, AND 2 CHANGING ROOMS WITH AN EQUIPMENT PLATFORM
<br />ABOVE. THE (3) PAINT ROOMS ARE AN H3 OCCUPANCY. THE OTHER ROOMS REMAIN F1 OCCUPANCY.
<br />THERE IS NO CHANGE TO THE TOTAL BUILDING FLOOR AREA. TWO SPRAY ROOMS (AS DEFINED BY IFC
<br />CHAPTER 24) ARE PLANNED UNDER A SEPARATE PERMIT.
<br />AREA/HEIGHT/NUMBER OF STORIES:
<br />EXISTING PROPOSED ALLOWED
<br />AREA UNLIMITED
<br />1ST FLOOR 1,217,869 NO CHANGE
<br />MEZZANINE 50,848 NO CHANGE 2/3 OF FLOOR AREA OF ROOM
<br />2ND MEZZANINE 94,007 NO CHANGE
<br />3RD MEZZANINE 94,007 NO CHANGE
<br />EQUIPMENT PLATFORMS 1,522 SF MEZZ PLUS EQUIP >2/3RD OF ROOM
<br />FIRE AREA (1ST FLOOR PLUS MEZZANINES): 1,456,731 NO CHANGE
<br />ALLOWABLE GROUP H AREA:
<br />OCUPANCY ACTUAL ALLOWED WHEN NOT ON PERIMETER (507.8.1.1).
<br />PAINT STORAGE H-3 442 1,000
<br />PAINT MIX H-3 487 500
<br />GUN CLEANING H-3 233 500
<br />CHANGE ROOM 1 F-1 (NO CHANGE) 128
<br />CHANGE ROOM 2 F-1(NO CHANGE) 123
<br />ALLOWABLE GROUP H AREA NOT LOCATED ON THE PERIMETER OF AN UNLIMITED AREA BUILDING
<br />(IBC 507.8.1):
<br />NOT MORE THAN 25% OF THE AREA LIMITATIONS FOR GROUP H OCCUPANCIES AS SPECIFIED
<br />IN SECTION 506:
<br />14,000 SF x 25% = 3,500 SF
<br />TOTAL GROUP H NOT LOCATED ON PERIMETER = 1,162 SF < 3,500 SF
<br />ALLOWABLE GROUP H AREA IN AN UNLIMITED AREA BUILDING (IBC 507.8.1):
<br />1. NOT MORE THAN 10% OF THE AREA OF THE BUILDING
<br />10%X 1,217,869=121,787 SF
<br />EXISTING H3 H3 THIS PROJECT
<br />911 SF + 1,162 SF = 2,073 SF < 121,787 SF
<br />OR
<br />2, THE AREA LIMITATIONS FOR GROUP H AS SPECIFIED IN IBC 506:
<br />14,000 SF WITHOUT ALLOWED INCREASES
<br />EXISTING H3 H3 THIS PROJECT
<br />911 SF + 1,162 SF = 2,073 SF < 14,000 SF
<br />OCCUPANCY: SPECIAL INDUSTRIAL
<br />F1/H3
<br />UNLIMITED AREA BUILDING WITH GROUP H OCCUPANCY
<br />ACTUAL PROPOSED ALLOWED
<br />HEIGHT 147'-4" NO CHANGE UNLIMITED
<br />NUMBER OF STORIES 1 NO CHANGE 3
<br />NUMBER OF MEZZANINES 3 NO CHANGE 3
<br />OCCUPANCY SEPARATION:
<br />F-1/H-3: UNLIMITED AREA BUILDING (IBC 507.8.3) : 1 HR
<br />SEPARATED OCCUPANCY (IBC 507.8.3)
<br />SEPARATION SHALL BE A FIRE BARRIER (IBC 707.3.9)
<br />SUPPORTING CONSTRUCTION SHALL BE PROTECTED (IBC 707.5.1)
<br />OCCUPANT LOAD:
<br />2 EXITS REQUIRED FROM H-3 OCCUPANCY WHEN OCCUPANT LOAD IS GREATER THAN 3.
<br />2 EXISTS REQUIRED FROM F OCCUPANCY WHEN OCCUPANT LOAD IS GREATER THAN 49.
<br />TYPE OF CONSTRUCTION: NO CHANGE
<br />4
<br />AO bUALL: 'I /b 7 -U" AO
<br />ACCEPTABILITY
<br />DRAM
<br />R, PINLAC
<br />THIS DESIGN AND/OR
<br />CHECKED
<br />SPECIFICATION IS APPROVED
<br />R, PINLAC
<br />ENGINEER
<br />APPROVED BY DEPT. DATE
<br />R. GHIGLIANO
<br />CHECKED
<br />L.COSGROVE
<br />APPROVED
<br />R. PLUCINSKI
<br />APPROVED
<br />R. THIRTYACRE
<br />LEGEND
<br />®®®®I° EXISTING 1HRWALL OCCUPANCY SEPARATION
<br />------©-- EXIT ACCESS TRAVEL DISTANCE
<br />---------- COMMON PATH OF TRAVEL
<br />REQUIRED EXIT
<br />\ 60" DIAMETER WHEELCHAIR TURNING SPACE
<br />12" DOOR SWING ENCROACHMENT
<br />/ INTO WHEELCHAIR TURNING SPACE
<br />36" X 48" CLEAR FLOOR SPACE
<br />J SHOWER
<br />30" X 48" CLEAR FLOOR SPACE
<br />L-__J LAV
<br />30" X 48" CLEAR FLOOR SPACE
<br />®� BENCH AT WALL
<br />-lII
<br />L - J
<br />W- -1 30" X 48" CLEAR FLOOR SPACE
<br />L LOCKER
<br />60" DEEP CLEAR FLOOR SPACE
<br />PULL SIDE,FRONT APPROACH DOOR
<br />zC
<br />GENERAL NOTES
<br />1. SEE 1AL10-14 FOR BUILDING LIFE SAFETY EGRESS ARANGEMENT.
<br />2. MINIMUM AISLE WIDTH (IBC 1018.5):
<br />36" OL IS UNDER 50
<br />44" OL IS OVER 50
<br />24" AT ACCESS TO MECHANICAL, PLUMBING OR ELECTRICAL
<br />SYSTEMS OR EQUIPMENT
<br />28" NONPUBLIC AISLE WHERE ADA ACCESS IS NOT
<br />REQUIRED SERVING LESS THAN 50 (IBC 1018.5)
<br />ADA ACCESS (IBC 1103.2.9)
<br />SERVICE AREAS FREQUENTED ONLY BY SERVICE PERSONNEL FOR
<br />MAINTENANCE, REPAIR OR OCCASIONAL MONITORING OF EQUIPMENT
<br />ARE NOT REQUIRED TO BE ACCESSIBLE.
<br />3. DOORS IN ANY POSITION SHALL NOT REDUCE THE REQUIRED WIDTH
<br />BY MORE THAN ONE-HALF. (IBC 1005.7)
<br />ALLOWABLE EXIT ACCESS TRAVEL DISTANCE IN H-3 OCCUPANCY IS 150'.
<br />ACTUAL WORST CASE EXIT ACCESS TRAVEL DISTANCE IS 109'. IBC
<br />TABLE 1017.2
<br />5 ALLOWABLE COMMON PATH OF TRAVEL IN H-3 IS 25'. ACTUAL WORST
<br />CASE COMMON PATH OF TRAVEL IS 20'. IBC TABLE 1006.2.1
<br />6 ALLOWABLE EXIT ACCESS TRAVEL DISTANCE IN AIRCRAFT
<br />MANUFACTURING FACILITIES IS 1,500'. ACTUAL WORST CASE EXIT
<br />ACCESS TRAVEL DISTANCE THIS PROJECT IS 123'. 166' AROUND NEW
<br />PAINT ROOMS ON FACTORY FLOOR.
<br />7 ALLOWABLE COMMON PATH OF TRAVEL IN F-1 IS 100'. ACTUAL WORST
<br />CASE COMMON PATH OF TRAVEL IS 12'. IBC TABLE 1006.2.1.
<br />FO NOT LESS THAN 25% OF THE PERIMETER WALL OF AN H-3 OCCUPANCY
<br />SHALL BE AN EXTERIOR WALL EXCEPT:
<br />® LIQUID USE, DISPENSING AND MIXING ROOMS NOT MORE THAN
<br />500 SF
<br />® LIQUID STORAGE ROOMS HAVING A FLOOR AREA OF NOT MORE
<br />THAN 1,000 SF
<br />9. THE TOTAL FLOOR AREA OF H OCCUPANCIES NOT LOCATED ON AN
<br />EXTERIOR WALL SHALL NOT EXCEED 25% OF THE AREA LIMITATIONS
<br />FOR THE H GROUP OCCUPANCY:
<br />.25 x 13,000 sf = 3,250sf ALLOWED. 1,117 sf ACTUAL.
<br />10. THE TOTAL FLOOR AREA OF H OCCUPANCY OF.AN UNLIMITED AREA
<br />BUILDING SHALL BE LIMITED TO 10% OF THE BUILDING AREA:
<br />.10 x 1,217,869 SF = 121,789 sf ALLOWED. ACTUAL H THIS PROJECT =
<br />1,117 sf + EXISTING H IN PANEL PAINT = 900 sf.
<br />TOTAL = 2,017 sf<l21,789 sf
<br />11. SUPPORTING CONSTRUCTION AT HORIZONTAL FIRE BARRIERS
<br />SEPARATING MIXED OCCUPANCIES (IBC 707.5.1, 711.2.3):
<br />1) COLUMNS MUST BE INDIVIDUALLY ENCASED. (IBC704.2)
<br />2) BEAMS THAT ARE PART OF THE PRIMARY STRUCTURAL FRAME
<br />MAY BE PROTECTED ON EXPOSED SIDES ONLY. (IBC704.3)
<br />3) MIXED OCCUPANCY REQUIRED PROTECTION = H-3/F-1 =1 HR
<br />(IBC 508A).
<br />CITY OF EVERETT
<br />REVIEWED FOR PERMIT (Bll
<br />ISSUED
<br />ffil