Laserfiche WebLink
4 . • <br /> Additional Comments: <br /> 16. Plans A2.0 and A4.0, and Equipment Plan 1/A-3.0 are not consistent. The drawings should <br /> be revised. See IBC Section 107.2.1. <br /> REPLY:See revised plan A-3.0 to match layout plans of A2.0 and A4.0. <br /> 17. The plan includes new rooms. Details for the construction of the walls, including <br /> connections to the floor and ceiling/roof should be provided. The walls should be designed for <br /> the loads per IBC Section 1607.14. See IBC Sections 107.2.1, 1603.1, and 1604.1. <br /> REPLY:See sheet A6.0 for new construction wall details. The new walls are all non bearing <br /> wall, 20 lbs dead load. They are sitting on an existing 4 inches concrete slab on grade. <br /> 18. The plan includes an unknown wall with diagonal fill between the dining area and <br /> restrooms. The wall and its construction should be clarified. Provide details as needed. See <br /> IBC Sections 107.2.1 and 1607.14. <br /> RELY: The diagonal wall is interior non bearing wall,for electric fire place screen. <br /> 19. The new office appears to include a doorway and window. A door is not indicated. The <br /> doorway should be accessible. The size and height of the window should be specified. See IBC <br /> Sections 2406.4.2 and 2406.4.3 for safety glazing requirements. An elevation of the wall is <br /> recommended. See IBC Section 107.2.1. <br /> REPLY: The office does not have a door, only 36 inches opening. The window size is 36"x48" <br /> tall with 36"sill height from finish floor. The window size is noted on revised plan sheet A2.0. <br /> Please feel free to contact me at 253-232-5342 if you have any other questions. <br /> Sincerely, <br /> Tzzy Wong <br /> 5 \ 5 <br />