RACK A CONTROLLER
<br />RACK B/C CONTROLLERS
<br />TO RESPECTIVE
<br />BOARD IN RACK
<br />CONTROL PANEL
<br />i
<br />E
<br />F
<br />I
<br />CD'0(Daa �� (D� � EXISTING NEW LEAK I /
<br />molGimommmmem(M V amMmMMmm@Me1Dffl V CONDENSER DETECTION
<br />Mae @190090mmamelmmo Mai VSD'S Pf\i`JEL
<br />000P230MIMM DMID Mmal 11013EIM%l©E OMF9 Mae i
<br />MISS ECIMSOMM 00mm mam
<br />{ 5562�21=1123S flan seel 81250 f0s80
<br />CPC RX-400 CPC RX-400 �
<br />F2 CONTROLLER E2 CONTROLLER \ / 3)
<br />\l (� \1
<br />i
<br />- 4 L a n
<br />tea d ° d n Qa d v ° , J - ° v ° 4 a _ v°4 °
<br />COMPRESSOR AREA.
<br />EXHAUST FANS
<br />INTER! OCKED WITH
<br />AN AC UNIT —�
<br />7
<br />I INE VOLTAGE TO
<br />EXHAUST FAN
<br />J JUNCTION BOX FOR CONTROL TRANSFOMER
<br />\—ELECTRICAL CONTRACTOR TO PROVIDE 3/4"C
<br />FROM THE CONTROL TRANFORMER PANEL TO
<br />A JUNCTION BOX FOR CONNECTIONS TO EMS
<br />SYSTEM. SEE DELI HOOD DETAIL FOR DELI
<br />HOOD CONTROL PANEL.
<br />10
<br />3
<br />TO ENVIROMENTAL CONTROL PANEL.
<br />ENVIRONMENT CONTROL PANEL
<br />'PC BX
<br />CONTROLLER
<br />GENERAL NOTES:
<br />DETAIL 1 IS DI,AGRAiMMATIC IN NATURE AND IS INTENDED TO ``5
<br />CONVEY INSTALLATION REQUIREMENTS
<br />REGARDING THE ENERGY MANAGEMENT CONTROL SYSTEM. THIS
<br />DRAWING IS PICTORIALLY DRAWN FOR
<br />CLARIFICATION PURPOSES ONLY, DO NOT SCALE. THIS DRAWING
<br />IS GENERIC AND NOT ALI_ COMPONENTS
<br />SHOWN ARE REQUIRED FOR INSTALLATION. REFER TO
<br />RESPONSIBILITY CHARTS, DETAIL 1/SHEET EMI, FOR
<br />FINAL EQUIPMENT AND INSTALLATION REQUIREMENTS. REFER TO
<br />OTHEREM SHEETS WHERE THESE DEVICES ARE CALLED OUT TO
<br />BE USED IF ANY.
<br />REFRIGERATION ALARM
<br />ANNUCIATOR PANEL
<br />TYPICAL OF SMAI L 1pll� SDI -
<br />H.V.A.C. UNITS v_s r
<br />TO FNVIRONMENTAL
<br />CONTROL PANEL
<br />TO BX Q
<br />CONTROIER
<br />�9
<br />AKC
<br />TO RESPECTIVE POINTS
<br />ON BOARD INSIDE RTU
<br />CABINET. SEE DETAIL 3
<br />ON EM8.
<br />CPC MULTIPLEX 88AO (VENDOR INSTALLED,
<br />/ NEW; CONTRACTOR INSTALLED, EXISTING)
<br />INSIDE RTU CABINET. SEE DETAIL 3 ON EM8
<br />FOR INPUT CONNECTIONS.
<br />I`\\�_
<br />TO / FROM OTHER RTU
<br />BOARDS AS REQUIRED
<br />DOCK SENSOR DOCK
<br />(S s HFAT EF,
<br />`
<br />- SEE DETAIL 2/EM8 TYPICAL OF UH
<br />1-8,10
<br />I
<br />TO RESPECTIVE BX
<br />POINT 13 -
<br />INPUT
<br />TO RESPECTIVE BX
<br />OUTPUT POINT
<br />(INFO ONLY)
<br />TO ENVIRO
<br />IMENTAL
<br />ALARM
<br />CONTROI IANEI
<br />111
<br />PANEL
<br />� 1�
<br />TO RTU REI AY MODULES
<br />02 FROM DUCT SMOKE DETECTOR(S) 8 8
<br />IRLDS/REFRIGERTION ALARM
<br />STOCK ROOM LTG /
<br />OVERRIDE BUTTON /
<br />v v a d J -,
<br />1 �i ENERGY MANAGMEINT SYSTEM REQUIRMENTS
<br />TO RESPECTIVE P,X
<br />CONTROLLER INPUT
<br />Dn[,\ITC
<br />GENERAL NOTES: KEY NOTES:
<br />1. THE EMS-C SHALL BE RESPONSIBLE FOR THE COMPLETE INSTALLATION OF THE ENERGY O COORDINATE WITH FIRE A RM CONTRACTOR AND KROGER PROJECT MANAGER FOR THE FIRE
<br />AL ARM SYSTEM AND STORE SECURITY ALARMS.
<br />MANAGEMENT SYSTEM (EMS). THIS SHALL INCLUDE, BUT NOT BE LIMITED TO THE START-UP, PUNCHDOWN
<br />AND PROGRAMMING ADJUSTMENT OF THE ENTIRE CPC CONTROL SYSTEM THAT IS LISTED IN EMS-C SCOPE, INCLUDING 0 CONTRACTOR TO COORDINATE REQUIRED DUCT SMOKE DETECTORS AND CONDUCTORS WITH FIRE
<br />HVAC AND LIGHTING CONTROL. ALARM CONTRACTOR/KROGER PROJECT MANAGER.
<br />2. THE EMS-C SHALL PROVIDE ALL COORDINATION BETWEEN THE VARIOUS TRADES, INCLUDING REFRIGERATION, G SEE NETWORK LOOP DIAGRAM SHEET EMI. CONNECT COM LOOP TO CORRECT CONTROLLER
<br />HVAC AND ELECTRICAL TO ENSURE THAT ALL EQUIPMENT IS PROPERLY CONTROLLED AND THAT ALL
<br />CONTROL POINTS HAVE BEEN ACCOMMODATED. THIS SHALL INCLUDE VERIFYING AIL HVAC EQUIPMENT TO VERIFY VOLTAGE. VAIVE SHIPPED LOOSE FROM MANUFACTURE. COORDINATE WITH KROGER
<br />BE CONTROLLED, VERIFYING ALL STAGES OF HEATING, COOLING, HEAT RECLAIM, TWO SPEED FANS, LIGHTING 0 PROJECT MANAGER.
<br />CONTROLS, ETC. AND ENSURING THAT ADEQUATE SENSORS HAVE BEEN SUPPLIED TO ENABLE PROPER
<br />CONTROL OF THE SAME 5 CONTACTOR COILS TO BE 120 VOLT WITH 24 VOLT CONTROL RELAYS.
<br />3. UPON COMPLETION OF THE EMS INSTALLATION, THE EMS-C SHALL PROVIDE ACCURATE AND COMPLETE 06 AS -BUILT DOCUMENTATION TO THE OWNER AND THE ENGINEER. THIS DOCUMENTATION MUST INCLUDE AN SEE DETAIL 5/EM4.
<br />30"X42" PION INDICATING THE LOCATIONS OF ALL OF THE CASE CONTROLLERS PROBES, SENSORS, RELAYS, SEE THE MECHANICAL SCHEDULE FOR FAN AND AC UNIT INTERLOCKS.
<br />REMOTE 1/0 BOARDS, CONTROLLERS, MODEM AND REFRIGERANT LEAK SENSORS FOR THE ENTIRE EMS
<br />INSTAI LATION INCI UDING REFRIGERATION, HVAC AND LIGHTING. THE EMS C SHALL ALSO FURNISH AND 8 PROVIDE AND INSTALL HOSES AND STROBES AS REQUIRED FOR REFRIGERATIONI UNITS. VERIFY
<br />INSTAI L AN 8" X1 I " SHEET WITH COMPLETE PRINTOUT SHOWING TERMINATION POINTS, BOARD LAYOUTS AND INITIAL CONTROL SET WORKING CONDITION OF EXISTING AND REPLACE AS REQUIRED. SEE Dv13 FOR LOCATIONS
<br />POINTS FOR HVAC AND LIGHTING CONTROL. POST EACH SHEET ADJACENT TO EACH REFRIGERATION CONTROLLER OR BUILDING CONTROLLER.
<br />a ONCE THE NEW CONTROL SYSTEM HAS BEEN INSTALLED AND THE HVAC SYSTEMS ARE READY TO BF
<br />BROUGHT ON LINE, THE HVAC-C MUST PROVIDE THE NECESSARY SUPERVISION FOR STARTUP OF THE
<br />CONTROL SYSTEP,jj ^ND COORDINATE START-UP WITH EMS-C. THE HVAC-C MUST ENSURE THAT ALL LEGEND
<br />THE HVAC SYSTEMS ARE OPERATING CORRECTLY AND PROVIDE ANY FINE TUNING OF -THE SYSTEM THAI IS
<br />REQUIRED. - - OEM INSTALLED WIRING
<br />5. DETAIL 1 IS DIAGRAMMATIC IN NATURE AND IS INTENDED TO CONVEY INSTALLATION REQUIREMENTS FIELD INSTALLED WIRING
<br />REGARDING THE ENERGY MANAGEMENT CONTROL SYSTEM. THIS DRAWING IS PICTORIALLY DRAWN FOR — — — -- — EXISTING DEVICE OR WIRING
<br />CLARIFICATION PURPOSES ONLY, DO NOT SCALE, THIS DRAWING IS GENERIC AND NOT ALL COMPONENTS
<br />SHOWN ARE REQUIRED FOR INSTALLATION. REFER TO RESPONSIBILITY CHARTS, DETAIL 1/SHEET EMI, FOR EQUIPMENT NOTE
<br />FINAL EQUIPMENT .AND INSTALLATION REQUIREMENTS. REFER FOR TO FM-3 AND EM-6 WHERE THESE DEVICES — -�
<br />ARE CALLED OUT TO BE USED IF ANY.
<br />REFER TO EMERSON INSTRUCTION MANUALS OR EMEP,SON.COM FOR INFORMATION
<br />6. REFRIGERATION CONTRACTOR SHALL BE RESPONSIBLE FOR ALL REFRIGERATION ISSUES REGARDING REGARDING CPC CONTROL COMPONENTS (I.E. INPUT/OUTPUT BOARDS, ELECTRICAL
<br />REFRIGERATED CASES, EVAPORATOR COILS, REFRIGERATION CONDENSERS, PREP ROOM REFRIGERATION, REQUIREMENTS, ETC.).
<br />COMPRESSOR RACKS AND 'HOT 'WATER RECLAIM. IT SHALL BE THE RESPONSIBILITY OF THE REFRIGERATION RTU'S ARE SHUT DOWN, VIA THE E2 CONTROLLER/EMS PANEL, UPON SIGNAL FROM SMOKE DETECTORS.
<br />CONTRACTOR TO ENSURE A FULLY OPERATIONAL SYSTEM. INCLUDING PROGRAMMING THE MAIN CONTROLLER FOR
<br />CIRCUITS, VERIFY CASE TEMPERATURE, MAKING PROGRAMMING ADJUSTMENT, ADDII"IC DELETING DEFROST SCHEDULE. REFER TO
<br />REFRIGERATION INSTALLATION SPECIFICATIONS 114143 SECTION 3.7(N). SEE DETAIL 1/SHEET EMI FOR IvJORE
<br />INFORMATION REGARDING CONTRACTOR RESPONSIBILITIES.
<br />7. LOW VOLTAGE EMS CONTROL WIRING AND CONNECTIONS BY EMS-C. ALL OTHER HIGH VOLTAGE WIRING
<br />SHALL BE BY THE GENERA CONTRACTORS OR ELECTRICAL CONTRACTOR (UNLESS OTHERWISE NOTED),
<br />8. REFER TO REFRIGERATION LEGENDS FOR INFORMATION REGARDING FIXTURE, WALK-IN COOLER/FREEZERS,
<br />EVAPORATORS, CONDENSERS AND RECLAIM REQUIREMENTS.
<br />; 2 E1IERGY MANAGE- M FFENT GENERAL NOTES SCALE: NONE
<br />TO RESPECTIVE POINTS
<br />ON BOARD INSIDE RTU
<br />TO RESPECTIVE AUX CABINET. SEE DETAIL 9
<br />INPUT POINT IN HVAC CON A I CONTROL BOARD. SEE EMT,
<br />DETAIL 6/EM8 3�
<br />CPC IMULTIFLEX RTU+ (VENDOR INSTALLED,
<br />/-MOUNT ON RTU FACING NEW; CONTRACTOR INSTALLED, EXISTING)
<br />NORTH —� INSIDE RTU CABINET. SEE DETAII 9 ON
<br />EM8.
<br />LLS e A — --
<br />�� HVAC UNIT
<br />LOCATED ABOVE
<br />PHARMACY
<br />TYPICAL OF LARGE
<br />PM SD " 4S IF � 88A0
<br />H. J.A.C. UNITS BOARD
<br />TO /FROM OTHER RTU
<br />BOARDS AS REQUIRED
<br />7� % �� A i K O / I� i / \ / �� 171 1
<br />TO RESPECTIVE RX
<br />CONTROLLER INPUT
<br />POI INTS
<br />]F� _ 2I I e TO REMAINING
<br />SEE DETAIL 1/EM8 RH S ROOFTOP UNITS
<br />2
<br />SEE DETAIL 2/EM8
<br />— - TO CPC SPACE TEMP SENSOR
<br />6 WITH SI ME BAR & WALL
<br />5 ENCLOSURE,
<br />LOCATED IN PHARMACY.
<br />FROM RESPECTIVE
<br />RACK OUTPUT POINTS
<br /><1 10
<br />SS EPR
<br />HS IT
<br />-55
<br />DS
<br />- I WALK-IN FREEZER,/COOLER
<br />EVAPORATOR COIL (EVAPORTATOR
<br />COILS ARE ALSO IN PREP. AREAS) -
<br />IRLDS - WIRING TO
<br />RESPECTIVE CONTROLLER
<br />INPUT POINTS
<br />RIDS - TUBING THE UNIT
<br />LEAK DETECTION UNIT
<br />WALK-IN FREEZER/COOLER
<br />°
<br />TO RESPECTIVE
<br />RACK INPUT POINTS FROM RESPECTIVE
<br />RACK OUTPUT POINTS
<br />TO CONDENSER
<br />CONTROL PANEL
<br />TO CONDENSER
<br />CONTROL PANEL CONDENSER CONTROL
<br />TYPICAL CONDENSER BOARD.
<br />OEM INSTALLED
<br />BOARD.
<br />LIQUID LEVEL SENSOR TQ
<br />CONDENSER CONTROL PANEL
<br />INPUT POINT.
<br />AMBIENT TEMPERATURE TYPICAL
<br />PER CONDENSER. SEE DETAIL
<br />9/EIv14. TO CONDENSER
<br />CONTROL PANEL INPUT POINT. -
<br />DEDICATED RH SENSOR FOR PMAC
<br />SYSTEM. MOUNT IN FROZEN FOOD
<br />REACH -IN AREA. SEE EM6 FOR
<br />I LOCATION.
<br /><5> m
<br />I
<br />TO RESPECTIVE POINTS
<br />ON BOARD AC-1.
<br />THESE �3� BX CONTROL WIRING ARE AN
<br />ENLARGED EXAMPLE OF < > & <�> ON LARGE RTU
<br />TO RESPECTIVE
<br />FROM RESPECTIVE
<br />TO RESPECTIVE
<br />FROM RESPECTIVE
<br />RACK INPUT POINTS
<br />RACK OUTPUT POINTS
<br />RACK
<br />INPUT POINTS
<br />RACK OUTPUT
<br />POINTS
<br />TO EMS PANEL OR
<br />1/0 BOARD.
<br />\ J 3
<br />10
<br />EI-R
<br />SALE FLOOR LTG
<br />REF. CASES
<br />TYPICAI
<br />OVERBID
<br />BUTTON
<br />THAT HAVE
<br />REF RIGERTED
<br />A
<br />IN STOCK
<br />ROOM
<br />HIGHER EVAP.
<br />GLASS DOOR
<br />OVERRIDE
<br />BUTTON
<br />THAN REST OF
<br />FIXTURE
<br />RACK BY AT
<br />I EAST 5' F.
<br />ROUTE TO OTHER CASES ROUTE TO OTHER CASES ROUTE TO OTHER CASES,j
<br />AS INDICATED ON PLANS AS INDICATED ON PLANS AS INDICATED ON PLANS
<br />T-SCALENONE
<br />Portland, OR
<br />503.224.9560
<br />Vancouver, WA
<br />360.695.7879
<br />Seattle, WA
<br />206.749.9993
<br />www.mcknze.corn
<br />MACKENZIE.
<br />DESIGN DRIVEN I CLIENT FOCUSED
<br />Client
<br />FRED MEYER
<br />STORES,
<br />ROAD,
<br />PORTLAND, OR 97202
<br />° # ��NOft
<br />MACKENZIE
<br />2019 ALL RIGHTS RESERVED
<br />THESE DRAWINGS ARE THE PROPERTY OF
<br />MACKENZIE AND ARE NOT TO DE USED
<br />OR REPRODUCED IN ANY MANNER,
<br />WITHOUT PRIOR WRITTEN PERMISSION
<br />Revision Schedule
<br />RevIssue Date
<br />DRAWN BY: GI
<br />CHECKED BY: WC
<br />SHEET
<br />
|