KEY NOTES. <br />1. NEW UNIT WIRED WITH FACTORY INSTALLED CPC CONTROL BOARD. EMS CONTRACTOR TO Architecture ® Interiors <br />COORDINATE WORK WITH OTHER TRADES AND MAKE ALL CONTROL CONNECTIONS AS <br />REQUIRED. EMS-C TO COORDINATE ALL ROOFTOP PENETRATIONS WITH EC. Planning I- Engineering <br />2. NEW THERMOSTAT/SENSOR(S) FOR UNIT, INSTALLED BY CONTROLS CONTRACTOR. <br />3. (E) CPC CONTROL BOARD TO BE REPLACED AS REQUIRED. NEW BOARD SUPPLIED BY KROGER <br />PROJECT MANAGER. RELOCATED THE BOARD FROM FAN COMPARTMENT TO THE ENCLOSURE <br />4. EXITING CPC CONTROL BOARD TO REMAIN, PROVIDE AND INSTALL WEATHER PROOF Portland, O <br />ENCLOSURE, RELOCATED THE BOARD FROM FAN COMPARTMENT TO THE ENCLOSURE 503.224.9560 <br />Vancouver, WA <br />5. LIGHTING CONTACTOR ENCLOSURE, INSTALL AND MODIFY CONTACTORS AS SHOWN ON THE 360.695.7879 <br />PLANS. SEE EM7 PLANS FOR DETAILS TERMINATION OF ALL LOW VOLTAGE WIRING <br />COORDINATE WITH ELECTRICAL CONTACTOR. Seattle, WA <br />206.749.9993 <br />6. NEW TEMPERATURE AND HUMIDITY SENSORS, INSTALLED BY CONTROLS CONTRACTOR. www.mcknze.com <br />r' r 7. NEW RETURN SMOKE <br />DUC E GENERALT TECTOOR PROVID <br />6. ED, WIRED AND TESTED BY CONTROLS CONTRACTOR <br />DESIGN DRIVEN i CLIENT FOCUSED <br />_. - <br />- -- -- -- -- - - - - --- 8 SMOKED CT DETECTOR TO REMAIN, T OPERATION CONNECTION, E <br />- --- I -. --_ GENE Client <br />_ �� -� - �- <br />EXITING U E TES !T OPE A NAND <br />GENERAL NOTE 6. <br />\I �� 9. INPUT/OUTPUT TO BX CONTROLLER. <br />I <br />i <br />10. EXISTING CONTACTOR ENCLOSURE MAKE ALL MODIFICATIONS AS SHOWN ON EM7 PLANS FOR <br />FRED MEYER <br />- 1 - SCHEDULES. <br />11. EXHAUST FAN TO BE INTERLOCKED WITH AC UNIT(S). SEE M6.1.1 FOR SCHEDULE. PROVIDE CT STORES, INC. <br />FOR FAN STATUS TO CONTROL SYSTEM AND PROGRAM TO INTERLOCK AC UNITS AS SHOWN 3800 SE 22 D ROAD, <br />- - ON M6.1.1 PORTLAND, OR 97202 <br />12. PUSH BUTTON FOR LIGHTING OVERRIDE, PULL SEPARATE WIRES FOR PUSH BUTTON TO AC , <br />�. , ; � <br />UNIT BOARD OR EMS PANEL.' �- <br />13. BUILDING CONTROLLER. MODIFY EXISTING PANEL AND ADD ALL NECESSARY 1/0 BOARDS AS <br />SHOWN ON THE PRINTS PER DETAIL EM8. <br />r-- ---- - -- - ---- - - --- ---- --=--- - - ---- ---- -- ---- ---� - - ' 14. 12"x12°'x6" JUNCTION BOX IN BETWEEN GUTTER AND BX PANEL;PROVIDE APPROPRIATELY <br />> s, 's, (,1 � SIZED CHASE NIPPLES TO BX PANEL AND GUTTER (2). EMS-C TO INSTALL NEW TERMINAL <br />6 �_' l'� �) �_.l `" �.-'i �.� �`i <br />v STRIP IN JUNCTION BOX, EMS-C TO LAND ALL LIGHTING LOW VOLTAGE WIRES WIRES AS <br />NECESSARY AND DEMO ALL UNUSED. <br />15. REMOTE BUILDING CONTROL PANEL. PROVIDE NEW ENCLOSURE TO HOUSE TWO BOARDS. <br />RELOCATE EXISTING RELAY BOARD INTO NEW PANEL WITH PROVIDED 88AO BOARD. EXTEND <br />ALL POWER AND NETWORK CONNECTIONS AS REQUIRED. <br />16. EXISTING TEMPERATURE SENSOR AND RELATIVE HUMIDITY SENSOR, REPLACE AS NEEDED Project <br />-- -- 17. EXISTING SENSOR REUSE/REPLACE AS NEEDED <br />MILL CREEK <br />l 18. HAM GLAZING EXHAUST FAN, INSTALL CT TO MONITOR STATUS OF FAN AND INTERLOCK UNIT <br />THAT IS LISTED ON M6.1.1 FOR THIS FAN. PROGRAM THE CONTROLLER TO BRING AC UNIT ON <br />-__ _ -- --- - WHEN FAN IS ON12906 Bothell Everett Hwy <br />--- - - - <br />------ - <br />i; <br />Everett, WA 98208 <br />19. INSTALL NEW COM CABLE BETWEEN UNITS TO MAINTAIN DAISY CHAIN FORMAT. <br />20. SKYLIGHT LIGHT LEVEL SENSOR. SEE DETAILS ON EM8. ROUTE TO BX PANEL. <br />f <br />= 21 EXISTING i CONTROL OL CONDUCTOR TO REMAIN, <br />i I <br />N <br />I I - <br />_ l' _ -..__ - Lam--- - -- <br />I 22. CO2 SENSOR, PULL WIRES TO NEAREST UNIT AS REQUIRED, INSTALL AND VERIFY OPERATION. <br />_ JL j 23. AMBIENT TEMPERATURE SENSORS, PULL WIRES TO EMS PANEL AS REQUIRED AND VERIFY <br />- �I I� <br />_4 -, <br />© �I OPERATION. <br />24. OUTDOOR LIGHT LEVEL SENSOR, PULL WIRES TO EMS PANEL AND VERIFY OPERATION. <br />=- <br />- 25. BUILDING PRESSURE TRANSDUCER,PROVIDE AND INSTALL TRANSDUCER THAT MEASURES <br />--- -- - ---_ li BUILDING PRESSURE IN INW, CONNECT TO BUILDING CONTROLLER INPUT POINT. USE DEVICE <br />THAT IS COMPATIBLE WITH CONTROL SYSTEM. 0-5VDC OUTPUT WITH +0.1 TO -0,1 INW SCALE. <br />26. EXISTING PROGRAMMABLE THERMOSTAT TO REMAIN. <br />27. MASTER LIGHTING OVERRIDE PUSH BUTTON, USE THE BUILT IN PUSH BUTTON WITH ZONE <br />- - SENSOR AND PULL SEPARATE WIRE FOR THE BUTTON TO EMS PANEL. <br />I'I <br />a 28. CONTROL EACH UNIT HEATER SEPARATE, PULL TEMPERATURE SENSOR WIRE AND CONTROL <br />WIRE TO EMS PANEL INPUT/OUPUT BOARD. INSTALL 24V RELAY AT UNIT HEATER AND <br />CONTROL FROM EMS PANEL. <br />29. NEW TEMPERATURE, HUMIDITY AND CO2 SENSOR, INSTALL BY CONTROLS CONTRACTOR, <br />WIRED TO CPC BOARD AT RESPECTIVE UNIT <br />WAIN <br />r �\ - - 30. PUSH BUTTON OVERRIDE PANELS, SUPPLIED & INSTALLED BY CONTROLS CONTRACTOR, WIRE <br />1i TO BUILDING CONTROL PANEL , INC. <br />I 31. 15 CONDUCTOR CABLE(18AWG CONDUCTOR) FROM EACH ELECTRICAL ROOM TO EMS PANEL 19255 SW TETON AVE. <br />TUA OFF 503.691.90027062 <br />\ I <br />FAX 501691.0313 <br />L11 <br />-- - - <br />IGENERAL NOTES. <br />1. MAINTAIN ALL SENSORS AND COMM LOOPS <br />1. COORDINATE ALL ROOF PENETRATIONS WITH EC. ALL ROOF TOP PENETRATIONS TO BE BY <br />1 ELECTRICAL CONTRACTOR. <br />g LIGHT <br />REPLACE EXIS <br />2. CONTRACTOR TO PROVIDE CONDUCTORS AND INSTALL ANY NEW HVAC SENSORS TO CPC BOARDS <br />III AS INDICATED. <br />4ISENSOR WITH OWNER PROVIDED SENSOR <br />it i <br />3. CONTRACTOR TO COORDINATE HVAC INTERLOCK MODIFICATIONS WITH MECHANICAL PLANS AND <br />..MECHANICAL CONTRACTOR. <br />REPLACE SPACE SENSOR IN PRX WITH NEW <br />I'3.4. SEE SHEET EM8 FOR ALL NEW OR REPLACED TEMPERATURE SENSORS. <br />5. CONTRACTOR TO COORDINATE WORK WITH RELATED TRADES. MACKENZIE <br />='- - FOWNER SUPPLIED SENSOR W/ 2019 ALL RIGHTS RESERVED <br />6. DUCT SMOKE DETECTORS WILL BE MONITORED BY THE CONTROLS SYSTEM VIA INPUT BOARD OR THESE DRAWINGS ARE THE PROPERTY OF <br />RTU/RCB INPUT POINT. UNIT SHALL TURN OFF WHEN DETECTOR IS TRIPPED. SEE DETAILS EM8 MACKENZIE AND ARE NOT TO 8E USED <br />III I j <br />OR REPRODUCED IN ANY MANNER, <br />WITHOUT PRIOR WRITTEN PERMISSION <br />I II 7. EMS-C TO ACQUIRE (E)CPC BOARDS FROM DEMO'D RTU'S AND RETURN TO OWNER IN ANTISTATIC <br />MATERIAL. - <br />1 3 <br />8. EMS-C TO DISCONNECT AND REMOVE ALL CONTROL CONDUCTORS ASSOCIATED WITH DEMOTED Revision <br />Schedule <br />HVAC EQUIPMENT. SEE MECHANICAL SCHEDULES FOR A LIST OF REMOVED UNITS. Revision Delta issue Date <br />�I 9. EMS-C RESPONSIBLE FOR THE DISCONNECT AND REMOVAL OF LOW VOLTAGE ITEMS INDICATED AS <br />I <br />DEMOTED OR TO BE BE REMOVED. <br />10. EMS-C RESPONSIBLE TO PROVIDE LABEL ON EACH TEMPERATURE SENSOR INDICATING THE AC UNIT <br />IT SERVES. <br />11. ALL ZONE SENSORS ARE OWNER PROVIDED AND HAVE BUILT IN PUSH BUTTON, USE BUTTON <br />WHERE INDICATED ON THE DRAWINGS. <br />li <br />12. MAINTAIN COM LOOP TO ALL AC UNITS AND E2 CONTROLLER. <br />13 SAVE ALL THERMOSTATS AND PROTECT FROM ANY DAMAGE <br />r f ] <br />�I <br />r <br />- 14. PUSH BUTTON OVERRIDE PANELS, PULL CONTROL WIRES/CABLES FROM EMS CONTROLLER PANEL. <br />SHEET TITLE: <br />CA <br />ENERGY <br />MANAGEMENT <br />I) <br />I I <br />Ll <br />I LIGHTING/HVAC <br />HVAC <br />PLANI <br />! I� <br />NOTE: <br />1. MAINTAIN COM LOOP TO ALL AC UNITS AND E2 <br />o <br />CONTROLLER. <br />2. SAVE ALL THERMOSTATS ARE SAVED FROM ANY <br />--- -- DAMAGE DRAWN BY: GF <br />3. PUSH BUTTON OVERRIDE PANED, PILL CONTROL <br />MIRES/CABLES FROM EMS CONTROLLER PANEL. CHECKED BY: WC <br />SHEET <br />EM6 <br />SCALD: N/A <br />I' LIGH I ING AND HVAC OVERALL Pi AN <br />JOB NO. 2190236.00 <br />