Laserfiche WebLink
TRNYE <br /> Fan Performance <br /> Table 30. Auxiliary electric heat capacity(e) <br /> Total(b) Stagel Stage 2 <br /> Unit Model kW MBh No. of kW MBh kW MBh <br /> Tons Number Input() Output Stages Input Output Input Output <br /> 3 WSC036E3,E4,EW 6.00 20.48 1 6.00 20.48 - - <br /> 3 WSC036E3,E4,EW 12.00 40.97 2 6.00 20.48 6.00 20.48 <br /> 3 WSC036E3,E4,EW 17.40 59.40 2 8.70 29.70 8.70 29.70 <br /> 4 WSC048E3,E4,EW 6.00 20.48 1 6.00 20.48 - - <br /> 4 WSC048E3,E4,EW 12.00 40.97 2 6.00 20.48 6.00 20.48 <br /> 4 WSC048E3,E4,EW 17.40 59.40 2 8.70 29.70 8.70 29.70 <br /> 5 WSC060E3,E4,EW 6.00 20.48 1 6.00 20.48 - - <br /> 5 WSC060E3,E4,EW 12.00 40.97 2 6.00 20.48 6.00 20.48 <br /> 5 WSC060E3,E4,EW 17.40 59.40 2 8.70 29.70 8.70 29.70 <br /> 5 WSC060E3,E4,EW 23.00 78.52 2 8.70 29.70 14.30 48.82 <br /> 6 WSC072E3,4 9 30.73 1 9 30.73 - - <br /> 6 WSC072E3.4,W 18 61.45 1 18 61.45 - - <br /> 6 WSC072E3,4,W 27 92.18 2 18 61.45 9 30.73 <br /> 6 WSC072E3,4,W 36 122.9 2 18 61.45 18 61.45 <br /> 71/2 WSC090E3,4 9 30.73 1 9 30.73 - - <br /> 7Y2 WSC090E3,4,W 18 61.45 1 18 61.45 - - <br /> 71/2 WSC090E3,4,W 27 92.18 2 18 61.45 9 30.73 <br /> 71/2 WSC090E3,4,W 36 122.9 2 18 61.45 18 61.45 <br /> 10 WSC120E3,4,W 18 61.45 1 18 61.45 - - <br /> 10 WSC120E3,4 27 92.18 2 18 61.45 9 30.73 <br /> 10 WSC120E3,4,W 36 122.9 2 18 61.45 18 61.45 <br /> 10 WSC120E3,4,W 54 184.36 2 36 122.9 18 61.45 <br /> (a)600V is not available on high efficiency units. <br /> (b)Heaters are rated at 240V,380V,480V and 600V. For other than rated voltage,CAP= (voltage/rated voltage)z x rated cap. <br /> (c)All input/output does not include indoor fan power or heat. <br /> PKGP-PRC013K-EN 47 <br />