Laserfiche WebLink
TRAME' <br /> Heating Performance Data <br /> Table 34. 3 tons three phase heating capacities(net)WSC036E3,E4,EW at 1200 cfm <br /> Outdoor Integrated Heating Capacity(Btuh/1000) Total Power in Kilowatts at <br /> Temp. at Indicated Indoor Dry Bulb Temp(a) at Indicated Indoor Dry Bulb Temp <br /> F. 60 70 75 80 60 70 75 80 <br /> -8 11.7 11.0 10.5 10.2 2.41 2.68 2.81 2.97 <br /> -3 13.8 13.0 12.6 12.1 2.45 2.72 2.87 3.02 <br /> 2 15.9 15.0 14.7 14.3 2.48 2.75 2.92 3.07 <br /> 7 16.9 15.8 15.3 14.7 2.48 2.76 2.91 3.05 <br /> 12 19.5 18.3 17.8 17.1 2.53 2.81 2.94 3.12 <br /> 17 21.8 20.7 20.1 19.5 2.57 2.85 3.02 3.17 <br /> 22 24.4 23.1 22.6 21.9 2.62 2.90 3.06 3.22 <br /> 27 27.2 26.0 25.3 24.7 2.66 2.96 3.11 3.29 <br /> 32 29.9 28.5 27.8 27.1 2.71 3.01 3.18 3.35 <br /> 37 32.9 31.4 30.7 30.0 2.77 3.08 3.25 3.42 <br /> 42 35.5 34.0 33.2 32.5 2.82 3.14 3.31 3.49 <br /> 47 38.7 37.0 36.2 35.5 2.90 3.21 3.38 3.58 <br /> 52 41.4 39.7 38.8 38.1 2.95 3.27 3.45 3.65 <br /> 57 44.7 42.9 41.9 41.1 3.02 3.35 3.53 3.73 <br /> 62 47.5 45.6 44.6 43.8 3.09 3.42 3.61 3.82 <br /> 67 50.7 48.7 47.8 46.8 3.16 3.51 3.70 3.91 <br /> 72 53.5 51.5 50.5 49.5 3.22 3.59 3.79 3.99 <br /> Notes: <br /> 1. For other airflow conditions,see heating capacity correction factor Table 31,p.48. <br /> 2. Net heating capacity and power input includes indoor fan heat at AHRI esp.To obtain net heating at other conditions,subtract fan heat at this <br /> condition and add fan heat at new condition. <br /> (a)Integrated heating capacities and powers include the effects of defrost in the frost region.All heating capacities and power(kw)are at 70%OD relative <br /> humidity and demand defrost cycle. <br /> PKGP-PRC013K-EN 49 <br />