r <br />• <br /> 4. The lobby is a two-story space that penetrates the 3-hour fire-resistive separation <br /> between construction types as required by Section 510.2 and should be revised. Possible <br /> solutions include: <br /> a. Separate the garage floor from the lobby area with vertical 3-hour, non- <br /> combustible construction, effectively creating a portion of the Type V-A <br /> construction on the garage level and providing for a separation between Type V- <br /> A and Type I-A construction at the garage level. <br /> b. Reclassify the garage as an enclosed parking garage (Section 406.6) and change <br /> the type of construction for the whole building to Type V-A (as long as the <br /> allowable area calculations will allow the revision). Section 506.1 <br /> 5. Elevator #1 and its equipment room and the lobby on the garage level are within the Type <br /> I portion of the building. The interior and exterior walls should be shown as non- <br /> combustible. Section 602.2 <br /> 6. The 2-hour construction on Section AA on Sheet A5.1 references GA File No. WP 3825: <br /> a. This listing is not shown on Sheet RA1.1 <br /> b. The listing is for a wood-framed assembly whereas the wall is in the Type I portion <br /> of the building. <br /> 7. The amount of ventilation provided for the parking garage should be shown on the plans. <br /> Section 406.5.2 <br /> 8. Two-hour roof/ceiling assembly 13/RA1.1 should be keyed into Section A-A, Sheet A5-1 <br /> above the stair enclosures. Section 1023.2 <br /> 9. The following comments are in regards to the mechanical shafts serving the corridors: <br /> a. Smoke/fire dampers should be shown where the ducts exit the shafts. Section <br /> 717.5.3 <br /> b. The supply fans should be shown to automatically shut off upon activation of <br /> corridor smoke detectors spaced at no more than 30 feet on center along the <br /> corridor. Exception 6.3 to Section 1020.5 <br /> Egress <br /> 1. Doors 36 & 37 from the courtyard should be provided with panic hardware. Section <br /> 1010.1.10 <br /> 2. Emergency egress lighting should be provided: <br /> a. Within the garage (Section 1008.3.1). <br /> b. Within the electrical room (Section 108.3.3). <br /> c. At the exterior landings at the exterior exit doorways (Section 1008.3.2, Item 5). <br /> 3. The stairs and landings within the Type I portion of the building should be of <br /> noncombustible construction. Section 1011.7 <br /> Energy <br /> a 3002 Wetmore Ave. 0 425.257.8800 • EPD@everettwa.gov <br /> Everett, WA 98201 425.257.8882 fax everettwa.gov <br />