Laserfiche WebLink
1. The minimum sone rating of 1.0 should be shown for the whole house fans. IMC Section <br /> 403.8.6.5 <br /> 2. The requirements of WSEC C402.5.1.2 for testing of the air barrier should be shown on <br /> the plans. <br /> Structural <br /> 1. On Sheet S2.1 Grid 1/E and Sheet C4.1 in the Civil Drawing set, there is a "Flow Control <br /> Structure" with a rim elevation of 188.50 feet. The top of slab on this sheet is 181'-9". <br /> Please clarify if a site retaining wall is required at this location and if the opening shown <br /> in this area needs to revised or relocated based on the proposed rim elevation of the"Flow <br /> Control Structure". <br /> 2. It appears that the redundancy factor, p, of 1.0, per ASCE 7-10 12.3.4.2, was included in <br /> the design of the lateral systems in either the concrete or the wood portions of the <br /> structure. Please provide supporting calculations to verify that these lateral systems in <br /> both orthogonal directions meet the requirements of p = 1.0. Otherwise, please provide <br /> design calculations and revise the lateral design as required to satisfy the increase due to <br /> the redundancy factor, p =1.3. <br /> 3. Based on the use of the Equivalent Lateral Force procedure in ASCE 7-10 Sec 12.8. Please <br /> provide drift calculations to verify that the Torsional Amplification factor, Ax, does not <br /> need to be increased more than 1.0 per ASCE 7-10 12.8.4.3. <br /> 4. Please provide checks for structural irregularities for both structures concrete and wood <br /> portions per Tables 12.3-1 and 12.3-2 in ASCE 7-10. <br /> 5. Permit calculations for the concrete column design do not appear to include tie design <br /> check requirements per ACI 318-14 Sec 18.14.3. Please provide calculations and revise <br /> tie designs are required. <br /> 6. It appears that concrete dowel designs between PT slab to concrete shear wall elements <br /> are using a (p =0.75 rather than the (p-factor of 0.6 per ACI 318-14 Sec 21.2.4.2 as this <br /> would correspond to the 0.6 factor used in concrete shear wall designs calculations. <br /> Please revise dowel design as required. <br /> In order for the processing of your application to continue, it will be necessary to provide the <br /> Building Division with two new sets of revised construction documents reflecting the corrections <br /> requested. Please include a response letter which indicates how the corrections were resolved. <br /> All codes cited refer to the 2015 International Building Code (IBC), 2015 International Existing <br /> Building Code (IEBC), the 2015 International Fire Code (IFC), the 2015 International Mechanical <br /> Code (IMC), and/or the 2015 Washington State Energy Code (WSEC), as amended by the State <br /> 3002 Wetmore Ave. © 425.257.8800 O EPD@everettwa.gov <br /> Everett, WA 98201 425.257.8882 fax everettwa.gov <br />