Laserfiche WebLink
Drew Martin,Commercial Plans Examiner—Public Services Department <br /> RE:Plan Check#C1802-019— 10725 19th Avenue SE—Correction Notice#2 <br /> October 18,2018 <br /> 'age 3/ <br /> g. The original comment recommended providing reinforcement per ACI 318-14 Section <br /> 10.7.6.1.6. The response appears to indicate that the reinforcement is not needed due to the <br /> anchor bolts extending to the footing. The intent of the reinforcement is to provide <br /> confinement at the point of load transfer and prevent localized failure of the concrete. Detail <br /> 12/S4.2 does not clearly indicate if additional shear anchorage will be provided, or if the <br /> tension anchors will also provide the shear load path into the walls. The load path should be <br /> clarified. The minimum number of supplemental anchors should be specified. The needed <br /> for confinement reinforcement should be reviewed. <br /> Reinforcement is called out on detail 12/S4.2 for the raised stemwall.It requires#4 at 10"o.c. <br /> each way. The detail has been updated to visually show this. <br /> 18. This comment has not been completely addressed. The manufacturer's literature indicates that a <br /> minimum of(26) 8d nails are required for each end length for Hem-Fir framing. Detail 10/S4.0 <br /> only specifies(15) 8d nails. Verify the required nailing for the straps. See IBC Section 107.2.1. <br /> The 26(8d) nails are required for the entire strap and only 13(8d) nails are required for each <br /> end per note 2 below the table on page 305 of the Simpson catalogue. So the 15(8d) nails <br /> shown on our drawings are adequate. <br /> 19. This comment has not been completely addressed. The original comment stated that additional <br /> holdowns are required. The response states that additional holdowns are not required straps <br /> providing shear transfer around the wall openings. It appears that the walls may be designed by <br /> the Force Transfer method per SDPWS-15 Section 4.3.5.2. Calculations substantiating the design <br /> should be submitted for review. See IBC Sections 1604.4 and 2306.1. <br /> See attached force transfer method calculation for these shear walls on sheet S-10. <br /> 21. This comment has not been completely addressed. The tension forces used in the holdown design <br /> on pages C-31 through C-42 are not consistent with the forces determined on pages C-17 and C- <br /> 27. Calculations clarifying the design values should be submitted for review. The calculations <br /> should address the following: <br /> a. The shear wall calculations on pages C-9 through C-17 and C-19 through C-27 appear to <br /> evaluate the walls using wind loads. The calculations appear to reference seismic criteria, <br /> though it is unclear if the seismic loads are also being evaluated. Note that it appears from <br /> other portions of the calculations that the seismic loads partially control the design. Verify <br /> that both wind and seismic loads are considered in the shear wall calculations. <br /> b. The holdown tables are noted as providing ASD-values. However,the tables appear to <br /> reference factored load combinations from IBC Section 1605.2. Verify that factored <br /> combinations have been used, and that the load combinations are not factoring load <br /> components that have been previously reduced for use in ASD load combinations(i.e.,all <br /> unfactored load components should be nomimal values). <br /> c. The load combinations shall include vertical seismic effects and overstrength per ASCE 7-10 <br /> Sections 12.4.2.2 and 12.4.3.2 Equation 7. Overstrength is required per ACI 318-14 Section <br /> 17.2.3.4.3. The overstrength factor shall be applied to the earthquake component only, not <br /> the net uplift force after removing resistance due to gravity loading. <br />