• <br /> {Company Mr., Ms.) First Last Name <br /> Plan Check Number: Number, First Review <br /> Month Day, Year <br /> 22.The holdown forces for the two-foot shear walls on the south elevation of the building do not <br /> appear to include cumulative loads from above. See page C-27 of the structural calculation. <br /> The calculations should be reviewed and revised as needed. See IBC Section 1604.4. <br /> 23. Detail 3/S4.2 includes the floor diaphragm connection to the shear wall. The detail does not <br /> appear to meet the requirement of IBC Section 706.2. The detail should be revised to allow <br /> collapse of the structure on either side of the wall system without causing collapse of the entire <br /> structure. <br /> 24. Detail 3/S4.2 includes the roof diaphragm connection to the shear wall. <br /> a) The detail does not appear to meet the requirement of IBC Section 706.2. The detail <br /> should be revised to allow collapse of the structure on either side of the wall system <br /> without causing collapse of the entire structure. <br /> b) The detail requires the lower roof diaphragm to connect to the shear wall through rim joist <br /> and nailing to the backside of the wall studs. This is not a substantiate load path to the <br /> shear wall. The load path should be revised to provide a system per AWC SDPWS-15 <br /> Section 4.2. See IBC Section 2306.1. <br /> c) The roof system appears to require an overhang at the upper level similar to Detail 6/S4.3. <br /> The detail should be revised to incorporate this feature. See IBC Section 107.2.1. <br /> 25.The balloon framing on the east wall of the structure is laterally anchored to the building at the <br /> third floor per Sheet S2.3. Calculations substantiating the load path and the framing capacities <br /> shall be submitted for review. Note that the beams dragging the wall load terminate at the <br /> first interior wall line. The drag framing must extend past this wall into the diaphragm beyond. <br /> The length of the drag framing shall be such that the drag load superimposed on the <br /> diaphragm shear does not exceed the diaphragm capacity. The diaphragm sheathing shall not <br /> be assumed to act in tension to drag the load past the interior wall and into the diaphragm <br /> beyond. See IBC Sections 1604.1 and 1604.4. <br /> Miscellaneous: <br /> 26. Sheet A5.1 states that stair framing shall be provided in the structural drawings. The stair <br /> design does not appear to be provided in the structural drawings. The drawings should be <br /> revised and revised as needed. Calculations substantiating the design of the stairway shall be <br /> submitted for review. See IBC Sections 1603.1 and 1604.1. <br /> cage5of5 <br /> CITY OF EVERETT • 3200 Cedar Street • Everett, WA 98201 • (425) 257-8810 • Fax(425) 257-88 <br />