Laserfiche WebLink
17. Grab bars are required in the bathrooms per IRC Section R330.8. Details for the grab bars should <br /> be included in the drawings. Blocking should be provided in the walls capable of resisting a 200- <br /> pound load per IRC Table R301.5. <br /> 18. Each sleeping room should be classified per IRC Section R330.3 <br /> In order for the processing of your application to continue, it will be necessary to provide the Building <br /> Division with two new sets of revised construction documents reflecting the corrections requested. <br /> Please include a response letter which indicates how the corrections were resolved. <br /> These initial comments are general in nature and based on preliminary information.Additional <br /> comments will typically be generated once a complete submission is reviewed. All comments are based <br /> on the 2018 International Building Code (IBC), 2018 International Residential Code (IRC),and/or the <br /> 2018 Washington State Residential Energy Code (WSEC), as amended by the State of Washington and <br /> adopted by the City of Everett. <br /> These comments address building issues only.Additional revisions or additions may be required by other <br /> departments(such as Utilities,Traffic,Planning or Fire). All required submittals must be of sufficient detail <br /> and information to ensure that the proposed structure will be constructed in compliance with all adopted <br /> codes. <br /> Sincerely, <br /> Ryan Hammer <br /> Residential Plans Examiner <br /> 425-257-7299 <br /> 0o 3200 Cedar Street © 425.257.8810 O rhammer@everettwa.gov <br /> �/ Everett,WA 98201 425.257.8857 fax everettwa.gov <br />