Laserfiche WebLink
ID TYPICAL INITIAL CONDUCTOR FINAL CONDUCTOR CONDUCTOR CONDUIT #OF CURRENT-CARRYING CONDUIT OCPD EGC TEMP.CORR. CONDUIT CONT. MAX. BASE DERATED TERM. LENGTH VOTAGE <br /> LOCATION LOCATION PARALLEL CONDUCTORS IN FILL FACTOR FILL CURRENT CURRENT AMP. AMP. TEMP. DROP <br /> CIRCUITS CIRCUIT PERCENT FACTOR RATING <br /> 1 3 ARRAY JUNCTION BOX 12 AWG Q CABLE COPPER - 1 2 N/A N/A 6 AWG BARE COPPER 0.82 (48°C) N/A 15.73A 19.66A N/A N/A 75°C 57FT 0.76% Lumio s <br /> SMART ENERGY TODAY <br /> 2 1 JUNCTION BOX IQ COMBINER BOX 10 AWG THWN 2 COPPER MIN 0.75'DIA 3 6 31.71% 20A 6 AWG THWN-2 1 (26°C) 0.8 15.73A 19.66A 40A 32.00A 75°C 45FT 0.76% (SET) <br /> EMT COPPER 1550 DIGITAL DR,LEHI,UT <br /> 3 1 IQ COMBINER BOX FUSED AC 6 AWG THWN 2 COPPER MIN 0.75'DIA 1 3 36.77% 60A 6 AWG THWN-2 1 (26°C) 1 42.35A 52.94A 75A 75.00A 75°C 5FT 0.09% 84043,USA <br /> DISCONNECT EMT COPPER <br /> 4 1 FUSED AC MSP 6 AWG THWN 2 1 COPPER MIN 0.75'DIA 1 3 36.77% N/A 6 AWG THWN-2 1 (26°C) 1 42.35A 52.94A 75A 75.00A 75°C 5FT 0.09% <br /> DISCONNECT SCH 40 PVC COPPER <br /> SING. EQUIPMENTS MAX CURRENT OCPD <br /> NO OF MICROINVERTERS IN A STRING X OUTPUT SYSTEM INFO <br /> IQ COMBINER <br /> 1 CURRENT OF MICROINVERTERS X 1.25=MAX 13X1.21X1.25=19.7A 20A (35)Q CELLS <br /> BOX __ CURRENT _ (40OW) <br /> Q.PEAK DUO BILK + <br /> FUSED AC TOTAL NO. OF MICROINVERTERS X OUTPUT (35)ENPHASE <br /> 2 DISCONNECT CURRENT OF MICROINVERTER X 1.25=MAX 35X1.21X1.25=52.9A 60A IQ8PLUS-72-2-US(240V) <br /> CURRENT TO UTILITY GRID DC SYSTEM SIZE:14.000 kWDC <br /> BRANCHIAC SYSTEM SIZE:10.500 kWAC <br /> 13- Q CELL Q.PEAK DUO BLK ML-G10+ (400W) MODULES L' 'IN <br /> rr BI-DIRECTIONAL UTILITY <br /> 1-PH,3-W, 120V/240V <br /> POINT OF - REVISIONS <br /> INTERCONNECTION DESCRIPTION DATE REV <br /> (E)MAIN BREAKER TO <br /> SUPPLY SIDE TAP `� REVISION 12/16/2022 A <br /> PRODUCTION CTSI <br /> HOUSE 240 V.200A/2P <br /> JUNCTION BOX � __ <br /> 600 V, NEMA 3R, 2 GATEWAY (E)MAIN SERVICE <br /> ti ti O CABLE I i KNIFE SWITCH a �Ll <br /> UL LISTED 1 t_ "R0°1G1OM1 PANEL,200A RATED. PROJECT NAME&ADDRESS <br /> AC DISCONNECT: L2 L2 1-PH,3-W,240V <br /> 1 F7171 2r)A/2P 15A/2P 240V.60A FUSED �� Ll <br /> L1 NEMA u 3R, UL LISTED Q <br /> II ( (2)60A FUSES <br /> BRANCH 2 �, 20AQP �+ , r a :L+ L+ <br /> 0 �2 <br /> 12- Q CELL Q.PEAK DUO BLK ML-G10+ (400W) MODULES L220Ai2Pj N N 1- <br /> 6 6 <br /> f O O <br /> NO <br /> • • • a a ` � 3 4 c cn < o <br /> - p uJ o <br /> --- - (N) ENPHASE IQ Z I j <br /> COMBINER 4C BOX WIRELESS COM KIT W lY c+) <br /> - - - m 0 W Lo <br /> (X-I0-AM1-240-4C) EXISTING GROUND LU <br /> � ELECTRODE CONDUCTOR Z W W p <br /> Q J <br /> 2 <br /> � Z <br /> BRANCH3 o a <br /> 10- Q CELL Q.PEAK DUO BLK ML-G10+ (400W) MODULES U <br /> N <br /> O <br /> Lo <br /> N <br /> DATE: 12/16/2022 <br /> � -- <br /> UTILITY PROVIDER: SNOPUD SHEET NAME <br /> SERVICE INFO ELECTRICAL <br /> LINE & CALCS. <br /> AHJ NAME: CITY OF EVERETT SHEET SIZE <br /> MAIN SERVICE VOLTAGE: 240V ANSI B <br /> (35)ENPHASE IQ8PLUS 72 2 US(240V)MICROINVERTERS MAIN SERVICE PANEL: 200 A 11" X 17" <br /> MAIN BREAKER RATING: 200 A <br /> MAIN SERVICE LOCATION: SOUTH SHEET NUMBER <br /> SERVICE FEED SOURCE: OVERHEAD PV-7 <br /> SCALE: NTS <br />