1.) LOWEST EXPECTED AMBIENT TEMPERATURE <br /> BASED ON ASHRAE MINIMUM MEAN EXTREME <br /> DRY BULB TEMPERATURE FOR ASHRAE LOCATION <br /> MOST SIMILAR TO INSTALLATION LOCATON. <br /> LOWEST EXPECTED AMBINETTEMP: -17°C <br /> 2.) HIGHEST CONTINUOUS AMBIENT <br /> TEMPERATURE BASED ON ASHRATE HIGHEST <br /> MONTH 2%DRY BULB TEMPERATURE FOR <br /> ASHRAE LOCATION MOST SIMILAR TO <br /> INSTALLATION LOCATION. HIGHEST CONTINUOUS <br /> TEMPERATURE: 28.4°C <br /> 3.) 2013 ASHRAE FUNDEMENTALS 2%DESIGN <br /> TEMPERATURES DO NOT EXCEED 47°C IN THE <br /> UNITED STATES. FOR LESS THAN 9 CURRENT- <br /> CARRYING CONDUCTORS IN ROOF-MOUNTED <br /> SUNLIT CONDUIT AT LEAST 7/8"ABOVE ROOF <br /> AND USING THE OUTDOOR DESIGN <br /> TEMPERATURE OF 47°C OR LESS(ALL OF UNITED <br /> STATES) <br /> a.) 12AWG, 90°C CONDUCTORS ARE GENERALLY <br /> ACCEPTABLE FOR MODULES WITH Isc OF <br /> 7.68AMPS OR LESS WHEN PROTECTED BY A <br /> 12AMP OR SMALLER FUSE. <br /> b.) 10AWG, 90°C CONDUCTORS ARE GENERALLY <br /> ACCEPTABLE FOR MODULES WITH Isc OF <br /> 9.6AMPS OR LESS WHEN PROTECTED BY A 15- <br /> AMP OR SMALLER FUSE. <br /> _ One-Line Standard Electrical Diagram for SYSTEM SIZE AE JOB NO. DWG NO REVISION <br /> ' . Small-Scale Single-Phase PV System 6.48kW 22-10359-R E1.2 1 Drawn By: Chivy Chun <br /> 969 S Nebraska St � 9 y <br /> ARTISAN Seattle, WA 98108 Site Name: Ciera Cox Photovoltaic System <br /> 206-557-4215 Site Address: 4319 Crescent Ave Everett, WA 98203 Scale: NTS Sheet 2 Date: 2/16/2023 Checked By: <br /> System AC Size: 6.48kW Solar Array <br />