Laserfiche WebLink
Test and Balance Report <br /> H <br /> VAC <br /> ACP <br /> Date: 05/06/2023 Time: 17:45Hrs <br /> Site Information <br /> Address: 1130 SF Fyerett Mall Way <br /> Address: <br /> City Fyerett <br /> State WA Zip A8208 <br /> Construction Type ❑ New ❑ Existing ❑ Commercial ❑ Residential <br /> Testing Technician: Rnrlrign Ramirez Test Mode: E] Heating ElCooling <br /> Testing Method: ❑ Flow Hood ❑Traverse(Anemometer) ❑Traverse(Pitot Tube) ❑ Velocity/Grille Ak <br /> Test Instrument Brand: Alnnr Model: 6700F Date Calibrated: 05/02/2023 <br /> Test Instrument Serial Number: 801750 Air Temperature: 67 Altitude: A2ft/25m <br /> Room/ Duct Terminal Location Design Airflow Test 1 Final Test 2 Final Test 3 Final % Design <br /> 1 RTU-7 Supply Air 220 243 239 234 100.3% <br /> 2 RTU-7 Supply Air 225 256 246 232 100.3% <br /> 3 RTU-7 Supply Air 200 168 181 195 99.9% <br /> 4 RTU-7 Supply Air 50 102 84 65 100.1% <br /> 5 RTU-7 Supply Air 250 274 269 258 100.2% <br /> 6 RTU-7 Supply Air 250 218 236 241 99.8% <br /> 7 RTU-7 Supply Air 150 147 147 147 99.9% <br /> 8 RTU-7 Supply Air 250 286 279 272 100.6% <br /> 9 RTU-7 Supply Air 250 224 236 243 99.8% <br /> 10 RTU-7 Supply Air 170 149 154 161 99.6% <br /> 11 RTU-7 Supply Air 170 165 168 168 99.90 <br /> 12 RTU-7 Return Air 200 238 223 216 100.3% <br /> 13 <br /> 0 <br /> 14 <br /> 15 <br /> % <br /> 16 <br /> 0 <br /> 17 <br /> 0 <br /> 18 RTLI-7 Return Air 200 246 238 2?1 10 1 <br /> 0 <br /> 19 <br /> 0 <br /> 20 <br /> 0 <br /> 21 <br /> 22 <br /> 23 <br />