Laserfiche WebLink
Test and Balance Report <br /> H <br /> VAC <br /> ACP <br /> Date: 05/06/2023 Time: 17:001-1rs <br /> Site Information <br /> Address: 1130 SF FvPrPtt Mall Way <br /> Address: <br /> City Everett <br /> State WA Zip A8208 <br /> Construction Type ❑ New ❑ Existing ❑ Commercial ❑ Residential <br /> Testing Technician: Rnrlrign Ramirez Test Mode: E] Heating ElCooling <br /> Testing Method: ❑ Flow Hood ❑Traverse(Anemometer) ❑Traverse(Pitot Tube) ❑ Velocity/Grille Ak <br /> Test Instrument Brand: Alnnr Model: 6700F Date Calibrated: 05/02/2023 <br /> Test Instrument Serial Number: 801750 Air Temperature: 67 Altitude: A2ft/25m <br /> Room/ Duct Terminal Location Design Airflow Test 1 Final Test 2 Final Test 3 Final % Design <br /> 1 DOSA-1 Supply Air 500 476 483 489 99.3% <br /> 2 DOSA-1 Supply Air 500 520 517 509 100.3% <br /> 3 DOSA-1 Supply Air 500 483 489 492 99.8% <br /> 4 DOSA-1 Supply Air 500 462 476 481 98.9% <br /> 5 DOSA-1 Supply AiR 500 536 524 519 100.6 <br /> 6 DOSA-1 Supply AiR 500 477 481 486 99.0% <br /> 7 DOSA-1 Supply Air 500 518 503 503 100.1% <br /> 8 DOSA— Supply Air 500 524 521 513 100.4% <br /> 9 DOSA-1 Supply Air 500 581 586 594 99.8% <br /> 10 DOSA-1 Exhaust Air 450 475 462 458 100.1% <br /> 11 DOSA-1 Exhaust Air 450 453 453 453 100.1% <br /> 12 DOSA-1 Exhaust Air 450 426 432 439 99.0% <br /> 13 <br /> 0 <br /> 14 0 <br /> 15 r)nqA-1 Exhaust Air 450 474 468 461 <br /> 0 <br /> 16 Dnl;A-1 Exhaust Air 490 4q1 486 474 100. <br /> 0 <br /> 17 <br /> 0 <br /> 18 DOSA-1 Fxhaij.,;t Air 490 445 447 447 99 0 <br /> 19 D—A-1 Exhaust Air 450 471 466 45q 100.3 <br /> 20 <br /> 21 <br /> 22 <br /> 23 <br />