Laserfiche WebLink
7. On Sheet 2,the vertical post sizes appear to be missing from the plan views. Please update <br /> drawings and provide supporting structural calculations verifying the member adequacy and <br /> connection hardware. IRC R106.1.1, IBC 1604. <br /> 8. Please identify deck concrete footing sizes as this may mor may not be similar to the <br /> proposed footing for the post located in the garage area. Please update drawings as <br /> required. IRC R106.1.1. <br /> 9. Please identify roof ventilation details proposed as this appears to be missing from the plans. <br /> IRC R806 and its subsections. <br /> 10. Please identify attic access location on the roof framing plans as this appears to be missing <br /> from the plans. IRC R807.1. <br /> RESUBMITTAL REQUIREMENTS <br /> In order for the processing of your application to continue,it will be necessary to provide the Building <br /> Division with the following items: <br /> ❑ (2) New,complete sets of revised construction documents reflecting the corrections as <br /> required. <br /> ❑ (1) Response letter detailing how the corrections were resolved. <br /> All codes cited refer to the 2018 International Residential Code(IRC), 2018 International Building Code <br /> (IBC), 2018 International Existing Building Code (IEBC),the 2018 International Fire Code (IFC),the 2018 <br /> International Mechanical Code (IMC),and/or the 2018 Washington State Energy Code(WSEC), as <br /> amended by the State of Washington and adopted by the City of Everett. The current IBC referenced <br /> standard for accessible design is the 2009"Accessible and Usable Buildings and Facilities" (ICC/ANSI <br /> A117.1). Federal ADA regulations and standards may be more restrictive. <br /> These comments address building issues only.Additional revisions or additions may be required by <br /> other departments (such as Utilities,Traffic, Planning or Fire). All required submittals must be of <br /> sufficient detail and information to ensure that the proposed structure will be constructed in <br /> compliance with all adopted codes. <br /> Sincerely, <br /> mes Bronder, PE,SE <br /> Associate Engineer <br /> Plans Examiner <br /> Page 2 of 2 <br />