b2 structural D/ ( LIIen ineers <br /> info@b2engineers.com <br /> 425-318-7047 (0) JUL 15 ��20 <br /> 425-318-0031 (C) <br /> CITyoFE\E <br /> Permit rer RETT <br /> SEAMAR EVERETT ADDITION v!ces <br /> 1920 100TH SE, EVERETT, WA 98208 <br /> RESPONSE TO COMMENTS <br /> PROJECT NO: 20055 DATE:06-04-20 <br /> PREPARED BY: BASRI BASRI PE,SE <br /> RESPONSE TO COMMENTS <br /> 1.The"Concrete and Reinforcing"section of the General Notes and Specifications on Sheet S-0 <br /> specifies strengths of 2,500 psi for all concrete elements. The exterior foundation walls appear <br /> to be exposed to freeze-thaw conditions and water, and qualify as Class F2 concrete per ACI <br /> 318-14 Table 19.3.1.1. Per ACI 318-14 Table 19.3.2.1, the minimum concrete strengths for <br /> Class F2 concrete is 4,500 psi. The minimum concrete strength for exposed concrete should be <br /> revised as required. See IBC Section 1901.2. <br /> RE: PLEASE SEE UPDATED "CONCRETE AND REINFORCING" SECTION OF THE GENERAL NOTES ON <br /> S-0. CONCRETE STRENGTH OF THE FOUNDATION WALL AND FOOTING HAS BEEN MODIFIED TO <br /> 4,500 PSI. <br /> 2.The"Dimensional Lumber"section of the General Notes and Specifications on Sheet S-0 <br /> specifies the wall stud species as Hem-Fir. The capacities in the shear wall schedule in Detail <br /> 7/S-2 and the structural calculations appear to be based on Douglas-Fir. The notes should be <br /> revised. See IBC Section 2307.1 and AWC SDPWS-15 Table 4.3A Footnote 3. <br /> RE: PLEASE SEE UPDATED "DIMENSIONAL LUMBER" SECTION OF THE GENERAL NOTES ON S-0. <br /> SPECIFIES THE WALL STUD SPECIES HAS BEEN MODIFIED TO DOUGLAS-FIR. <br /> 3. Detail 2/S-2 shows the wood-framed wall located adjacent to exposed earth. The framing and <br /> sheathing should be located at least 8 inches above grade. Alternatively,the wood-framed wall <br /> should be constructed of preservative-treated or naturally-durable wood. See IBC Section <br /> 2304.12.1.2. <br /> RE: PLEASE SEE UPDATED DETAIL 2/S-2. 8" MIN CLEARANCE HAS BEEN ADDED TO DETAIL. <br /> Foundation System: <br /> 4.The foundation wall in Detail 2/S-2 specifies soil preparation per the notes on Sheet S-1. The <br /> "Foundation"section in the General Notes and Specifications on Sheet S-0 indicates that a <br /> geotechnical report has not been prepared. The detail should be revised to specify the soil <br /> preparation requirements. See IBC Sections 107.2.1 and 1804. <br /> RE: PLEASE SEE UPDATED DETAIL 2/S-2. SOIL PREPARATION NOTE HAS BEEN ADDED. <br /> Gravity System: <br /> 5.The project includes a two-hour fire wall per the First Floor Plan on Sheet A2.03. The structure <br /> is required to be designed and detailed to allow collapse of the structure on each. The design <br /> does not appear to satisfy this requirement. Notable issues include, but are not limited to,the <br /> continuous north and south shear walls through the fire wall, and the north-south oriented truss <br /> spanning over the firewall. The structural design should be revised. See IBC Section 706.2. <br /> RE: THE STRUCTURAL DESIGN HAS BEEN REVISED. PLEASE RESPONSE TO COMMENT#6 TO 9 <br />