Laserfiche WebLink
BOOTH SUPPLY FAN (S <br />REFER TO DRAWING M310 FOR CONTROL DIAGRAM ASSOCIATED WITH THESE <br />GUIDELINES AND SPECIFICATIONS. ALSO REFER TO SPECIFICATION SECTION <br />15975 FOR ADDITIONAL REQUIREMENTS. <br />HEATING AND VENTILATING EQUIPMENT ASSOCIATED WITH THIS BOOTH SHALL <br />BE CONTROLLED BY A PROGRAMMABLE LOGIC CONTROLLER (PLC). CONTROL <br />DECISIONS SHALL BE MADE AT THE PLC BASED ON INPUT SIGNALS RECEIVED B <br />FROM SENSORS LOCATED IN THE SYSTEM. OUTPUT SIGNALS FROM THE PLC <br />SHALL ENERGIZE, DEENERGIZE OR MODULATE CONTROLLED DEVICES TO <br />MAINTAIN PROGRAMMED SET POINTS OR CONDITIONS. ANALOG AND DIGITAL <br />INPUT AND OUTPUT SIGNALS SHALL BE UTILIZED BY THE CONTROLLER. <br />DIGITAL INPUT OR OUTPUT SIGNALS SHALL BE USED FOR TWO POSITION <br />CONTROL MODES. ANALOG INPUT OR OUTPUT SIGNALS SHALL BE USED FOR ALL <br />OTHER CONTROL MODES. <br />EQUIPMENT OPERATIONAL STATUS SHALL BE INDICATED AT THE PLC AS <br />SENSED BY CURRENT RELAYS (XM) AT EACH MOTOR AS INDICATED ON THE <br />CONTROL DIAGRAM. <br />RUN LIGHTS (XI) SHALL BE PROVIDED ADJACENT TO THE OPERATIONAL MODE <br />PUSHBUTTONS AT THE OPERATORS CONTROL PANEL AS SHOWN ON THE CONTROL <br />DIAGRAM TO INDICATE THE MODE OF OPERATION THE SYSTEM IS OPERATING <br />IN. RUN LIGHTS SHALL BE RED. <br />BOOTH EXHAUST FAN (EF) <br />GENERAL: <br />EACH VERTICAL PAINT BOOTH HAS TWO EXHAUST FANS (EF). THE CONTROL <br />DIAGRAM AND THE FOLLOWING SEQUENCE DESCRIBE OPERATIONS FOR ONLY ONE <br />FAN SYSTEM, BUT ARE TYPICAL FOR BOTH UNLESS OTHERWISE NOTED. <br />THE EF SHALL BE EITHER MANUALLY OR AUTOMATICALLY STARTED THROUGH <br />THE H-O-A SWITCH (HS-2XX01) LOCATED AT THE MOTOR CONTROL CENTER. <br />MANUAL ACTIVATION SHALL OCCUR IN THE HAND POSITION. AUTOMATIC <br />ACTIVATION SHALL OCCUR THROUGH THE PLC WHEN THE H-O-A SWITCH IS <br />POSITIONED IN THE AUTO POSITION. THE SWITCH SHOULD NORMALLY BE <br />POSITIONED IN THE AUTO POSITION. <br />WHEN THE EF IS EITHER MANUALLY OR AUTOMATICALLY STARTED, THE <br />SOLENOID VALVES ON THE PLANT COMPRESSED AIR LINES SERVING THE FANS <br />AUTOMATIC DAMPER (SnV-2XX01) AND THE BOOTH SPRAY GUN (SnV-OXXO1 AND <br />OXXO2) SHALL BE ENERGIZED. WHEN ENERGIZED, THESE VALVES SHALL ALLOW <br />90 PSIG AIR TO THE AUTOMATIC AIR DAMPER AND THE BOOTH DISTRIBUTION <br />SYSTEM SERVING THE SPRAY GUN AIR OUTLETS. THE 90 PSIG AIR SHALL <br />OPEN THE NORMALLY CLOSED (N.C.) AUTOMATIC AIR DAMPER. WHEN THE EF <br />IS DEACTIVATED FOR ANY REASON THE SOLENOID VALVES SHALL BE <br />DEENERGIZED, ALLOWING PLANT AIR TO BLEED OFF THE SYSTEMS. THIS <br />SHALL DEACTIVATE THE SPRAY GUNS AND ALLOW THE AUTOMATIC DAMPER TO <br />RETURN TO ITS FAIL SAFE (NORMAL) POSITION. <br />AIR FLOW CONTROL: <br />THE EF VARIABLE FREQUENCY DRIVE (VFD) SHALL CONTROL EXHAUST SYSTEM <br />AIR FLOW BASED ON PREDETERMINED AIR FLOW SETTINGS (SEE DRAWING M3) <br />IN RESPONSE TO PLC COMMANDS. THE CONTROL SYSTEM INSTALLER AND THE <br />HVAC BALANCING CONTRACTOR SHALL WORK TOGETHER TO ESTABLISH THESE <br />SET POINTS AS REQUIRED TO OBTAIN THE VARIOUS AIR FLOWS DESCRIBED <br />BELOW UNDER OPERATIONAL MODES A, B, AND C. THESE SET POINTS SHALL <br />BE DISPLAYED AND SHALL BE ADJUSTABLE FROM THE PLC STATION. ACCESS <br />TO CHANGE THESE SET POINTS SHALL BE PASSWORD PROTECTED. CONTROL OF <br />EACH OF THE THREE MODES SHALL BE AT THE LOCAL CONTROL STATION AND <br />SHALL BE REMOTELY INDICATED AT THE PLC STATION. <br />ON A CHANGE IN AIR FLOW (OPERATIONAL MODE CHANGE), THE PLC SHALL <br />RAMP -UP THE FAN VARIABLE FREQUENCY DRIVE. THE RAMP -UP DURATION FROM <br />NO -FLOW TO FULL -FLOW SHALL BE IN EQUAL INCREMENTS FOR A 90 SECOND <br />TIME PERIOD (ADJUSTABLE). THE SAME STEPS ESTABLISHED FOR THE NO - <br />FLOW TO FULL -FLOW RAMP -UP SHALL BE USED FOR RAMP -UP FROM ANY AIR <br />FLOW MODE TO A HIGHER AIR FLOW MODE. <br />WHEN THE SYSTEM IS OPERATING IN THE MANUAL MODE OF CONTROL (HAND <br />POSITION AT THE H-O-A SWITCH), THE FAN SHALL NOT BE UNDER CONTROL <br />OF THE PLC AND AIR FLOW SHALL FAIL TO THE FULL FLOW (OPERATIONAL <br />MODE B) SETTING. <br />FAN SAFETY CONTROLS: <br />WHEN THE EF IS OPERATING IN EITHER THE MANUAL OR AUTOMATIC MODE AND <br />SMOKE IS DETECTED BY THE DUCT SMOKE DETECTOR (AS-2XX01), THE <br />EXHAUST FAN SHALL BE DEENERGIZED AND CONTROLLED COMPONENTS SHALL <br />RETURN TO THEIR FAIL SAFE POSITIONS. SMOKE DETECTOR ALARMS, AS WITH <br />OTHER SUMMARY ALARMS, SHALL BE REGISTERED AT THE EVERETT DISPATCH <br />CENTER THROUGH THE EXISTING FACILITY ENERGY MANAGEMENT SYSTEM <br />STATION. SUMMARY ALARMS SHALL BE ENTERED IN ONE OF THE LOCAL 40-51 <br />'EXCEL' PANELS FOR FORWARDING TO THE EXISTING FACILITY ENERGY <br />MANAGEMENT SYSTEM. UPON RECEIPT OF A MALFUNCTION, DISPATCH SHALL <br />NOTIFY THE COGNIZANT MAINTENANCE SUPERVISOR, WHO WILL, IN TURN, <br />SEND THE APPROPRIATE MAINTENANCE PERSON WHO WILL DETERMINE THE <br />EXACT NATURE OF THE SYSTEM MALFUNCTION AT THE 40-51 PLC STATION. <br />INDIVIDUAL SYSTEM STATUS AND ALARMS SHALL BE REGISTERED AND <br />DISPLAYED AT THE PLC STATION. <br />WHEN THE EXHAUST FAN IS DEENERGIZED FOR ANY REASON, THE ASSOCIATED <br />BOOTH SUPPLY FAN (SF) SHALL BE <br />DEENERGIZED AND THEIR ASSOCIATED CONTROL COMPONENTS SHALL RETURN TO <br />THEIR FAIL SAFE POSITIONS. <br />IF EXHAUST AIR FLOW IS NOT PROVEN BY PRESSURE DIFFERENTIAL <br />TRANSMITTER (PdT-2XX01), THE EXHAUST FAN MOTOR SHALL BE DEENERGIZED <br />WHICH SHALL DEENERGIZE THE SOLENOID VALVES (SnV-OXX01 AND OXXO2) <br />SERVING THE PAINT BOOTH SPRAY GUNS AND (SnV-2XX01) SERVING THE <br />N.C.-AAD. THIS ALARM CONDITION SHALL BE INDICATED AT THE EXISTING <br />FACILITY ENERGY MANAGEMENT SYSTEM. <br />FILTER BANK: <br />PRESSURE DROP ACROSS THE FILTER BANK SHALL BE MONITORED AT THE <br />LOCAL PRESSURE DIFFERENTIAL INDICATOR TRANSMITTER (PdIT-2XXO1) <br />LOCATED ON THE BOOTH CONTROL PANEL. WHEN THE DIFFERENTIAL PRESSURE <br />ACROSS THE FILTERS EXCEEDS THE FILTER CHANGE OUT SET POINT, THIS <br />INFORMATION SHALL BE REGISTERED AT THE EVERETT DISPATCH CENTER <br />THROUGH THE FACILITY ENERGY MANAGEMENT SYSTEM STATION. SUMMARY <br />ALARMS SHALL BE ENTERED IN ONE OF THE LOCAL 40-51 'EXCEL' PANELS <br />FOR FORWARDING TO THE FACILITY ENERGY MANAGEMENT SYSTEM. UPON <br />RECEIPT OF A MALFUNCTION, DISPATCH SHALL NOTIFY THE COGNIZANT <br />MAINTENANCE SUPERVISOR, WHO WILL, IN TURN, SEND THE APPROPRIATE <br />MAINTENANCE PERSON WHO WILL DETERMINE THE EXACT NATURE OF THE <br />SYSTEM MALFUNCTION AT THE 40-51 PLC STATION. INDIVIDUAL SYSTEM <br />STATUS AND ALARMS SHALL BE REGISTERED AND DISPLAYED AT THE PLC <br />STATION. <br />ACCESS TO CHANGE THE FILTER DIFFERENTIAL PRESSURE DESIGN SET POINT <br />SHALL BE PASSWORD PROTECTED SO AS TO BE ACCESSIBLE TO HVAC <br />MAINTENANCE PERSONNEL ONLY. <br />EACH VERTICAL PAINT BOOTH HAS TWO SETS OF TWO SUPPLY FANS (SF) <br />EACH. THE CONTROL DIAGRAM AND THE FOLLOWING SEQUENCE DESCRIBE <br />OPERATIONS FOR ONLY ONE FAN SYSTEM BUT, ARE TYPICAL FOR BOTH UNLESS <br />OTHERWISE NOTED. <br />THE SF SHALL BE EITHER MANUALLY OR AUTOMATICALLY STARTED THROUGH <br />THE H-O-A SWITCH (HS-5XX01) LOCATED AT THE MOTOR CONTROL CENTER. <br />MANUAL ACTIVATION SHALL OCCUR IN THE HAND POSITION. AUTOMATIC <br />ACTIVATION SHALL OCCUR THROUGH THE PLC WHEN THE H-O-A SWITCH IS <br />POSITIONED IN THE AUTO POSITION. THE SWITCH SHOULD NORMALLY BE <br />POSITIONED IN THE AUTO POSITION. <br />WHEN THE SF IS EITHER MANUALLY OR AUTOMATICALLY STARTED, THE 3-WAY <br />SOLENOID VALVES ON THE PLANT COMPRESSED AIR LINE SERVING THE FAN'S <br />AUTOMATIC DAMPER (SnV-5XX01), THE PREHEAT COIL'S FACE & BY-PASS <br />DAMPER (SnV-3XX02), AND ON THE INSTRUMENT AIR LINE SERVING THE <br />VARIOUS SYSTEM CONTROL VALVES (SnV-3XX01) SHALL BE ENERGIZED. WHEN <br />ENERGIZED, THESE VALVES SHALL ALLOW 90 PSIG AIR TO THE AUTOMATIC <br />AIR DAMPER AND THE I/P SERVING THE FACE & BY-PASS DAMPER (I/P- <br />3XX03) AND 20 PSIG INSTRUMENT AIR TO THE I/P SERVING EACH CONTROL <br />VALVE(I/P-3XX01 , 3XX02 AND 7XX01). THE 90 PSIG AIR SHALL OPEN THE <br />NORMALLY CLOSED (N.C.) AUTOMATIC AIR DAMPER. WHEN THE SF IS <br />DEACTIVATED FOR ANY REASON THE SOLENOID VALVES SHALL BE <br />DEENERGIZED, ALLOWING PLANT AND INSTRUMENT AIR TO BLEED OFF THE <br />SYSTEMS. THIS SHALL ALLOW THE AUTOMATIC AIR DAMPER, FACE & BY-PASS <br />DAMPER, AND THE CONTROL VALVES TO RETURN TO THEIR FAIL SAFE <br />(NORMAL) POSITIONS. <br />AIR FLOW CONTROL: <br />THE SF VARIABLE FREQUENCY DRIVE (VFD) SHALL CONTROL SUPPLY SYSTEM <br />AIR FLOW BASED ON PREDETERMINED AIR FLOW SETTINGS (SEE DRAWING M3) <br />IN RESPONSE TO PLC COMMANDS. THE CONTROL SYSTEM INSTALLER AND THE <br />HVAC BALANCING CONTRACTOR SHALL WORK TOGETHER TO ESTABLISH THESE <br />SET POINTS AS REQUIRED TO OBTAIN THE VARIOUS AIR FLOWS DESCRIBED <br />BELOW UNDER OPERATIONAL MODES A, B, AND C. THESE SET POINTS SHALL <br />BE DISPLAYED AND SHALL BE ADJUSTABLE FROM THE PLC STATION. ACCESS <br />TO CHANGE THESE SET POINTS SHALL BE PASSWORD PROTECTED. CONTROL OF <br />EACH OF THE THREE MODES SHALL BE AT THE LOCAL CONTROL STATION AND <br />SHALL BE REMOTELY INDICATED AT THE PLC STATION. THE AIR FLOW TO <br />THE BOOTH SHALL BE REDUCED BELOW THE PREDETERMINED QUANTITIES BY <br />THE PLC UPON INDICATION OF EXCESSIVE POSITIVE STATIC PRESSURE <br />INSIDE THE BOOTH AS INDICATED BY THE DIFFERENTIAL PRESSURE <br />INDICATING TRANSMITTER (PdIT-5XX02) INSTALLED ACROSS THE VERTICAL <br />PAINT BOOTH WALL. <br />ON A CHANGE IN AIR FLOW (OPERATINAL MODE CHANGE), THE PLC SHALL <br />RAMP -UP THE FAN VARIABLE FREQUENCY DRIVE. THE RAMP -UP DURATION FROM <br />NO -FLOW TO FULL -FLOW SHALL BE IN EQUAL INCREMENTS FOR A 90 SECOND <br />TIME PERIOD (ADJUSTABLE). THE SAME STEPS ESTABLISHED FOR THE NO - <br />FLOW TO FULL -FLOW RAMP -UP SHALL BE USED FOR RAMP -UP FROM ANY AIR <br />FLOW MODE TO A HIGHER AIR FLOW MODE. <br />WHEN THE SYSTEM IS OPERATING IN THE MANUAL MODE OF OPERATION (HAND <br />POSITION AT THE H-O-A SWITCH), THE FAN SHALL NOT BE UNDER CONTROL <br />OF THE PLC AND AIR FLOW SHALL FAIL TO THE FULL FLOW (OPERATIONAL <br />MODE B) SETTING. B <br />PREHEAT CONTROL: <br />STEAM FLOW TO THE PRE OIL SHALL BE CONTROLLED BY NORMALLY <br />CLOSED (N.C.), TEMPERATURE CONTROL VALVE (TCV-3XX01). <br />THE PLC SHAL LOCK OPEN HE TCV WHEN THE OUTSIDE AIR TEMPERATURE <br />DROPS BELOW ETPOINT TEMPERATURE AS SENSED BY OUTSIDE AIR <br />TEMPERATURE TRANSMITTER (TT-3XX03). <br />ACCESS TO CHANGE THE PREHEAT CONTROL SET POINTS SHALL BE PASSWORD <br />PROTECTED SO AS TO BE ACCESSIB TO HVAC MAINTENANCE PERSONNEL <br />ONLY. B <br />HEATING CONTROL (1/3 VALVE IR TAGE): B <br />STEAM FLOW RATE T STAGE HEATING SHALL BE CONTROLLED BY <br />NORMALLY CLOSED (N.C.) TEMPERATURE CONTROL VALVE (TCV-3XX02). THE <br />PLC SHALL OD T THE TCV TO MAINTAIN HE SP C ESIGN SET P T <br />P RE S NS A T S - X <br />WHEN TEMPERATURE CONTROL VALVE (TCV-3XXO2) HAS REACHED THE FULL OPEN <br />POSITION AND THE SPACE DESIGN SET POINT IS NOT SATISFIED, THE PLC SHALL <br />CLOSE TEMPERATURE CONTROL VALVE (TCV-3XX02) AND OPEN TEMPERATURE <br />CONTROL VALVE . TCV-3XX03 <br />( ) <br />ACCESS TO CHANGE THE HEATING CONTROL (FIRST STAGE) SET POINTS SHALL <br />BE PASSWORD PROTECTED SO AS E ACCESSIBLE TO HVAC MAINTENANCE <br />PERSONNEL ONLY. B <br />HEATING CONTROL Q23ZVALVEqE STAGE): <br />STEAM FLOW RATE OND STAGE HEATING SHALL BE CONTROLLED BY <br />NORMALLY CLOSED (N.C.) TEMPERATURE CONTROL VALVE (TCV-3XX03). THE B <br />PLC SHALL MODULATE THE TCV TO MAINTAIN THE SPACE DESIGN SET POINT <br />WHEN TEMPERATURE CONTROL VALVE (TCV-3XXO3) HAS REACHED THE FULL OPEN <br />POSITION AND THE SPACE DESIGN SET POINT IS NOT SATISFIED, THE PLC SHALL <br />OPEN TEMPERATURE CONTROL VALVE (TCV-3XX02). r <br />THE HIGH TEMPERATURE TRANSMITTER (TT-3XX02) LOCATED DOWNSTREAM OF <br />THE HEATING COIL SHALL PREVENT OVER HEATING OF THE SUPPLY AIR <br />STREAM. WHEN EXCESSIVE TEMPERATURE IS SENSED, THE PLC SHALL REDUCE <br />STEAM FLOW TO THE HEATING COIL AS REQUIRED TO MAINTAIN TT-3XX02 <br />HIGH TEMPERATURE SET POINT. ONCE THE SPACE TRANSMITTER DEMAND DROPS <br />BELOW THE DUCT TRANSMITTER, THE SPACE TRANSMITTER SIGNAL SHALL BE <br />USED BY THE PLC TO RESUME CONTROL. <br />ACCESS TO CHANGE THE HEATING CONTROL (SECOND STAGE) SET POINTS <br />SHALL BE PASSWORD PROTECTED SO AS TO BE ACCESSIBLE TO HVAC <br />MAINTENANCE PERSONNEL ONLY. <br />FAN SAFETY CONTROLS: <br />WHEN THE SF IS OPERATING IN EITHER THE MANUAL OR AUTOMATIC MODE AND <br />SMOKE IS DETECTED BY THE DUCT SMOKE DETECTOR (AS-5XX01), THE SUPPLY <br />FAN SHALL BE DEENERGIZED AND ASSOCIATED CONTROL COMPONENTS SHALL <br />RETURN TO THEIR FAIL SAFE POSITIONS. SMOKE DETECTOR ALARMS, AS WITH <br />OTHER SUMMARY ALARMS, SHALL BE REGISTERED AT THE EVERETT DISPATCH <br />CENTER THROUGH THE EXISTING FACILITY ENERGY MANAGEMENT SYSTEM <br />STATION. SUMMARY ALARMS SHALL BE ENTERED IN ONE OF THE LOCAL 40-51 <br />'EXCEL' PANELS FOR FORWARDING TO THE EXISTING FACILITY ENERGY <br />MANAGEMENT SYSTEM. UPON RECEIPT OF A MALFUNCTION, DISPATCH SHALL <br />NOTIFY THE COGNIZANT MAINTENANCE SUPERVISOR, WHO WILL, IN TURN, <br />SEND THE APPROPRIATE MAINTENANCE PERSON WHO WILL DETERMINE THE <br />EXACT NATURE OF THE SYSTEM MALFUNCTION AT THE 40-51 PLC STATION. <br />INDIVIDUAL SYSTEM STATUS AND ALARMS SHALL BE REGISTERED AND <br />DISPLAYED AT THE PLC STATION. <br />WHEN THE LOW LIMIT TEMPERATURE SENSOR (TSL-5XX01) SENSES A LEAVING <br />HEATING COIL TEMPERATURE OF 40 DEGREES F, THE SUPPLY FAN SHALL BE <br />DEENERGIZED AND CONTROLLED COMPONENTS SHALL RETURN TO THEIR FAIL <br />SAFE (NORMAL) POSITIONS. THE PLC SHALL INDICATE SYSTEM SHUTDOWN AT <br />THE EXISTING FACILITY ENERGY MANAGEMENT SYSTEM. <br />WHEN THE SUPPLY FAN IS DEENERGIZED FOR ANY REASON THE ASSOCIATED <br />BOOTH EXHAUST FAN (EF) SHALL BE <br />DEENERGIZED AND THEIR CONTROLLED COMPONENTS SHALL RETURN TO THEIR <br />FAIL SAFE (NORMAL) POSITIONS. <br />IF SUPPLY AIR FLOW IS NOT PROVEN BY PRESSURE DIFFERENTIAL <br />TRANSMITTER (PdT-5XX01), THE SUPPLY FAN MOTOR SHALL BE DEENERGIZED <br />WHICH SHALL DEENERGIZE THE ASSOCIATED EXHAUST FAN AND THE SOLENOID <br />VALVE (SnV-OXXO1) SERVING THE PAINT BOOTH SPRAY GUN. THIS CONDITION <br />SHALL BE INDICATED AT THE EXISTING FACILITY ENERGY MANAGEMENT <br />SYSTEM. <br />FILTER BANK: <br />PRESSURE DROP ACROSS THE FILTER BANK SHALL BE MONITORED AT THE <br />LOCAL PRESSURE DIFFERENTIAL INDICATOR TRANSMITTER (PdIT-5XXO1) <br />LOCATED ON THE BOOTH CONTROL PANEL. WHEN THE DIFFERENTIAL PRESSURE <br />ACROSS THE FILTERS EXCEEDS THE FILTER CHANGE OUT SET POINT, THIS <br />INFORMATION SHALL BE REGISTERED AT THE EVERETT DISPATCH CENTER <br />THROUGH THE FACILITY ENERGY MANAGEMENT SYSTEM STATION. SUMMARY <br />ALARMS SHALL BE ENTERED IN ONE OF THE LOCAL 40-51 'EXCEL' PANELS <br />FOR FORWARDING TO THE FACILITY ENERGY MANAGEMENT SYSTEM. UPON <br />RECEIPT OF A MALFUNCTION, DISPATCH SHALL NOTIFY THE COGNIZANT <br />MAINTENANCE SUPERVISOR, WHO WILL, IN TURN, SEND THE APPROPRIATE <br />MAINTENANCE PERSON WHO WILL DETERMINE THE EXACT NATURE OF THE <br />SYSTEM MALFUNCTION AT THE 40-51 PLC STATION. INDIVIDUAL SYSTEM <br />STATUS AND ALARMS SHALL BE REGISTERED AND DISPLAYED AT THE PLC <br />STATI 0 N . <br />ACCESS TO CHANGE THE FILTER DIFFERENTIAL PRESSURE DESIGN SET POINT <br />SHALL BE PASSWORD PROTECTED SO AS TO BE ACCESSIBLE TO HVAC <br />MAINTENANCE PERSONNEL ONLY. <br />OPERATIONAL MODE A - WING PREPARATION <br />WHEN OPERATIONAL MODE A PUSH BUTTON (HS-OXX02) IS SELECTED AND THE <br />HOA'S ARE IN THE AUTO POSITIONS, THE PLC SHALL AUTOMATICALLY <br />ACTIVATE THE BOOTH EXHAUST FANS (EF), SUPPLY FANS (SF), <br />SEQUENCE OF OPERATION FOR EACH OF THE <br />SELECTED SYSTEMS SHALL BE AS PREVIOUSLY DESCRIBED WITH THE <br />FOLLOWING MODE SPECIFIC REQUIREMENTS.BOOTH EXHAUST FANS (EF) SHALL <br />OPERATE IN THE 25,000 CFM (EACH) SETTING.BOOTH SUPPLY FANS (SF) <br />SHALL OPERATE IN THE 25,000 CFM (PER SET OF 2) SETTING. TWO STAGE <br />HEATING SHALL BE ACTIVATED. PREHEAT HEATING SHALL NORMALLY BE <br />DEACTIVATED (UNLESS OUTDOOR TEMPERATURE IS 36 DEGREES F OR LOWER). <br />OPERATIONAL MODE B - PAINTING <br />WHEN OPERATIONAL MODE B PUSH BUTTON (HS-OXX03) IS SELECTED AND THE <br />HOA'S ARE IN THE AUTO POSITIONS, THE PLC SHALL AUTOMATICALLY <br />ACTIVATE THE BOOTH EXHAUST FANS (EF), SUPPLY FANS (SF), <br />SEQUENCE OF OPERATION FOR EACH OF THE SELECTED SYSTEMS SHALL BE AS <br />PREVIOUSLY DESCRIBED WITH THE FOLLOWING MODE SPECIFIC REQUIREMENTS. <br />BOOTH EXHAUST FANS (EF) SHALL OPERATE IN THE 64,000 CFM (EACH) <br />SETTING. <br />BOOTH SUPPLY FANS (SF) SHALL OPERATE IN THE 64,000 CFM (PER SET OF <br />2) SETTING. TWO STAGE HEATING SHALL BE ACTIVATED. PREHEAT HEATING <br />SHALL NORMALLY BE DEACTIVATED (UNLESS OUTDOOR TEMPERATURE IS 36 <br />DEGREES F OR LOWER). <br />OPERATIONAL MODE C - CURE <br />WHEN OPERATIONAL MODE C PUSH BUTTON (HS-OXX04) IS SELECTED AND THE <br />HOA'S ARE IN THE AUTO POSITIONS, THE PLC SHALL AUTOMATICALLY <br />ACTIVATE THE BOOTH EXHAUST FANS (EF), SUPPLY FANS (SF). <br />SEQUENCE OF OPERATION FOR EACH OF THE SELECTED SYSTEMS SHALL BE AS <br />PREVIOUSLY DESCRIBED WITH THE FOLLOWING MODE -SPECIFIC REQUIREMENTS. <br />THERE ARE FOUR PHASES WITHIN THIS OPERATING MODE: PURGE, RAMP -UP, STEADY <br />STATE, AND RAMP -DOWN. THE PHASES ARE PROGRESSIVE BASED UPON AN <br />ADJUSTABLE TIME SCHEDULE. IN ALL PHASES OF MODE C, THE PREHEAT <br />FUNCTION SHALL BE ACTIVE. <br />PROFESSIONAL STAMP & SIGNATURE <br />APPLIES TO WORK WITHIN THE CLOUDED <br />REVISION AREAS ONLY AS INDICATED <br />pfKENGINEERS <br />Seattle H Spokane H Baltimore <br />DUE TO THE EXPANSION OF THE SUPPLY AIR FLOW RESULTING FROM HEATING <br />THE DIFFERENTIAL PRESSURE INDICATING <br />TRANSMITTER (PdIT-5XXO2) MOUNTED ACROSS THE BOOTH WALL SHALL <br />MONITOR THE RELATIVE PRESSURIZATION OF THE BOOTH. THE PLC SHALL <br />CONTROL THE PRESSURIZATION UTILIZING THE SUPPLY FAN VFD'S. <br />PURGE PHASE: BEFORE ANY TEMPERATURE RAMP -UP OCCUR, THE <br />BOOTH SHALL BE VENTILATED FOR 10 MINUTES. <br />RAMP -UP PHASE: THE RAMP -UP PHASE CONSISTS OF A DRY BULB TEMPERATURE <br />RAMP -UP FOR THE RAMP -UP PHASE, THE FOLLOWING REQUIREMENTS APPLY. <br />BOOTH EXHAUST FANS (EF) SHALL OPERATE IN THE 25,000 CFM (EACH) SETTING. <br />BOOTH SUPPLY FANS (SF) SHALL OPERATE IN THE 25,000 CFM (PER SET OF <br />2) SETTING. BOTH STAGES OF HEATING CONTROL SHALL BE ACTIVATED. <br />PREHEAT CONTROL SHALL BE ACTIVATED. DURING THE DRY BULB TEMPERATURE <br />RAMP -UP, THE TEMPERATURE OF THE BOOTH SHALL BE ELEVATED FROM THE <br />MODE B TEMPERATURE TO 120 DEGREES F OVER A PERIOD OF 40 MINUTES. <br />STEADY STATE PHASE: AFTER THE RAMP -UP PERIOD IS OVER AND SPACE CURE <br />TEMPERATURE STABILIZE, THE PLC SHALL CONTROL <br />THE OPERATION OF ALL SUPPLY AND EXHAUST SYSTEM COMPONENTS TO <br />MAINTAIN THE CURE MODE TEMPERATURE IN THE BOOTH FOR <br />THE SELECTED PERIOD OF TIME. <br />RAMP -DOWN PHASE: AFTER THE END OF THE CURE HOLD PERIOD, THE RAMP - <br />DOWN PHASE SHALL BE INITIATED. DURING THE RAMP -DOWN PHASE, <br />THE DRY BULB <br />TEMPERATURE SHALL BE REDUCED FROM 120 DEGREES F TO THE INDOOR <br />AMBIENT TEMPERATURE OVER A PERIOD OF 40 MINUTES. <br />VERTICAL PAINT BOOTH LID AND DOOR CONTROL <br />THE BOOTH CLOSURE LID AND HORIZONTAL SLIDING DOOR CONTROLS WILL BE <br />PROVIDED BY THE VERTICAL PAINT BOOTH SUPPLIER. OPERATIONAL MODES A, <br />B AND C SHALL NOT BE ALLOWED TO OPERATE UNTIL A SIGNAL IS RECEIVED <br />FROM THE WING PREPARATION AND PAINT CONTROL PLC, SUPPLIED BY THE <br />BOOTH VENDOR, INDICATING THE LID AND SLIDING DOORS ARE COMPLETELY <br />CLOSED. <br />THE PREVIOUSLY MENTIONED WING PREPARATION AND PAINT CONTROL PLC <br />WILL NOT ALLOW WING PREPARATION ACTIVITIES OR PAINTING ACTIVITIES <br />TO BEGIN UNTIL THE LID AND SLIDING DOORS ARE COMPLETELY CLOSED AND <br />THE APPROPRIATE OPERATIONAL MODE IS PROVEN. PROVIDE A SIGNAL TO THE <br />WING PREP AND PAINT CONTROL PLC INDICATING THE SYSTEMS ARE <br />OPERATING IN THE APPROPRIATE OPERATIONAL MODE. <br />THE CONTROL SYSTEM SUPPLIER AND THE VERTICAL PAINT BOOTH SUPPLIER <br />SHALL WORK TOGETHER TO COORDINATE INTERFACE REQUIREMENTS BETWEEN <br />THE WING PREPARATION AND PAINT CONTROL PLC AND THE HVAC SYSTEM <br />CONTROL PLC. <br />ERAIR:Z01a114 '<ciaolUZ•PiTlEdT/aaIIII_11INIE011040 11RA■RAIR:1IIN11540111110 Imto] 0Ia� <br />WHEN THE <br />EMERGENCY SHUTDOWN SWITCH <br />(HS-OXXO1, <br />BREAK GLASS TYPE) IS <br />SELECTED, <br />THE PLC SHALL AUTOMATICALLY <br />OVERRIDE ALL <br />OTHER MODES OF <br />OPERATION <br />AND DEACTIVATE THE BOOTH EXHAUST FANS <br />(EF), SUPPLY FANS <br />(SF). <br />WHEN THESE SYSTEMS ARE <br />DEACTIVATED THEIR ASSOCIATED CONTROL COMPONENTS <br />(AUTOMATIC AIR <br />DAMPERS, <br />TEMPERATURE CONTROL VALVES, <br />ETC.) SHALL <br />RETURN TO THEIR <br />FAIL SAFE <br />(NORMAL) POSITIONS. <br />Urr IVIVUC — DUUIF] VLN I IL/11 IUIN JI JI LIVI <br />WHEN THE OFF MODE PUSH BUTTON HS-OXXO5) IS SELECTED AND THE HOA'S <br />ARE IN THE AUTO POSITIONS, THE PLC SHALL AUTOMATICALLY DEACTIVATE <br />THE BOOTH EXHAUST FANS (EF), SUPPLY FANS (SF), <br />WHEN THESE SYSTEMS ARE DEACTIVATED THEIR ASSOCIATED <br />CONTROL COMPONENTS (AUTOMATIC AIR DAMPERS, TEMPERATURE CONTROL <br />VALVES, ETC.) SHALL RETURN TO THEIR FAIL SAFE (NORMAL) POSITIONS. <br />EQUIPMENT START-UP PRIORITY <br />THE START-UP SEQUENCE FOR EQUIPMENT ASSOCIATED WITH THIS BOOTH <br />SHALL BE AS LISTED IN THE START-UP PRIORITY LIST THAT FOLLOWS. ONCE <br />A COMMAND IS ISSUED TO INITIATE A PARTICULAR OPERATIONAL MODE, THE <br />FIRST SYSTEM SHALL BE ENERGIZED. THE SUBSEQUENT SYSTEMS SHALL BE <br />SEQUENTIALLY ENERGIZED AS LISTED IN THE START-UP PRIORITY LIST WITH <br />A MINIMUM 5 SECOND TIME DELAY (ADJUSTABLE) BETWEEN EACH GROUPING OF <br />EQUIPMENT FOR THAT PARTICULAR OPERATIONAL MODE. ALL AUTOMATIC <br />SHUTDOWN SAFETIES SHALL BE OVERRIDDEN FOR 90 SECONDS (ADJUSTABLE) <br />TO ALLOW THE SYSTEM TO STABILIZE. <br />START-UP PRIORITY LIST: <br />1 - BOOTH EXHAUST FANS (EF). BOTH CAN START SIMULTANEOUSLY. <br />2 - BOOTH SUPPLY FANS (SF). BOTH SETS CAN START SIMULTANEOUSLY. <br />ISSUED FOR CONSTRUCTION <br />DESIGN BY FSi <br />DATE 06.27.2022 <br />SYM <br />REVISION <br />BY <br />APPROVED <br />DATE <br />SYM <br />REVISION <br />BY <br />APPROVED <br />DATE <br />® <br />BOE//VO <br />�� wA0. q� <br />1:s� <br />y <br />,p9 x <br />? <br />fS6/ST1ONAL�ENG\�� <br />°&" �°'� <br />sM <br />THIS DESIGN AND/OR <br />SPECIFICATION IS APPROVED <br />DRAWN <br />CTOLLIVER <br />DAEACCEPTABILITY <br />6T19-92 <br />SUBTITLE VERTICAL PAINT BOOTH <br />SYST. GUIDELINES & SPECS. <br />CURRENT REVISION <br />W5523782 <br />SYMBOL <br />B <br />DATE <br />06.27.2022 <br />RECORD DWG. — LOCKWOOD GREENE <br />03/94 <br />CHECKED <br />R. RODEMS <br />8-92 <br />SHEET <br />M 310a <br />A <br />767 VERTICAL PAINT BOOTH VENTILATION W5523782 <br />FSi <br />KMC <br />06.18.2021 <br />ENGINEER <br />ENGINE KWISH <br />6-19-92 <br />TITLE <br />767 VERTICAL PAINT BOOTH VENTILATION - PHASE 2 <br />BUILDING 40-051 <br />MECHANICAL MASTER COL. EVERETT, WA <br />APPROVED BY <br />DEPT. <br />DATE <br />B <br />767 VERTICAL PAINT BOOTH VENTILATION — PHASE 2W5523782 <br />FSi <br />KMC <br />06.27.2022 <br />CHECKED <br />D.ROBY <br />8-19-92 <br />JOB NO. <br />94049.01/31329.04 <br />COMP No. <br />APPROVED <br />J.S HOPKINS <br />9-11-92 <br />APPROVED <br />LRCROTZER <br />9-11-92 <br />DWG No. 40-051-M310a <br />