Laserfiche WebLink
• • <br /> 1. Not required for ADU <br /> : The ceiling construction and minimum ceiling height should be specified. <br /> 1. Ceiling construction and height noted on sections. <br /> 71'.. <br /> The exterior wall detail on Sheet A2.00 should provide minimum R-21 insulation. <br /> 1. Revised <br /> 13. The interior wall detail on Sheet A2.00 should provide top and bottom connections. The <br /> top connections should fasten directly to framing, not through the GWB. Details for <br /> blocking should be provided where the walls are parallel to and between top framing. <br /> 1. Details provided for interior wall connections. Notes added for walls running <br /> parallel with truss members. <br /> . The laundry units are separated from the bathroom by doors and include a separate <br /> exhaust fan. <br /> 1. revised <br /> 5')Landing are required at all exterior doors. A/o 46470 .74 SAM", <br /> 1. Landings confirmed to comply with R311.3.1 as requested. <br /> Section 7.0 "Energy Code" on Sheet G1.00 specifies a maximum thermal rating of <br /> U=0.33 for the windows. The value should not exceed 0.3. <br /> 1. revised <br /> Detail 4/A3.00 specifies R-19 insulation. This should be R-38. <br /> 1. revised <br /> 8 Sheet A3.00 appears to indicate new roofing for the new AFH. This should be indicated <br /> in the Roof Plan on this sheet. <br /> 1. No work proposed at primary residence. No new roofing proposed in this <br /> project. Existing roofing to remain. <br /> 111 Page 4 of 4 <br />