My WebLink
|
Help
|
About
|
Sign Out
Home
Browse
Search
1726 63RD ST SE 2023-06-23
>
Address Records
>
63RD ST SE
>
1726
>
1726 63RD ST SE 2023-06-23
Metadata
Thumbnails
Annotations
Entry Properties
Last modified
6/23/2023 4:37:34 PM
Creation date
6/23/2023 4:37:08 PM
Metadata
Fields
Template:
Address Document
Street Name
63RD ST SE
Street Number
1726
Imported From Microfiche
No
There are no annotations on this page.
Document management portal powered by Laserfiche WebLink 9 © 1998-2015
Laserfiche.
All rights reserved.
/
24
PDF
Print
Pages to print
Enter page numbers and/or page ranges separated by commas. For example, 1,3,5-12.
After downloading, print the document using a PDF reader (e.g. Adobe Reader).
View images
View plain text
• * <br /> Continuing from the previous comment, it is unclear if beams located above the garage are being <br /> replaced/new or are existing to remain. Structural calculations should include the design of the 5 1/8 x <br /> 16.5 Glulam floor beams (20'-0" and 16'-0" spans) located above the garage if these beams are new. <br /> Additional plan notes and wall key have been added to define areas of work. <br /> 6. See Sheet S-1 and S-2. Structural calculations should show the existing footing is adequate for the <br /> rallel wall girder truss located next to the laundry room. See revised structural calculations <br /> 7 Structural calculations should include calculations showing the deck footings are adequate. See <br /> evised structural calculations - 301/0 re,e tw (3u...t ()LAM CAW, Ot.T C-0 v4"0 <br /> ((See FORTE Calculations page 4, deck beam total length measured from outside to outside is 14'- <br /> 6" but plans show a total out-to-out length of around 15'-6". Plan dimensions have been corrected. <br /> 9. Plans should provide typical structural framing/connection details: See revised structural <br /> calculations and added structural detail sheet. <br /> etail of the trusses to the wall top plate. Detail should show a connection that is capable <br /> of resisting uplift forces. R802.11.1 See above general response <br /> A bracing detail for the gable end trusses. R802.10.3 See above general response <br /> /A floor-to-floor framing detail showing a complete load path and shear transfer. See above <br /> general response <br /> ).O Hold downs should be provided to resist uplift forces caused by overturning effects by lateral <br /> forces. Provide appropriate tie downs for walls with a resulting uplift force. Calculations substantiating <br /> the design should be submitted for review. CIBC 1604.4 and SDPWS 4.3.6.4.2 See revised structural <br /> calculations and additional plan notes and wall key have been added to define areas of work. Also <br /> see pan for hold downs that are existing from 2008 addition. <br /> ee Sheet A-2 and S-2. It appears that a portion of the framing in the laundry room is missing. <br /> See back wall of laundry room ("FOLD'G SH." area). R106.1.1 This is only a shelf and will have no <br /> floor load, it will be constructed between the trusses to allow for overbuild dormer to match existing <br /> and allow window for light. Shelf height will be a minimum of+ 36" to match base cabinet height with a <br /> vertical face/wall to separate from living area and attic. <br /> Mans should specify special inspections and the extent of each inspection (e.g., continuous, <br /> periodic) per IBC Section 1704.3.1. The list of special inspections should also include an inspection <br /> for shear walls with nailing closer than 4 inches o.c. IBC 1705.12.2 Special inspections shall be <br /> provided as required, see structural engineering information. <br /> ,1'3. Information for SW2 in the shear wall schedule on Engineered Notes 2018 Version should be <br /> updated to match the shear wall schedule on Sheet S1. Shear wall notes are updated and located in <br /> one place. <br /> Thank you for your time and consideration regarding this project. If you have any questions please <br /> contact me at 425-344-9942 or via email at GonzalesDesignPartners@hotmail.com. <br /> Sincerely, - <br /> Li:,,,,,___________ <br /> Ruth E. Gonz es, Arc ' ect 60 <br /> Gonzales Design Partners <br /> P.O. Box 97 <br /> Arlington, Washington 98223 <br />
The URL can be used to link to this page
Your browser does not support the video tag.