UNITE <br />ST. VON NT D '� L s s EM�l�:3 <br />� M E C H A N I C A L L L C <br />PROJECT DATA <br />MECHANICAL ABBREVIATIONS <br />MECHANICAL LEGEND <br />A <br />AMPS <br />HZ <br />HERTZ <br />10X10 <br />RECTANGULAR DUCT - <br />AC <br />AIR CONDITIONING <br />IBC <br />INTERNATIONAL BUILDING CODE <br />10%10 <br />OSUPPLY RAIR <br />TURNING UP R TOWA D <br />ACH <br />AIR CHANGES PER HOUR <br />ID <br />INSIDE DIAMETER/DIMENSION <br />ACT <br />AD <br />ACOUSTICAL TILE CEILING <br />ACCESS DOOR <br />IMC <br />IN <br />INTERNATIONAL MECHANICAL CODE <br />INCHES <br />10X10 < <br />ADD'L <br />ADDITIONAL <br />IN WG <br />INCHES WATER GAUGE <br />RECTANGULAR SUPPLY AIR DUCT - <br />TURNING DOWN OR AWAY <br />AFF <br />ABOVE FINISHED FLOOR <br />IPLV <br />INTEGRATED PART LOAD VALUE <br />10X10 <br />AFG <br />ABOVE FINISHED GRADE <br />KW <br />KILOWATTS <br />AHU <br />AIR HANDLING UNIT <br />LAT <br />LEAVING AIR TEMPERATURE <br />ALUM <br />ALUMINUM <br />LB/LBS <br />POUND/POUNDS <br />10X10 <br />RECTANGULAR EXHAUST OR RETURN AIR <br />AMP/AMPS <br />AMPERAGE <br />LD/LIN DIFF <br />LINEAR DIFFUSER <br />DUCT - TURNING UP OR TOWARD <br />AP <br />ACCESS PANEL <br />LF/LIN FT <br />LINEAL FOOT/FEET <br />MLI <br />ARCH <br />ARCHITECT <br />LPG <br />LIQUID PROPANE GAS <br />ROD <br />BHP <br />BACKDRAFT DAMPER <br />BRAKE HORSEPOWER <br />LVG <br />LWG <br />LEAVING <br />LOW WALL GRILLE <br />10X10 I, <br />RECTANGULAR EXHAUST OR RETURN AIR <br />BLOG <br />ROD <br />BUILDING <br />BOTTOM OF DUCT <br />LWR <br />LWT <br />LOW WALL REGISTER <br />LEAVING WATER TEMPERATURE <br />10X10 <br />DUCT - TURNING DOWN OR AWAY <br />BOP <br />ROT <br />BOTTOM OF PIPE <br />BOTTOM <br />MAX <br />MAU <br />MAXIMUM <br />MAKE UP AIR UNIT <br />100 <br />BTU <br />BRIITSH THERMAL UNIT <br />MBH <br />1000 BRITISH THERMAL UNITS <br />ROUND DUCT - TURNING UP OR TOWARD <br />BTUH <br />BRITSH THERMAL UNITS PER HOUR <br />MCA <br />MINIMUM CIRCUIT AMPACITY <br />7 0 <br />CAP <br />CAPACITY <br />MD <br />MOTORIZED DAMPER <br />CC <br />CONTROLS CONTRACTOR <br />MFR <br />MANUFACTURER <br />CD <br />CONDENSATE DRAIN <br />MSC <br />MISCELLANEOUS <br />100� <br />CDWR <br />CONDENSER WATER RETURN <br />MIN <br />MNIMUM <br />ROUND DUCT - TURNING DOWN OR AWAY <br />CDWS <br />CONDENSER WATER SUPPLY <br />MT <br />MOUNT <br />-- Q.@ o <br />CFM <br />CUBIC FEET PER MINUTE <br />MTD <br />MOUNTED <br />v.J <br />CH <br />CH CHILLED WATER RETURN <br />MUW <br />MAKE-UP WATER <br />FLATOVAL DUCT - TURNING UP OR <br />CHINS <br />CLG <br />CHILLED WATER SUPPLY <br />CEILING <br />N <br />N/A <br />NEW <br />NOT APPLICABLE <br />100 <br />TOWARD <br />COL <br />COLUMN <br />NC <br />NORMALLY CLOSED <br />CORD <br />CONCRETE <br />NG/NGAS <br />NATURAL GAS <br />100 ij <br />FLAT OVAL DUCT - TURNING DOWN OR <br />COND <br />CONDENSATE <br />Al <br />NOT IN CONTRACT <br />AWAY <br />CONN <br />CONNECT/CONNECTED/CONNECTION <br />NO <br />NORMALLY OPEN/NUMBER <br />CONT <br />CONTINUOUS/CONTINUATION <br />OA/OSA <br />OUTSIDE AIR <br />100 <br />CONTR <br />CONTRACTOR <br />OB <br />OPPOSED BLADE <br />VOLUME DAMPER <br />COORD <br />COORDINATE <br />OBD <br />OPPOSED BLADE DAMPER <br />100 T� <br />COP <br />COEFFICIENT OF PERFORMANCE <br />OD <br />OUTSIDE DIAMETER/DIMENSION <br />CT <br />COOLING TOWER <br />P <br />PUMP <br />l� <br />Cu <br />CONDENSER UNIT <br />PCF <br />POUNDS PER CUBIC FOOT <br />TAT <br />TRANSITION <br />DB <br />DUCTBOARD <br />PD <br />PRESSURE DROP <br />DBA <br />DEC <br />DEFL <br />DECIBEL <br />DIRECT DIGITAL CONTROL <br />DEFLECTION <br />PH <br />P <br />SS <br />PRESS <br />PHASE <br />POINT OF CONNECTION <br />PRESSURE <br />TURNING VANES <br />DEG <br />DEGREE/ DEGREES <br />PSI <br />POUNDS PER SQUARE INCH <br />DIA <br />DIAMETER <br />PSIG <br />POUNDS PER SQUARE INCH GAUGE <br />DMPR <br />ON <br />DAMPER <br />DOWN <br />CITY <br />R <br />QUANITY <br />RELOCATE <br />FLEXIBLE DUCT <br />DWG <br />DRAWING <br />RA <br />RETURN AIR <br />E <br />EXH <br />EXISTING <br />EXHAUST <br />RND <br />REF <br />ROUND <br />REFERENCE <br />14x12-SL <br />SOUNDLINED DUCT <br />EA <br />EAT <br />EACH <br />ENTERING AIR TEMPERATURE <br />REG <br />RED <br />REGISTER <br />REQUIRED <br />14x12-W <br />WRAPPED DUCT <br />EC <br />EGGCRATE GRILLE/END CAP/ELEC CONTRACTOR <br />RESID <br />RESIDENTIAL <br />EER <br />EF <br />ENERGY EFFICIENT RATING <br />EXHAUST FAN <br />RE <br />RG <br />RELIEF <br />RETURN GRILLE <br />14x12-SM <br />BARE SHEETMETAL DUCT <br />EFF <br />EFFICIENCY <br />RPM <br />REVOLUTIONS PER MINUTE <br />EL <br />ELEVATION <br />S <br />SUPPLY <br />ELEC/ELECT <br />ELECTRICAL/ELECTRIC <br />SA <br />SUPPLY AIR <br />O <br />WALL MOUNTED THERMOSTAT <br />EMCS <br />ENERGY MANAGEMENT CONTROL SYSTEM <br />SO <br />SMOKE DETECTOR <br />ENT <br />EQUIP <br />ENTERING <br />EQUIPMENT <br />SEER <br />SENS <br />SEASONAL ENERGY EFFICIENCY RATING <br />SENSIBLE <br />co <br />5000 SQUARE FOOT RANGE CO SENSOR <br />ESP <br />EXTERNAL STATIC PRESSURE <br />SG <br />SUPPLY GRILLE <br />1 <br />USE AIRTEST MODEL CT-1000 <br />EWT <br />ENTERING WATER TEMPERATURE <br />SL <br />SOUND LINED <br />EXIST <br />EXISTING <br />SM <br />SHEETMETAL <br />2 <br />10000 SQUARE FOOT RANGE CO SENSOR <br />F <br />FAHRENHEIT <br />SPEC <br />SPECIFICATION <br />USE CONSPEC MODEL P2621 <br />FAC <br />FIRE ALARM CONTRACTOR <br />Sp <br />STATIC PRESSURE <br />FD <br />FF <br />FIRE DAMPER <br />FINISHED FLOOR <br />SO FT <br />SWR <br />SQUARE FEET <br />SIDE WALL REGISTER <br />s <br />FD <br />1.5 HOUR CURTAIN STYLE VERTICAL FIRE DAMPER <br />F L A <br />FULL LOAD AMPS <br />SS <br />STAINLESS STEEL <br />s <br />FLEX <br />FLR <br />FLEXIBLE <br />FLOOR <br />STRUC <br />TA <br />STRUCTURAL <br />TRANSFER AIR <br />HFD � <br />1.5 HOUR CURTAIN STYLE HORIZONTAL FIRE DAMPER <br />FOR <br />FLAT ON BOTTOM <br />TEMP <br />TEMPERATURE/TEMPORARY <br />3 <br />FOS <br />FLAT ON SIDE <br />TBD <br />TO BE DETERMINED <br />FD <br />3 HOUR CURTAIN STYLE VERTICAL FIRE DAMPER <br />TOT <br />FLAT ON TOP <br />TG <br />TRANSFER GRILLE <br />FP <br />FPM <br />FIRE PROTECTION <br />FEET PER MINUTE <br />TOC <br />To <br />TOP OF CONCRETE/CURB <br />TOP TOP OF DUCT <br />3 <br />HFD lOO- <br />3 HOUR CURTAIN STYLE HORIZONTAL FIRE DAMPER <br />FSD <br />FIRE/SMOKE DAMPER <br />TOS <br />TOP OF STEEL/TOP OF SLAB <br />FT <br />FOOT/FEET <br />TOT <br />TOTAL <br />TV <br />FACE VELOCITY <br />TSP <br />TOTAL STATIC PRESSURE <br />CFD IX -CEILING <br />RADIATION DAMPER <br />G <br />GRILLE <br />TSTAT <br />THERMOSTAT <br />GA <br />GALV <br />GAUGE <br />GALVANIZED <br />TYP <br />UH <br />TYPICAL <br />UNIT HEATER <br />FSD <br />1.5 HOUR VERTICAL COMBINATION FIRE/SMOKE DAMPER <br />GC <br />GEN <br />GENERAL CONTRACTOR <br />GENERAL <br />V <br />VD <br />VOLT <br />VOLUME DAMPER <br />FSD 0-m <br />GRILLE ACCESS 1.5 HOUR VERTICAL COMBINATION <br />GPM <br />GR <br />GALLONS PER MINUTE <br />GRILLE <br />VEL <br />VERT <br />VELOCITY <br />VERTICAL <br />GA <br />FIRE/SMOKE DAMPER <br />GRD <br />GWB <br />GRILLE/REGISTER/DIFFUSER <br />GYPSUM WALL BOARD <br />VFD <br />VOL <br />VARIABLE FREQUENCY DRIVE <br />VOLUME <br />HEED <br />1.5 HOUR HORIZONTAL COMBINATION FIRE/SMOKE DAMPER <br />HD <br />HORIZ <br />HEAD <br />HORIZONTAL <br />WE <br />WG <br />WET BULB <br />WATER GAUGE <br />TF <br />1.5 HOUR TUNNEL CORRIDOR COMBINATION FIRE/SMOKE <br />HP <br />HORSEPOWER <br />W/ <br />WITH <br />TFSD <br />DAMPER <br />HP <br />HOUR <br />W/0 <br />WITHOUT <br />HSPF <br />HEATING SEASONAL PERFORMANCE FACTOR <br />W/SF <br />WATTS PER SQUARE FOOT <br />3 <br />HT <br />HEIGHT <br />WSEC <br />WASHINGTON STATE ENERGY CODE <br />FSD q- <br />3 HOUR VERTICAL COMBINATION FIRE/SMOKE DAMPER <br />HWTG <br />HIGH WALL TRANSFER GRILLE <br />HWR <br />HWS <br />HOT WATER RETURN <br />HOT WATER SUPPLY <br />3 <br />HFSD 1- <br />3 HOUR HORIZONTAL COMBINATION FIRE/SMOKE DAMPER <br />HX <br />HEAT EXCHANGER <br />3 <br />TFSD � <br />3 HOUR TUNNEL CORRIDOR COMBINATION FIRE/SMOKE <br />DAMPER <br />SO 4- <br />VERTICAL SMOKE DAMPER <br />MECHANICAL GENERAL NOTES <br />1. ALL WORK SHALL CONFORM TO ALL APPLICABLE CODES AND REGULATIONS, INCLUDING, BUT NOT LIMITED TO THE 2018 IBC, <br />2018 WSEC, 2018 IMC. <br />2. DIMENSIONS ARE TO FACE OF STUD, CONCRETE, OR MASONRY UNLESS NOTED OTHERWISE. <br />3. DO NOT SCALE DRAWINGS. DIMENSIONS GOVERN. <br />4. VERIFY ALL EXISTING CONDITIONS, DIMENSIONS, DETAILS, ETC, NOTIFY ENGINEER OF ANY DISCREPANCIES PRIOR <br />TO PROCEEDING WITH THE WORK. <br />5. WHEN CONSTRUCTION DETAILS ARE NOT SHOWN OR NOTED FOR ANY PART OF THE WORK DETAILS SHALL BE THE SAME <br />AS FOR OTHER SIMILAR WORK. IF ADDITIONAL QUESTIONS REMAIN, CONTACT THE ENGINEER PRIOR TO PROCEEDING. <br />6. ALL STRUCTURAL OPENINGS AND PLATFORMS SHALL BE PROVIDED BY THE GENERAL CONTRACTOR UNLESS NOTED OTHERWISE. <br />7. DUCT SEALING AND CONSTRUCTION TO MEET SMACNA AND ENERGY CODE REQUIREMENTS. UNLESS OTHERWISE NOTED, <br />LOW PRESSURE DUCTWORK (DOWNSTREAM OF VAV BOXES, CONSTANT VOLUME AC SYSTEMS, TOILET EXHAUSTS, ETC.) <br />TO MEET 2" CONSTRUCTION STANDARDS WITH SEAL CLASS C. MEDIUM PRESSURE DUCTWORK (UPSTREAM OF VAV BOXES, <br />HIGH VELOCITY EXHAUSTS, ETC. TO MEET 4'" CONSTRUCTION STANDARDS WITH SEAL CLASS A. DUCT RISERS IN SHAFTS <br />WITH DAMPERED PENETRATIONS TO MEET 6" CONSTRUCTION STANDARDS WITH SEAL CLASS A. <br />8. ALL CEILING DIFFUSERS ARE 4-WAY THROW UNLESS NOTED OTHERWISE. <br />9. ALL DUCT DIMENSIONS ARE CLEAR INSIDE DIMENSIONS AFTER LINING HAS BEEN INSTALLED. <br />10. OUTSIDE AIR INTAKES ON ALL AIR HANDLING UNITS SHALL BE 10 FEET AWAY FROM ANY FUEL BURNING EQUIPMENT, AND 10 FEET <br />AWAY FROM, OR 3 FEET BELOW ANY PLUMBING VENT OR EXHAUST OUTLET. <br />11. ALL AIR ECONIMIZERS SHALL COMPLY WITH THE 2018 WSEC SECTIONS C403.5.1 THROUGH C403, 5, 5, <br />12. OUTSIDE AIR INTAKE, RELIEF, AND EXHAUST OPENINGS SHALL BE EQUIPPED WITH MOTORIZED DAMPERS WHICH CLOSE <br />AUTOMATICALLY WHEN SYSTEM IS OFF OR UPON POWER FAILURE, AS REQUIRED BY ENERGY CODE. <br />13. THE CONTROL SYSTEM SHALL BE 7-DAY PROGRAMABLE, CAPABLE OF BEING SET FOR SEVEN (7) DIFFERENT DAY TYPES PER WEEK, <br />AND CAPABLE OF A DEADBAND SETTING OF AT LEAST 5 DEGREES F 10 F FOR RESIDENTIAL BETWEEN THE HEATING AND COOLING <br />SETPOINTS. AHU CONTROL SYSTEM SHALL INCLUDE A MICROPROCESS R AND BE CAPABLE OF ESETTING SUPPLY AIR TEMPERATURES <br />BY REPRESENTATIVE BUILDING LOADS. <br />14. RECORD DRAWINGS OF THE ACTUAL. INSTALLATION SHALL. BE. PROVIDED. TO THE BUILDING OWNER WITHIN 90. DAYS OF THE DATE <br />BE PREPARED PRIOR TO ISSUANCE OF A FINAL CERTIFICATE OF OCCUPANCY. A COMPLETE FINAL COMMISSIONING REPORT OF <br />TEST PROCEDURES AND RESULTS SHALL BE PROVIDED TO THE OWNER. COMMISSIONING, SYSTEM BALANCING, RECORD DRAWINGS <br />AS REQUIRED PER THE WASHINGTON STATE ENERGY CODE. <br />15. MECHANICAL SYSTEMS SHALL COMPLY WITH SEISMIC RESTRAINT REQUIREMENTS OF THE BUILDING CODE SMACNA AND ASCE 7. <br />ALL LIFE SAFETY HAZARDOUS MATERIAL RELATED SYSTEMS SHALL BE DEEMED AN Ip-1 .5 FOR RESTRAINT METHODS OR AS NOTED <br />ON THE DRAWINGS. REFER TO THE ABOVE NOTED CODES FOR INSTALLATION REQUI RLMENTS AND EXCEPTIONS BASED ON SIZING, <br />WEIGHTS AND MOUNTING HEIGHTS. <br />16. PROVIDE EARTHQUAKE RESTRAINTS FOR HVAC EQUIPMENT AS REQUIRED BY SMACNA SEISMIC RESTRAINT MANUAL, SEIZMIC HAZARD B. <br />WIRES FOR CEILING SYSTEM ETC. SHALL NOT BE HUNG OFF HVAC EQUIPMENT OR HVAC EQUIPMENT SUPPORTS. <br />17. PROVIDE FIRE AND COMBINATION FIRE/SMOKE DAMPERS WHERE SHOWN ON PLANS AND WHERE REQUIRED PER CODE. <br />18. ALL PIPING PENETRATIONS THROUGH RATED ASSEMBLIES SHALL BE SEALED WITH A UL APPROVED FIRE CAULKING. <br />19. SMOKE DETECTORS PROVIDING AUTOMATIC SHUTDOWN SHALL BE PROVIDED FOR HVAC EQUIPMENT DELIVERING IN EXCESS OF <br />2000 CFM [INCLUDING MULTIPLE UNITS DUCTED INTO COMMON DISTRIBUTION OR RETURN, WITH AN AGGREGATE SUPPLY GREATER <br />THAN 2000 CFM 1 OR EACH STORY OF RETURN SYSTEMS OVER 15 000 CFM IN A MULTI -STORY INSTALLATION PER CODE. <br />SMOKE DETECTORRS SHALL BE FURNISHED AND NSTALLED BY ELECTRICAL CONTRACTOR UNLESS NOTED OTHERWISE. POWER -WIRING <br />AND INTERLOCK TO FIRE ALARM SYSTEM BY ELECTRICAL CONTRACTOR AS APPLICABLE. <br />20. ACCESS PANELS SHALL BE PROVIDED AND INSTALLED BY GENERAL CONTRACTOR. <br />21. ALL MOTOR STARTERS NOT SHOWN IN EQUIPMENT SCHEDULES SHALL BE FURNISHED AND INSTALLED BY ELECTRICAL CONTRACTOR. <br />22. FOR ALL "SEALED AIR TIGHT SHAFTS OR ROOMS THE FOLLOWING SHALL OCCUR: <br />-ALL VERI <br />TICAL JOINTS NSIDE THE SHAFT SHALL BE PROVIDED WITH A CONTINUOUS SEAL FOR THE LENGTH OF THE JOINT, <br />INCLUDING THE SHAFT CORNERS (BY GC) <br />_TO AND -ANY FLOOROTTOM DECCKINGLL TRA KS PERPENDICULAARLTTOBTHEAULKED ALONG SHAFTT SHALL BEEIR CAULKEDR(BYEGC)TH FRILLING WITH ROCK WOOL IS NOT ACCEPTABLE <br />-ANY PENETRATIONS OF THE SHAFT CONSTRUCTION (DUCTWORK, CONDUIT, PIPING, ...) SHALL BE SEALED ON BOTH SIDES <br />OF THE PENETRATION. <br />-USE SECTION 909.5 OF THE 2015 IBC FOR MAXIMUM ALLOWABLE LEAKAGE AREA, FOLLOWING THE GUIDELINES FOR TIGHT STAIR <br />SHAFT CONSTRUCTION. <br />-ALL DOORS SHALL BE PROVIDED WITH TIGHT FITTING GASKETS, AND OPEN AGAINST THE DIRECTION OF ROOM/SHAFT PRESSURE. <br />23. MAXIMUM LENGTH OF FLEXIBLE DUCT SHALL BE 12 FEET. REFER TO INSTALLATION DETAILS FOR SUPPORT REQUIREMENTS. <br />FLEXIBLE DUCT FLAME SPREAD RATING SHALL BE < 25 AND SMOKE DEVELOPED RATING SHALL BE < 50. USE FLEXIDUCT <br />MODEL G-KM FOR LOW AND MEDIUM PRESSURE APPLICATIONS OR APPROVED EQUAL. <br />24. LOCATION AND DETAILS OF EQUIPMENT DUCT ROUTING AND CONNECTIONS ARE APPROXIMATE. COORDINATE FINAL LOCATIONS WITH <br />OTHER TRADES, INSTALL IN ACCORDANCE WITH APPROVED SUBMITTALS AND DETAIL DRAWINGS WHEN APPLICABLE. <br />ADDRESS OF PROJECT <br />6424 BROADWAY AVENUE <br />EVERETT, WASHINGTON <br />98203 <br />PARCEL NUMBER <br />75267 <br />VICINITY MAP <br />Madison St <br />A FULL SERVICE COMMERCIAL <br />HVAC CONTRACTOR <br />1400 AIRPORT WAY SOUTH <br />SUITE 202 <br />SEATTLE, WASHINGTON 98134 <br />(206)933-6036/FAX 937-3084 <br />E Sq� <br />' i172 sTEIC 12� <br />�SSJONAL <br />EXPIRES 05-09-2023 <br />10-25-22 <br />REVISIONS <br />DATE DISCRIPTION <br />J <br />L.L <br />W <br />0 <br />LJ <br />Z <br />Z <br />O j O <br />W <br />Q Q O <br />U <br />�rZ <br />Z <br />�Q= <br />�o< <br />zoo <br />> <br />�12� <br />DO ~ <br />W <br />W M <br />O 71 w <br />'t > c0 <br />coD' <br />VJ <br />D_ c0 w rn <br />FILE NAME : SVOP-M <br />PROJECT ENGINEER :,JGL <br />DATE REVISED : 3- 1 0-2023 <br />JOB NUMBER :9825 <br />SHEET NUMBER <br />M - i <br />THESE DRAWINGS ARE THE PROPERTY OF UNITED SYSTEMS MECHANICAL LLC AND MUST NOT BE REPRODUCED, ALTERED OR USED WITHOUT THE PRIOR WRITTEN AUTHORITY OF UNITED SYSTEMS LLC. THESE DRAWINGS ARE TO BE USED ONLY AS SUPPLEMENTARY TO THE ARCHITECT'S DRAWINGS AND SPECIFICATIONS. ANY PROPOSED VARIATIONS OR DEPARTURES FROM THESE DRAWINGS MUST BE APPROVED BY UNITED SYSTEMS MECHANICAL LLC. <br />