Cooling' (Non -Ducted // Mix // Ducted)
<br />Maximum Capacity
<br />BTU/H
<br />48,000 H 48,000 H 48,000
<br />Rated Capacity
<br />BTU/H
<br />48,000 H 48,000 H 48,000
<br />Minimum Capacity
<br />BTU/H
<br />W
<br />16,000 H 16,000 H 16,000
<br />3,665 // 3,930 H 4,245
<br />Maximum Power Input
<br />Rated Power Input
<br />W
<br />%
<br />3,665 // 3,930 H 4,245
<br />98.5, 98.5 // 98.5, 98.5 // 98.5, 98.5
<br />Power Factor (208V, 230V)
<br />Heating at 47°F2 (Non -Ducted H Mix //
<br />Ducted)
<br />Maximum Capacity
<br />BTU/H
<br />BTU/H
<br />BTU/H
<br />54,000 H 54,000 H 54,000
<br />54,000 H 54,000 // 54,000
<br />27,000 H 27,000 H 27,000
<br />Rated Capacity
<br />Minimum Capacity
<br />Maximum Power Input
<br />W
<br />3,955 // 4,335 H 4,795
<br />Rated Power Input
<br />W
<br />3,955 // 4,335 H 4,795
<br />Power Factor (208V, 230V)
<br />%
<br />98.5, 98.5 // 98.5, 98.5 // 98.5, 98.5
<br />Heating at 17°F3 (Non -Ducted // Mix //
<br />Ducted)
<br />Maximum Capacity
<br />BTU/H
<br />43,000 // 43,000 H 43,000
<br />Rated Capacity
<br />BTU/H
<br />31,400 // 31,400 H 31,400
<br />Maximum Power Input
<br />W
<br />5,200 H 5,650 H 6,350
<br />Rated Power Input
<br />W
<br />3,410 // 3,840 H 4,270
<br />Heating at 5°F4 (Non -Ducted // Mix //
<br />Ducted)
<br />Maximum Capacity
<br />BTU/H
<br />32,400 // 32,400 H 32,400
<br />Maximum Power Input
<br />W
<br />4,530 H 4,650 H 4,770
<br />Efficiency (Non -Ducted // Mix // Ducted)
<br />SEER
<br />23.0 H 19.75 H 16.5
<br />EER'
<br />13.1 //12.2 //11.3
<br />HSPF (IV)
<br />12.0 H 11.5 // 11.0
<br />COP at 47°F2
<br />4.0 // 3.65 // 3.3
<br />COP at 17°F at Maximum Capacity3
<br />2.1 // 1.96 // 1.7
<br />COP at 5°F at Maximum Capacity'
<br />2.1 // 2.05 // 2.0
<br />ENERGY STAR® Certified
<br />Yes // No // No
<br />Electrical
<br />Electrical Power Requirements
<br />Voltage, Phase,
<br />Frequency
<br />208/230, 1, 60
<br />Guaranteed Voltage Range
<br />VAC
<br />187-253
<br />Voltage: Indoor - Outdoor, S1-S2
<br />VAC
<br />208/230
<br />Voltage: Indoor - Outdoor, S2-S3
<br />V DC
<br />24
<br />Short-circuit Current Rating (SCCR)
<br />kA
<br />5
<br />Recommended Fuse/Breaker Size if Branch Box Powered by
<br />Outdoor Unit
<br />A
<br />30 (40)
<br />Recommended Fuse/Breaker Size without Branch Box or
<br />Branch Box Powered Separate
<br />A
<br />30
<br />Recommended Wire Size
<br />AWG
<br />8
<br />MCA if Branch Box Powered by Outdoor Unit
<br />A
<br />35.0
<br />MOCP if Branch Box Powered by Outdoor Unit
<br />A
<br />50
<br />MCA without Branch Box or Branch Box Powered Separate
<br />A
<br />29
<br />MOCP without Branch Box or Branch Box Powered Separate
<br />A
<br />40
<br />Fan Motor Full Load Amperage
<br />A
<br />0.6+0.6
<br />Outdoor unit
<br />Airflow Rate (Cooling / Heating)
<br />CFM
<br />3,885 / 3,885
<br />Refrigerant Control
<br />LEV
<br />Defrost Method
<br />Reverse Cycle
<br />Heat Exchanger Type
<br />Plate fin coil
<br />Heat Exchanger Coating
<br />Blue Fin Coating
<br />Sound Pressure Level, Cooling'
<br />dB(A)
<br />51
<br />Sound Pressure Level, Heating2
<br />dB(A)
<br />54
<br />Compressor Type
<br />Hermetic
<br />Compressor Model
<br />ANB33FNHMT
<br />Compressor Motor Output
<br />kW
<br />3.4
<br />Compressor Rated Load Amps
<br />A
<br />19
<br />Compressor Locked Rotor Amps
<br />A
<br />22.0
<br />Compressor Oil Type // Charge
<br />oz.
<br />FV50S // 78
<br />Base Pan Heater
<br />Optional (PAC-SJ20BH-E)
<br />Unit Dimensions
<br />W: In. [mm]
<br />41-11/32 [1,050]
<br />D: In. [mm]
<br />13 [330]
<br />H: In. [mm]
<br />52-11/16 [1,338]
<br />Package Dimensions
<br />W: In. [mm]
<br />43 [1,090]
<br />D: In. [mm]
<br />18 [450]
<br />H: In. [mm]
<br />57 [1,430]
<br />Unit Weight
<br />Lbs.[kg]
<br />271 [123]
<br />Package Weight
<br />Lbs.[kg]
<br />295 [134]
<br />NOTES:
<br />AHRI Rated Conditions 'Cooling (Indoor // Outdoor) °F 80 DB, 67 WB // 95 DB, 75 WB
<br />(Rated data is determined at a fixed compressor speed) 21-leating at 47°F (Indoor H Outdoor) °F 70 DB, 60 WB // 47 DB, 43 WB
<br />31-leating at 17°F (Indoor H Outdoor) °F 70 DB, 60 WB // 17 DB, 15 WB
<br />Conditions 41-leating at 5°F (Indoor // Outdoor) °F 70 DB, 60 WB // 5 DB, 4 WB
<br />'Applications should be restricted to comfort cooling only; equipment cooling applications are not recommended for low ambient temperature conditions.
<br />when 1 or more PIA-A-EA7 connected
<br />'a Branch box should be placed within the level between the outdoor unit and indoor units
<br />5°F DB - 115°F DB when optional wind baffles are installed
<br />For actual capacity performance based on indoor unit type and number of indoor units connected, please refer to MXZ Operational Performance.
<br />Although the maximum connectable capacity is 130 % , the outdoor unit cannot provide more than 100 % of the rated capacity. Please utilize this over capacity capability for load shedding or applications
<br />where it is known that all connected units will NOT be operating at the same time.
<br />Specifications are subject to change without notice. © 2022 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.
<br />
|