Laserfiche WebLink
PROPOSED 2" UNDERGROUND FIBER <br />CONDUIT (LENGTH: 75'-0"t) WITH <br />400—lb MULE TAPE TO BE INSTALLED <br />BY DISH WIRELESS, L.L.C. CONTRACTOR <br />TO COORDINATE ROUTING WITH UTILITY <br />COMPANY. SEE NOTE 3. VERIFY <br />AGAINST FINAL APPROVED TELCO <br />DESIGN PRIOR TO CONSTRUCTION. <br />DISH WIRELESS, L.L.C. CONTRACTOR TO <br />STUB UP 2" CONDUIT FOR FIBER 5 FT <br />ABOVE GRADE NEAR EXISTING FIBER <br />HAND HOLE. VERIFY AGAINST FINAL <br />APPROVED TELCO DESIGN PRIOR TO <br />CONSTRUCTION. <br />APPROXIMATE LOCATION OF <br />EXISTING FIBER HAND HOLE <br />VERIFY <br />NOTES <br />1. CONTRACTOR SHALL FIELD VERIFY ALL PROPOSED UNDERGROUND UTILITY CONDUIT ROUTE. <br />2. ANTENNAS AND MOUNTS OMITTED FOR CLARITY. <br />3. THE GROUND LEASE PROVIDES BROAD/BLANKET UTILITY RIGHTS. "PWR" AND "FBR" PATH DEPICTED ON A-1 AND E-1 ARE BASED ON BEST AVAILABLE INFORMATION INCLUDIKLd <br />BUT NOT LIMITED TO FIELD VERIFICATION, PRIOR PROJECT DOCUMENTATION AND OTHER REAL PROPERTY RIGHTS DOCUMENTS. WHEN INSTALLING THE UTILITIES PLEASE LOCATE <br />AND FOLLOW EXISTING PATH. IF EXISTING PATH IS NOT AN OPTION, PLEASE NOTIFY TOWER OWNER AS FURTHER COORDINATION MAY BE NEEDED. <br />FBR FBR - <br />m <br />A <br />m <br />FBR FBR�I PER PER <br />1 FU <br />DD <br />XI IX <br />k <br />X X <br />UTILITY ROUTE PLAN <br />APPROXIMATE LOCATION OF <br />EXISTING GROUND —MOUNTED <br />TRANSFORMER <br />FOR CONDUITS TRAVELING ACROSS <br />VEHICLE ZONES TO AVOID DAMAGE <br />PROPOSED 3" UNDERGROUND POWER <br />CONDUIT (LENGTH: 10'-0"f) FROM <br />PROPOSED 200A METER TO EXISTING <br />GROUND —MOUNTED TRANSFORMER TO BE <br />INSTALLED BY DISH WIRELESS, L.L.C. <br />CONTRACTOR TO COORDINATE ROUTING WITH <br />V UTILITY COMPANY. <br />BR X X <br />PWR <br />X <br />X <br />x <br />X X X Xu <br />DC POWER WIRING SHALL BE COLOR CODED AT EACH END FOR IDENTIFYING +24V AND —48V CONDUCTORS. <br />RED MARKINGS SHALL IDENTIFY +24V AND BLUE MARKINGS SHALL IDENTIFY —48V. <br />1. CONTRACTOR SHALL INSPECT THE EXISTING CONDITIONS PRIOR TO SUBMITTING A BID. ANY QUESTIONS ARISING <br />DURING THE BID PERIOD IN REGARDS TO THE CONTRACTOR'S FUNCTIONS, THE SCOPE OF WORK, OR ANY <br />OTHER ISSUE RELATED TO THIS PROJECT SHALL BE BROUGHT UP DURING THE BID PERIOD WITH THE PROJECT <br />MANAGER FOR CLARIFICATION, NOT AFTER THE CONTRACT HAS BEEN AWARDED. <br />2. ALL ELECTRICAL WORK SHALL BE DONE IN ACCORDANCE WITH CURRENT NATIONAL ELECTRICAL CODES AND ALL <br />STATE AND LOCAL CODES, LAWS, AND ORDINANCES. PROVIDE ALL COMPONENTS AND WIRING SIZES AS <br />REQUIRED TO MEET NEC STANDARDS. <br />3. LOCATION OF EQUIPMENT, CONDUIT AND DEVICES SHOWN ON THE DRAWINGS ARE APPROXIMATE AND SHALL BE <br />COORDINATED WITH FIELD CONDITIONS PRIOR TO CONSTRUCTION. <br />4. CONDUIT ROUGH —IN SHALL BE COORDINATED WITH THE MECHANICAL EQUIPMENT TO AVOID LOCATION CONFLICTS. <br />VERIFY WITH THE MECHANICAL EQUIPMENT CONTRACTOR AND COMPLY AS REQUIRED. <br />5. CONTRACTOR SHALL PROVIDE ALL BREAKERS, CONDUITS AND CIRCUITS AS REQUIRED FOR A COMPLETE SYSTEM. <br />6. CONTRACTOR SHALL PROVIDE PULL BOXES AND JUNCTION BOXES AS REQUIRED BY THE NEC ARTICLE 314. <br />7. CONTRACTOR SHALL PROVIDE ALL STRAIN RELIEF AND CABLE SUPPORTS FOR ALL CABLE ASSEMBLIES. <br />INSTALLATION SHALL BE IN ACCORDANCE WITH MANUFACTURER'S SPECIFICATIONS AND RECOMMENDATIONS. <br />8. ALL DISCONNECTS AND CONTROLLING DEVICES SHALL BE PROVIDED WITH ENGRAVED PHENOLIC NAMEPLATES <br />INDICATING EQUIPMENT CONTROLLED, BRANCH CIRCUITS INSTALLED ON, AND PANEL FIELD LOCATIONS FED FROM. <br />9. INSTALL AN EQUIPMENT GROUNDING CONDUCTOR IN ALL CONDUITS PER THE SPECIFICATIONS AND NEC 250. <br />THE EQUIPMENT GROUNDING CONDUCTORS SHALL BE BONDED AT ALL JUNCTION BOXES, PULL BOXES, AND ALL <br />DISCONNECT SWITCHES, AND EQUIPMENT CABINETS. <br />10. ALL NEW MATERIAL SHALL HAVE A U.L. LABEL. <br />11. PANEL SCHEDULE LOADING AND CIRCUIT ARRANGEMENTS REFLECT POST —CONSTRUCTION EQUIPMENT. <br />12. CONTRACTOR SHALL BE RESPONSIBLE FOR AS —BUILT PANEL SCHEDULE AND SITE DRAWINGS. <br />13. ALL TRENCHES IN COMPOUND TO BE HAND DUG. <br />14. CONTRACTOR TO VERIFY HANDHOLE AND/OR PULL BOXES REQUIREMENTS WITH SELECTED FIBER PROVIDER <br />PRIOR TO CONSTRUCTION OF TRENCH. <br />8' 4' 0 8' 1 E <br />ELECTRICAL NOTES NO SCALE 2 <br />d..*.sh <br />wirelessry <br />5701 SOUTH SANTA FE DRIVE <br />LITTLETON, CO 80120 <br />TOWER ING PROFESSIONALS <br />326 D. RALEIGH, NC <br />27603 FI E: (919) 661-6351 <br />A <br />N <br />50257 <br />�131ST <br />_v—fi 8, 2022 <br />IT IS A VIOLATION OF LAW FOR ANY PERSON, <br />UNLESS THEY ARE ACTING UNDER THE <br />DIRECTION OF A LICENSED PROFESSIONAL <br />ENGINEER, TO ALTER THIS DOCUMENT. <br />DRAWN BY: <br />CHECKED BY:APPROVED <br />BY: <br />CDK <br />CP <br />CP <br />RFDS REV #: TBD <br />CONSTRUCTION <br />DOCUMENTS <br />SUBMITTALS <br />REV <br />DATE <br />DESCRIPTION <br />A <br />08-05-21 <br />PRELIMINARY <br />B <br />12-21-21 <br />PRELIMINARY <br />C <br />01-18-22 <br />PRELIMINARY <br />0 <br />03-08-22 <br />CONSTRUCTION <br />A&E PROJECT NUMBER <br />147003 <br />DISH WIRELESS, L.L.C. <br />PROJECT INFORMATION <br />SESEA00361C <br />9610 19TH AVENUE SE <br />EVERETT, WA 98208 <br />SHEET TITLE <br />ELECTRICAL/FIBER ROUTE <br />PLAN AND NOTES <br />SHEET NUMBER <br />E-1 <br />