Laserfiche WebLink
PEM POWER CABLE (SUPPLIED <br /> WITH PEM) <br /> FACP BATTERY CALCULATIONS `t <br /> COMPONENTS QTY. STANDBY ALARM <br /> CURRENT CURRENT <br /> AFC-100(FACP) 1 OA 3000A 0.22000A <br /> UD-2000(DACT) 1 0.01600A 0.02300A <br /> C <br /> SLC DEVICES SUPERVISORY CURRENT ALARURRENM <br /> T <br /> PAD-PD 6 0.00030A 0.00030A 0.00180A 0.00180A Fol <br /> PAD-HD 2 0.00030A 0.00030A 0.00060A 0.00060A 33/4"C - 2#14THHN,1#14G 20 <br /> PAD-DUCT 0 0.00030A 0.00030A 0.000OOA 0.000OOA TG-PEM RED <br /> PAD100-PSSA/PSDA 8 0.00020A 0.00020A 0.00160A 0.0O160A NNS <br /> PAD100-RM Q 0.00024A 0.00024A o.000oOA o.00coOA FACP EVT-FA-45-703 TG 7FS <br /> PAD100-MIM Q 0.00020A &00040A Q.000OOA o.00coOA (BY FIRE ALARM VENDOR) ORN 1 1 4 7 <br /> PAD100-DIM 0 0.00024A 0.00024A O.00o00A O.000OOA <br /> STANDBY ALARM R <br /> CURRENT CURRENT 3 <br /> NAC CRT 1(AUX PWR) 0.018A OA1000A 0.01800A 0.11000A <br /> NAC CRT 2 O.00A 0.26200A 0.000OOA 0.67100A T <br /> �TOTAL <br /> O.00A O.000OOA 0 OOOOOA O.000OOA <br /> LC ALARM LED O.00A 0.03600A O.000OOA 0.03600A DG STC2 STC1 TRIP BATT AG <br /> OA6800A 1.064A 2 1 2 3 4 5 6 1 2 3 2 G <br /> TOTAL STANDBY CURRENT DRAW= 0.168 AMPS �e oke �e <br /> X STANDBY TIME 48 HOURS <br /> STANDBY AMP HOUR TOTAL= 8.064 AH RED EOL(as NEEDED) <br /> TOTAL ALARM CURRENT DRAW= 1.064 AMPS <br /> X ALARM TIME 0.167 HOURS <br /> ALARM AMP HOUR TOTAL= 0.178 AH <br /> STANDBY AH + ALARM AH = 8.24 AH <br /> X DE-RATING FACTOR 1.20(20%) 3/4"C - (1) PHONE CABLE, <br /> TOTAL AH REQUIRED = 9.89 AH (1) 2 CONDUCTOR FPL OR REFERENCE DRAWINGS <br /> MINIMUM BATTERY SIZE NEEDED: 10 AH APPROVED EQUAL <br /> BATTERY SIZE PROVIDED: 12 AH v 45-703-E260 FIRE ALARM PLAN VIEW <br /> v N Na, NOTE: 0.167 EQUALS 10 MINUTES OF ALARM TIME <br /> w w ¢ w w <br /> CONSTRUCTION NOTES <br /> FACP VOLTAGE DROP CALCULATION FIRE ALARM SYSTEM COMMUNICATIONS DETAIL <br /> a a a a a CIRCUIT SUPPLY ALARM OHMS NCT TOTAL LAST DEVICE VOLTAc PROVIDE CELLULAR DIALER, AND MOUNT ADJACENT TO <br /> Z Z Z Z Z NAME VOLTAGE CURRENT WIRE TYPE 1000 F. FEET RESISTANCE VOLTAGE DROP% SCALE: NONE E260 E566 THE BUILDING FACP. CONFIGURE DIALER TO PROVIDE <br /> g g g g NAC1(AUX) 20.4 VDC 0.110 A #14AWG SOLID 3.07 10 0.0614 20.393 VDC 0.03% SOLE PATH COMMUNICATION. DIALER SHALL BE <br /> F F F F F NAC2 20.4 VDC 0.671 A #14AWG SOLID 3.07 424 2.6034 18.65 VDC 8.56% COMPATIBLE WITH AT&T CELL SERVICE. <br /> 1:16 1:15 _1:08 1:04 1:03 N/A 20.4 VDC 0.000 A #14AWG SOLID 3.07 0 0 00.00 VDC 0% <br /> PROVIDE (1) CONDUIT PENETRATION FOR PHONE AND <br /> N/A 20.4 VDC 0.000 A #14AWG SOLID 3.07 0 00.00 VDC o% FIRE ALARM CONNECTIONS. WIRE AS SHOWN. PROVIDE <br /> U U Q <br /> ckf <br /> � ADDRESSABLE MODULE AS NECESSARY TO PROVIDE <br /> z n z o o cz Cf w GENERAL TROUBLE ALARM FROM CELLULAR DIALER TO <br /> w w w w G, w w w BUILDING FACP. <br /> U U U U J z J U U <br /> O O O O a a g 3 a O O <br /> STEP 1: VERIFY SIGNAL STRENGTH AT PROPOSED LOCATION FOR CELLULAR COMMUNICATOR PANEL INDICATED ON [J:�:- PROVIDE (1) CONDUIT PENETRATION FOR 24/12VDC <br /> x x x x ¢ Q w w ¢ x x DRAWINGS. IF ACCEPTABLE *SIGNAL STRENGTH IS ACQUIRED, SKIP TO STEP 5. POWER AND EARTH GROUND FROM THE BUILDING FACP <br /> _ _ POWER SUPPLY. PROVIDE POWER AND EXPANSION <br /> S S S 00 S F F F S S CELLULAR MONITORED BY TYCO AND STEP 2: IF ORIGINALLY PROPOSED LOCATION IS INADEQUATE, FIELD TEST *SIGNAL STRENGTH WITHIN A 20FT RADIUS MODULE AND WIRE AS SHOWN. MAINTAIN <br /> L1:14 L1:13 Li;p7 L1:02 L1:01 SLC ANAL G P H O N LINE DIALER SIGNAL SENT TO CENTRAL TO IDENTIFY LOCATION(S) SUITABLE FOR INSTALLATION OF REMOTE/EXTERNAL CELLULAR ANTENNA. <br /> L1:10 L1:09 L1:12 11:11 L1:06 L1:05 ANALOG <br /> TG-7FS-A BOEING FIRE DEPARTMENT MANUFACTURER'S REQUIRED 1/4" SEPARATION <br /> COORDINATE THE FINAL ANTENNA LOCATION WITH BOEING AND SPACE USERS (IF IMPACTED) FOR BETWEEN POWER AND COMMUNICATION WIRING. <br /> 45-703 FACP *TWO SEPARATE PATHWAYS FOR SIGNAL REQUIRED BY CODE, AS SHOWN. APPROVAL PRIOR TO ROUGH-IN AND SKIP TO STEP 4. <br /> NAC2 STEP 3: IF ACCEPTABLE *SIGNAL STRENGTH IS NOT ACHIEVED WITHIN 20FT OF ORIGINAL PROPOSED LOCATION FOR ® PROVIDE PHENOLIC LABEL, WHITE LETTERING, RED <br /> 75CD 30CD 30CD 75CD 15CD 15CD 30CD 75CD CELLULAR COMMUNICATOR PANEL, PROPOSE ALTERNATE LOCATION FOR CELLULAR PANEL. COORDINATE BACKGROUND, THAT READS: <br /> BUILDING 713 BUILDING 733 BUILDING 773 BUILDING 703 WITH BOEING AND SPACE USERS FOR POTENTIAL LOCATIONS, PREFERABLY NEAR ORIGINAL LOCATION. "FIRE ALARM CELLULAR DIALER" <br /> ANALOG PHONE LINE STEP 4: LOCATE AND PROVIDE EXTERNAL CELLULAR ANTENNA, EXTERIOR MOUNTING BRACKET AND COAXIAL CABLE <br /> (SECONDARY) FROM CELLULAR COMMUNICATOR TO THE ANTENNA. THE ANTENNA AND PANEL SHOULD BE LOCATED [5:�, PROVIDE CELL ANTENNA AND EVALUATE FIELD SIGNAL <br /> EVT-FA-45-703 WITHIN 20FT OF EACH OTHER. STRENGTH IN ACCORDANCE WITH DETAIL 2. INSTALL <br /> STEP 5: PROVIDE 24VDC POWER, MONITORING CIRCUIT, AND TELEPHONE LINE TO CELLULAR COMMUNICATOR FROM CONDUIT AND EXTENDED ANTENNA CABLE <br /> BUILDING FACP. NECESSARY TO REMOTE MOUNT ANTENNA IF IF COVERAGE <br /> S NOT SUITABLE AT FACP LOCATION. UPDATE BOM <br /> DEDICATED 120VAC 20AMP STEP 6: PROVIDE REQUIRED SET-UP, PROGRAMMING AND TESTING OF CELLULAR COMMUNICATOR EQUIPMENT PER WITH SELECTED CABLE LENGTH AND PROVIDE REDLINES <br /> THE MANUFACTURER'S INSTRUCTIONS. CELLULAR DIALER SHALL BE CONFIGURED AND INSTALLED AS A TO BOEING ENGINEER. <br /> DDU II.NDN N R G FIRE ALARM SYSTEM S E R E� SOLE PATH FOR FIRE COMMUNICATIONS. ©506 FOR REMOTE INSTALLATIONS PROVIDE PHENOLIC LABEL, <br /> WHITE LETTERING, RED BACKGROUND, THAT READS: <br /> *ACCEPTABLE SIGNAL STRENGTH SHALL BE DETERMINED BY MANUFACTURERS SPECIFICATIONS AND LOCAL AHJ <br /> 45-703 B ILG SYSTEM FACP POINTS ORDINANCES. "FIRE ALARM CELLULAR ANTENNA" <br /> 7� INSIDE CELL ENCLOSURE POST COMMUNICATOR <br /> POINT NUMBER/ZONE BOEING DESCRIPTION FACP POINT - COMMENTS - GRID/SHEET LOC. SETTINGS AND CELLUAR PHONE NUMBER. PROVIDE <br /> PRINTED LABEL, HANDWRITTEN INFORMATION IS NOT <br /> L1:001 1 45-703 SMK OFFICE E 703 OFFICE EAST SMOKE DETECTOR - F2/E260 CELLULAR C0MMUNICATOR N STALLATI 0 N SEQUENCE ACCEPTABLE. PROVIDE SETTINGS AND CELLULAR <br /> _1:002 2 45-703 SMK OFFICE W 703 OFFICE WEST SMOKE DETECTOR - D2/E260 SCALE: NONEINFORMATION TO BOEING ENGINEER. <br /> L1:003 3 45-703 MAN PULL DR 11 E2 703 MANUAL PULL DOOR 11 E2 - F3/E260 E260 E506 <br /> _1:004 4 45-703 MAN PULL DR 11E26 703 MANUAL PULL DOOR 11 72A - D3/E260 <br /> _1:005 5 7-773 SMK M RESTROOM 773 WOMENS R.R. HEAT DETECTOR - A3/E260 <br /> _1:006 6 7-773 SMK W RESTROOM 773 MENS R.R. HEAT DETECTOR - A4/E260 <br /> _1:007 7 7-773 MAN PULL DR 11A3 773 WOMENS R.R. MANUAL PULL - A3/E260 BILL OF MATERIALS <br /> L1:008 8 7-773 MAN PULL DR 11A4 773 MANS R.R. MANUAL PULL - A4/E260 ITEM QTY. PART NO. MANUFACTURER DESCRIPTION <br /> _1:009 9 45-733 SMK OFFICE N 733 OFFICE NORTH SMOKE DETECTOR - C5/E260 1 1 3992753 POTTER FIRE ALARM CONTROL PANEL <br /> L1:010 10 45-733 SMK OFFICE S 733 OFFICE SOUTH SMOKE DETECTOR - C7/E260 2 1 3992769 POTTER UD-2000 DACT CARD <br /> _1:011 11 45-733 MAN PULL DR 1106A 733 MANUAL PULL DOOR 1106A - C5/E260 3 8 3992732 POTTER PAD100 6° BASE <br /> _1:012 12 45-733 MAN PULL DR 11 C613 733 MANUAL PULL DOOR 1106B - C8/E260 4 6 3992770 POTTER PAD200 PHOTO DETECTOR <br /> _1:013 13 45-713 SMK OFFICE N 713 OFFICE NORTH SMOKE DETECTOR - F5/E260 5 2 3992735 POTTER PAD100 HEAT DETECTOR(135° FIXED) <br /> _1:014 14 45-713 SMK OFFICE S 713 OFFICE SOUTH SMOKE DETECTOR - F7/E260 6 8 3992720 POTTER PAD100 PULL STATION <br /> L1:015 15 45-713 MAN PULL DR 11 F6 713 MANUAL PULL DOOR 11 F6 - E5/E260 <br /> 7 2 SLA1104 POWERPATROL 12VDC 12 AH BATTERIES <br /> L1:016 16 45-713 MAN PULL DR 11F66 713 MANUAL PULL DOOR 11`613 - E8/E260 <br /> 8 6 BK-P2RL SYSTEM SENSOR HORN/STROBES <br /> BUILDING FACP POINTS LIST 9 2 BK-SRL SYSTEM SENSOR STROBES <br /> 10 1 1 TG-7FS-A ITELGUARD ATT CELLULAR DIALER <br /> SCALE: NONE E506 111 1 ISSU00689 SPACEAGE IFIRE ALARM STORAGE CABINET <br /> SYM REVISION BY APPROVED DATE SYM REVISION BY APPROVED DATE ACCEPTABILITY DRAWN DATE SUBTITLE CURRENT REVISION SYMBOL DATE <br /> oR1G STALL 113 TRAILERS c243685 MDK ABR o,.z7.z3 HIS DESIGN AND/QR CHECKED FIRE ALARM SYSTEM DETAILS 0243685 A 04.28.23 0 <br /> SPECIFICATION IS APPROVED SHEET <br /> A SHOP DRAWINGS AGOW/JS 04.28.23 BOE//VG® m APPRovED er DEPT. DATE TITLE E506 \ <br /> NECKED <br /> e..e :� APPROVED BUILDING 45-703,713,733,773 DB NG DMP NG. <br /> APPROVED ELECTRICAL MASTER EVERETT, WA DWG NO. 45-703-E506 <br />