HVAC Systems <br />PROJECT: Kimley Horn Everett <br />LOCATION: Everett, WA <br />PROJECT #: 60940287 <br />SYSTEM/UNIT: HVAC-01/DOAS-02 <br />engineered <br />� I systems <br />DATE: 5/10/2023 <br />CONTACT: Steve Lybecker <br />Unit Data Equipment Tested.. <br />Location Ceiling TAB By Kalani Rivera <br />Serves Level 3 TAB Date 05/08/2023 <br />Manufacturer Mitsubishi <br />Model Number TLGHF060ORVX02A Test Data <br />Serial Number 22050006546177 Design Supply CFM 530 CFM <br />Type of Unit DOAS Actual Supply CFM 585 CFM <br />Main Unit Voltage 208 Volts Design Return CFM 530 CFM <br />Main Unit Phase 1 Actual Return CFM 585 CFM <br />HVAC-01/D0AS-02/Filter-01 Design Minimum Outside CFM 530 CFM <br />Filter 1 Type Lossnay Core Actual Minimum Outside CFM 585 CFM <br />Filter 1 Rating OEM <br />Filter 1 Qty 1 <br />Filter 1 Size OEM <br />Motor <br />ata <br />HVAC-01/D0AS-02/EF-1 , <br />Drive Type Direct Drive <br />Motor Manufacturer OEM <br />Rated Voltage 208 Volts <br />Rated Amperage 1.3 Amps <br />Phase 1 <br />Horsepower .41 HP <br />HVAC-01 /DOAS-02/SF-1 <br />Drive Type Direct Drive <br />Motor Manufacturer OEM <br />Rated Voltage 208 Volts <br />Rated Amperage 1.4 Amps <br />Phase 1 <br />Horsepower .42 HP <br />A rr-�% j <br />HVAC-01/DOAS-02 Supply Outlet - Constant Volume Summary <br />System/Unit <br />Type <br />Size <br />AK <br />Final (CFM) <br />%Final <br />Outlet-01 <br />CD <br />2408 <br />JILAIL- <br />190 <br />194 <br />102 <br />Outlet-02 <br />CD <br />2406 <br />20 <br />25 <br />125 <br />Outlet-03 <br />CD <br />2406 <br />15 <br />24 <br />160 <br />Outlet-04 <br />CD <br />2406 <br />20 <br />22 <br />110 <br />Outlet-05 <br />CD <br />2408 <br />120 <br />126 <br />105 <br />Outlet-06 <br />CD <br />2406 <br />20 <br />21 <br />105 <br />Outlet-07 <br />CD <br />2406 <br />20 <br />22 <br />110 <br />Outlet-08 <br />CD <br />2408 <br />110 <br />119 <br />108 <br />Outlet-09 <br />Totals: <br />SWG <br />2406 <br />- <br />15 <br />530 <br />32 <br />213 <br />110 <br />HVAC-01/DOAS-02 Exhaust Inlet - Constant Volume Summary <br />ACCO Engineered Systems <br />