Laserfiche WebLink
engineered <br />� I systems <br />HVAC Systems <br />PROJECT: Kimley Horn Everett DATE: 5/10/2023 <br />LOCATION: Everett, WA CONTACT: Steve Lybecker <br />PROJECT #: 60940287 <br />SYSTEM/UNIT: HVAC-01/FC-01 <br />Location Wall <br />Serves Server 216 <br />Manufacturer Mitsubishi <br />Model Number PKA-Al2LA <br />Serial Number 1XM03157 <br />Type of Unit 24/7 Cooling <br />Capacity 1.0 Tons <br />Voltage 208 Volts <br />Phase 1 <br />HVAC-01 /FC-01 /Filter <br />Filter 1 Type Washable <br />Filter 1 Rating OEM <br />Filter 1 Qty 2 <br />Filter 1 Size OEM <br />.. <br />HVAC-01 /FC-01 /Fan <br />Drive Type Direct Drive <br />Motor Manufacturer OEM <br />Rated Voltage 208 Volts <br />Rated Amperage 0.6 Amps <br />Phase 1 <br />Type TEFC <br />Design Motor RPM Fractional RPM <br />F � <br />SYSTEM/UNIT: HVAC-01/(E) 11-111-SM-01 <br />Unit ... <br />Location Ceiling LA3 <br />Serves Production <br />Manufacturer McQuay <br />r <br />O <br />Equipment Data <br />TAB By Kalani Rivera <br />TAB Date 05/08/2023 <br />Design Supply CFM <br />630 CFM <br />Actual Supply CFM <br />684 CFM <br />Design Return CFM <br />630 CFM <br />Actual Return CFM <br />684 CFM <br />Design Minimum Outside CFM <br />0 CFM <br />Actual Minimum Outside CFM <br />0 CFM <br />HVAC-01/(E) HPSM-01 Supply Outlet - Constant Volume Summary <br />System/Unit Type Size AK Design (CFM) Final (CFM) %Final <br />Totals: - - - 630 684 109 <br />ACCO Engineered Systems <br />