Laserfiche WebLink
HVAC Systems <br />PROJECT: Kimley Horn Everett <br />LOCATION: Everett, WA <br />PROJECT #: 60940287 <br />SYSTEM/UNIT: HVAC-01/HP 2-3 <br />Location <br />Serves <br />Manufacturer <br />Model Number <br />Serial Number <br />Capacity <br />Voltage <br />Phase <br />HVAC-01/HP 2-3/Filter <br />Filter 1 Type <br />Filter 1 Rating <br />Filter 1 Qty <br />Filter 1 Size <br />L,eumg wiz <br />Conf 204 <br />Climatemaster <br />TCH009AGD30CSBS <br />222611462 <br />3/4 Tons <br />208 Volts <br />1 <br />Pleated <br />MERV 8 <br />1 <br />10x18x1 <br />Drive Type <br />Direct Drive <br />Motor Manufacturer <br />OEM <br />Rated Voltage <br />208 Volts <br />Rated Amperage <br />0.8 Amps <br />Phase <br />1 <br />Type <br />ODP <br />Horsepower <br />Not Listed HP <br />HVAC-01/HP 2-3 Supply Outlet - Constant Vojume S <br />[elm.'9R] <br />L'A <br />engineered <br />� I systems <br />DATE: 5/10/2023 <br />CONTACT: Steve Lybecker <br />Equipment Tested Data <br />TAB By Kalani Rivera <br />TAB Date 05/03/2023 <br />Design Supply CFM <br />325 CFM <br />Actual Supply CFM <br />320 CFM <br />Design Return CFM <br />325 CFM <br />Actual Return CFM <br />320 CFM <br />Design Minimum Outside CFM <br />0 CFM <br />Actual Minimum Outside CFM <br />0 CFM <br />165 1 167 1 101 <br />ACCO Engineered Systems <br />