Laserfiche WebLink
HVAC Systems <br />PROJECT: Kimley Horn Everett <br />LOCATION: Everett, WA <br />PROJECT #: 60940287 <br />SYSTEM/UNIT: HVAC-01/(E) HPSM-06 <br />Unit Data <br />Location Ceiling LA3 <br />Serves Production <br />Manufacturer McQuay <br />engineered <br />systems <br />DATE: 5/10/2023 <br />CONTACT: Steve Lybecker <br />Equipment Data <br />TAB By Kalani Rivera <br />TAB Date 05/09/2023 <br />Design Supply CFM <br />630 CFM <br />Actual Supply CFM <br />685 CFM <br />Design Return CFM <br />630 CFM <br />Actual Return CFM <br />685 CFM <br />Design Minimum Outside CFM <br />0 CFM <br />Actual Minimum Outside CFM <br />0 CFM <br />HVAC-01/(E) HPSM-06 Supply Outlet - Constant Volume Summary <br />Outlet-01 <br />CD <br />2408 <br />165 <br />202 <br />122 <br />Outlet-02 <br />CD <br />2408 <br />155 <br />168 <br />108 <br />Outlet-03 <br />CD <br />2408 <br />155 <br />152 <br />98 <br />Outlet-04 <br />CD <br />2408 <br />155 <br />163 <br />105 <br />ACCO Engineered Systems <br />