• <br /> 4i0 <br /> Mr. Chad Georgell <br /> Rainier Structures, LLC <br /> Plan Check Number: C2006-007, First Building Review <br /> August 12, 2020 <br /> Structural <br /> 1. The foundation design for the proposed project should comply with the requirements of the <br /> 2015 International Building Code. The code should be specified in construction drawings. See <br /> the Everett Municipal Code Section 16.005.030 Article A and IBC Section 107.2.1. <br /> 2. The submitted documents do not include a project specific foundation design. Note that <br /> general requirements included in the manufacturer's published literature do n6t satisfy this <br /> required. A foundation plan and details should be included in the construction drawings. <br /> Structural calculations substantiating the foundation design, including the transfer of lateral <br /> forces (i.e., seismic and wind loads) to the foundation, should be submitted for review. See IBC <br /> Sections 1604.1, 1604.2, and 1604.4. <br /> 3. Structural and geotechnical special inspections may be required for this project where the <br /> design is performed per the IBC, including inspections for deep foundation elements (i.e., soil <br /> anchors). The statement should include a table listing each type of special inspection and the <br /> extent of each inspection (e.g., continuous, periodic) per IBC Section 1704.3.1. The table <br /> should include special requirements for seismic and wind resisting systems as required by IBC <br /> Sections 1704.3.2 and 1704.3.3, respectively. See IBC Sections 107.1, 1704.2.3 and 1704.3. <br /> 4. The submitted documentation does not include a geotechnical report providing criteria for use <br /> in the design of the foundation. A geotechnical evaluation should be performed and a report <br /> provided for review. Alternatively, the presumptive design criteria for use in the design should <br /> be established. In either case, the design criteria should be stated in the construction <br /> drawings. Note that the presumptive criteria must be verified by special inspection testing <br /> during construction; failure to meet the criteria may require modifications to the design during <br /> construction to satisfy the design requirements. See IBC Sections 1803.1 and 1803.6. <br /> This review has been performed for general compliance with the building codes as adopted and <br /> amended by the state of Washington and the city of Everett. Corrections and comments made <br /> during the review process do not relieve the project from compliance with code and permit <br /> requirements. The designers-of-record are responsible for a complete design in accordance with <br /> the laws of the state of Washington. <br /> If you have any questions or require additional clarification, please contact us. <br /> Respectfully, <br /> Drew Martin, P.E., S.E. <br /> Associate Engineer/ Commercial Plans Examiner <br /> (425)257-8813 <br /> dmartin@everettwa.gov <br /> O3200 Cedar Street © 425.257.8810 O everetteps@everettwa.gov <br /> Everett,WA 98201 425.257.8857 fax everettwa.gov/permits <br /> ' Page 3 of 3 <br />