ABBREVIATIONS PLAN SYMBOLS GENERAL HVAC NOTES b <br /> e, s yb' � 6U a <br /> 10490 7 q ' f g' , q g 10420 \ L Z 3 <br /> OJ DIAMETER MCA MINIMUM CIRCUIT AMPACITY E CEILING SUPPLY DIFFUSER 1. COMPLETE INSTALLATION OF MECHANICAL SYSTEMS -JJJ iii +++ 111 �9 - w <br /> MECH MECHANICAL SHALL MEET APPLICABLE CODES PER 2018 IBC WITH I, J <br /> AFF ABOVE FINISHED FLOOR MIN MINIMUM E CEILING RETURN GRILLE f °s°z O Z <br /> AHU AIR HANDLING UNIT MOCP MAXIMUM OVERCURRENT PROTECTION WASHINGTON STATE AMENDMENTS, 2018 IMC WITH a e e �J z,o O O <br /> ® CEILING EXHAUST GRILLE <br /> WASHINGTON STATE AMENDMENTS,&2018 IECC. U 2 <br /> ' ` <br /> BHP BRAKE HORSEPOWER <br /> IN NOISE CRITERIA /V\/\/ FLEX DUCT 2. EQUIPMENT INSTALLATION INSTRUCTIONS TO BE ON SITE 10505 V <br /> BDD BACKDRAFT DAMPER NOM NOMINAL FOR INSPECTORS. 81d zoor <br /> BPD BY-PASS DAMPER NO. NUMBER �4 CEILING EXHAUST FAN ' ' I �7 <br /> +z oso 1 1 1 zLo <br /> BTU/H BRITISH THERMAL UNIT PER HOUR N 3. DUCT INSULATION AND SEALING TO MEET REQUIREMENTS <br /> TS NOT TO SCALE ® INLINE EXHAUST FAN 051ROOFTOP UNIT <br /> C CONDENSATE DRAIN PIPING OF SEC C403.10.1 OF THE 2018 WSEC. x <br /> CD CEILING DIFFUSER OA OUTSIDE AIR EXHAUST FAN UP 4. SYSTEM CONTROLS TO MEET ALL APPLICABLE SECTIONS zoo0 a m <br /> CFM CUBIC FEET PER MINUTE OBD OPPOSED BLADE DAMPER UNDER SEC C403.4 OF 2018 WSEC. w �- 1051h = O <br /> ODD OUTSIDE DIMENSION OF DIAMETER O ROUND DUCT UP u <br /> DB DECIBAL OU OUTDOOR UNIT 5. THERMOSTATS SHALL BE SET TO MAINTAIN A MINIMUM <br /> 052 <br /> ROUND DUCT DOWN 0 m <br /> DH DUCT HEATER DEADBAND OF 5°F PER WSEC C403.4.1.2. > 20+0 202° <br /> DOAS DEDICATED OUTDOOR AIR SYSTEM POC POINT OF CONNECTION VAV FAN BOX 6. CONTROLS TO BE EQUIPPED WITH AUTOMATIC TIME " <br /> PSI POUNDS PER SQUARE INCH BALANCE DAMPER(MANUAL) CLOCK CAPABLE OF STARTING AND STOPPING THE os3o <br /> EER ENERGY EFFICIENCY RATIO DStd oso <br /> EG EXHAUST GRILLE R REFRIGERATION LINES __l FD FIRE DAMPER SYSTEM WITH MANUAL OVERRIDE PER WSEC C403.4.2.2 <br /> ESP EXTERNAL STATIC PRESSURE RA RETURN AIR 7. OUTDOOR AIR SUPPLY,EXHAUST OPENING,RELIEFS TO BE ofi 91s �5 931 <br /> �FSD FIRE SMOKE DAMPER zoor 0z zo3+ <br /> EXH EXHAUST RCP REFLECTED CEILING PLAN PROVIDED WITH CLASS 1 MOTORIZED DAMPER AND CLOSE <br /> RG RETURN GRILLE M-1 MOTORIZED DAMPER DURING UNOCCUPIED EQUIPMENT OPERATION PER WSEC 1a6e s+ <br /> FCU FAN COIL UNIT RPM REVOLUTIONS PER MINUTE C403.7.8.1. IF GRAVITY DAMPER, IT SHALL HAVE AN AIR <br /> FD FIRE DAMPER RTU ROOFTOP UNIT ® ZONE DAMPER 1061h PI SE <br /> FPM FEET PER MINUTE LEAKAGE RATE NOT GREATER THAN 20 CFM/FT^2. <br /> FSD FIRE AND SMOKE DAMPER SD SUPPLY DIFFUSER FIRE DAMPER ABOVE DIFFUSER 8, VENTILATION BY MECHANICAL OR NATURAL MEANS <br /> SL SOUND LINED063 aez 20 2090 <br /> FIRE DAMPER ABOVE GRILLE SHALL BE NO GREATER THAN 150 PERCENT OF THE <br /> GF GAS FURNACE SP STATIC PRESSURE MINIMUM OA REQUIRED PER WSEC C403.2.2. �J <br /> GRD GRILLE,REGISTER,DIFFUSER SM/D SMOKE DAMPER Q THERMOSTAT 9. ALL ECONOMIZERS PROVIDED SHALL MEET SEC C403.5 OF e,r azs <br /> HP HORSEPOWER,HEAT PUMP TG TRANSFER GRILLE Q SENSOR 2018 WSEC AND BE ABLE TO PROVIDE UP TO 100 PERCENT A PROPERTY SITE <br /> HRU HEAT RECOVERY UNIT T'STAT THERMOSTAT GAS METER OSA FOR COOLING PER WSEC C403.5.3.1. <br /> HVAC HEATING VENTILATION&AIR CONDITIONING TYP TYPICAL 10. SMOKE DETECTORS INSTALLED IN MAIN RETURN PER SEC _. <br /> sM SMOKE DETECTOR TENANT: ALLIED TELESIS <br /> ID INSIDE DIMENSION VAV VARIABLE AIR VOLUME 606 OF THE 2018 IMC. <br /> SD-# SUPPLY DIFFUSER 11. ALL HVAC EQUIPMENT TO BE LABELED FOR THE SPACE ° v - <br /> IECC INTERNATIONAL ENERGY CONSERVATION CODE VFD VARIABLE FREQUENCY DRIVE LAND OWNER: ALLIED TELESIS INC. <br /> IFR INFRARED HEATER VTR VENT TO ROOF RG-# RETURN GRILLE SERVED. go- <br /> IMC INTERNATIONAL MECHANICAL CODE 12. DUCTS TO BE SUPPORTED AT EACH CHANGE IN PARCEL NO. 28052000203000 _..°. <br /> IN INCH WSEC WASHINGTON STATE ENERGY CODE EF-# EXHAUST FAN DIRECTION,VERTICAL AT 12'-0"MAX,HORIZONTAL AT 10'-0" <br /> ISP INTERNAL STATIC PRESSURE SITE AREA: 1.01 ACRES BUILDING AREA 15,000 SF <br /> ZD ZONE DAMPER TG-# TRANSFER GRILLE MAX WITH STRAP,OR 8'-0"MAX FROM TRAPEZE SUPPORT "0 I <br /> LB POUND C- CONDENSATE LINE 13. ALL SUPPLY GRILLES TO HAVE MANUAL VOLUME DAMPERS USE CODE: 559 OTHER RETAIL TRADE-AUTO,MARINE,AIRCRAFT NEC <br /> LVR LOUVER FOR BALANCING OF SYSTEM UPON COMPLETION. A VICINITY MAP <br /> -R- PAIRED REFER LINES 14. ALL PIPING TO BE INSULATED ACCORDING TO SECTION <br /> PROPERTY DESCRIPTION: <br /> C403.10.3 OF 2018 WSEC. SEC 20 TWP 28 RGE 05 QTR NW-(COMB FOR TAX PURP ONLY)-W 260 FT S1/2 S1/2 N1/2 SW1/4 NWI/4 LESS S 30FT THOF <br /> 15. FRESH AIR INTAKE AND RELIEF/EXHAUST WILL BE &LESS W 30FT FOR RD&ALSO LESS E LOFT OF W 40FT AS ADD RD R/W PER WD TO CITY OF EVT RECIN VOL 1539 PG 79 <br /> EQUIPPED WITH A LOW LEAK, CLASS 1A MOTORIZED AUDS FILE NO 7906180188 TGW W 260 FT OF FDT S 30 FT N1/2 SW1/4 NWI/4&N 20 FT S1/2 SWI/4 NW1/4 EXC W 30FT FOR <br /> DAMPER THAT AUTOMATICALLY CLOSES DURING RD&EXC E 10FT OF W 40FT FOR ADD RD R/W TO CITY OF EVT PER WD REC INVOL 1539 PG 79 AUDS FILE NO 7906180188 <br /> PER OWNER'S REQ DATED 5/12/09 <br /> UNOCCUPIED HOURS TO COMPLY WITH SEC C403.7.8.1 OF <br /> 2018 WSEC SCOPE OF WORK: U) <br /> 16. GAS PIPING TO BE INSTALLED IN ACCORDANCE WITH THE 1. PROVIDE AND SUPPLY 21 AIR HANDLER HEADS CONNECTED TO A VRF ROOFTOP SYSTEM. <br /> 2018 IFGC TABLE C404.6 WHEN APPLICABLE. 2. PROVIDE AND INSTALL 2 DOAS SYSTEMS WITH DUCTWORK TO PROVIDE REQ'D VENTILATION. U) <br /> 3. PROVIDE AND INSTALL DUCTWORK FOR FIRST FLOOR FUTURE USE. <br /> 17. All EQUIPMENT SPECIFIED THE SMALLEST SIZE THAT 4, PROVIDE NECESSARY SUBMITTALS, PERMITS, O&M DUCUMENTS, EQUIPMENT START UP AND TEST,AND AIR LJJ <br /> EXCEEDS THE CALCULATED LOADS PER WSEC C403.3.1. BALANCE REPORT UPON COMPLETION. J <br /> 18. HVAC INSTALLATION SHALL BE COMPLETE WHEN ALL <br /> SECTIONS OF 408 IN 2018 WSEC HAVE BEEN SATISFIED, ui <br /> INCLUDING AS-BUILT DRAWINGS, SUBMITTALS, O&M SHEET INDEX p <br /> MANUALS, BALANCE REPORT, AND COMMISSIONING N <br /> REPORT. M0.0 GENERAL NOTES&INFORMATION Q j a <br /> 19. FLEXIBLE INSULATED DUCTS SHALL BE MAXIMUM 5'0" M1.0 FIRST&SECOND FLOOR MECHANICAL PLAN Q Q <br /> M2.0 FIRST&SECOND FLOOR PIPING DIAGRAMS _c >j <br /> LONG AND STALL MEET INSTALLATION AND MATERIAL M3.0 ROOF LEVEL MECHANICAL PLAN <br /> REQUIREMENTS OF LOCAL CODES. M3.0 SCHEDULES&ELEVATIONS JI <br /> 20. ALL BRANCH TAKE-OFFS SHALL BE PROVIDED WITH J c' <br /> OJ <br /> MANUAL BALANCING DAMPERS. Q p W <br /> z <br /> U w <br /> Z <br /> Ou <br /> 0 n <br /> Lu <br /> N <br /> N <br /> z O O <br /> QN N1 <br /> d � N <br /> J <br /> u Ld <br /> H <br /> Z a Q m <br /> Z <br /> xL2 3: <br /> U Z <br /> W <br /> :2LLJ <br /> n a <br /> LL <br /> m0.0 <br />