-COFFMAN <br /> ENGINEERS <br /> GENERAL NOTES LIGHTING REQUIREMENTS ONE-LINE DIAGRAM 1101 2nd Avenue,Suite 400 <br /> Seattle,WA 98101 <br /> THE FOLLOWING GENERAL NOTES APPLY TO ALL DRAWINGS THE FOLLOWING GENERAL NOTES APPLY TO ALL LIGHTING PLAN DRAWINGS 1. PROVIDE PULL BOXES AS REQUIRED BY THE NEC. <br /> 1. ITEMS NOTED AS"TYPICAL"ON ANY DRAWING REFERS TO ALL 1. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS AND ELEVATIONS 2. SHORT CIRCUIT CURRENTS LESS THAN 10,000 ASYM FOR 208V PANELS AND ph 206.623.0777 <br /> DRAWINGS. FOR EXACT LOCATION OF LUMINAIRES. 14,000 ASYM FOR 480V PANELS ARE NOT SHOWN. <br /> 2. PROVIDE NYLON PULL STRING IN ALL EMPTY RACEWAYS. 2. WHERE THERE IS A CONFLICT ARCHITECTURAL PLANS SHALL GOVERN. 4. THE ONE-LINE DIAGRAM IS DIAGRAMMATIC AND DOES NOT SHOW THE ACTUAL www.coffman.com <br /> ROUTING OF THE RACEWAYS. <br /> 3. NO STRUCTURAL MEMBERS SHALL BE CUT OR ALTERED WITHOUT PRIOR 3. COORDINATE THE FINAL LOCATION OF LUMINAIRES IN MECHANICAL <br /> APPROVAL OF THE ARCHITECT AND STRUCTURAL ENGINEER. ROOMS AND ATTIC SPACES TO AVOID CONFLICTS WITH DUCT WORK, 5. FOR TWO SECTION PANELS PROVIDE FULL SIZE FEEDER CONNECTIONS FROM <br /> PIPING,AND MECHANICAL EQUIPMENT. SECTION 1 TO SECTION 2. <br /> 4. LOCATIONS OF ALL WALL MOUNTED DEVICES ARE SHOWN <br /> SCHEMATICALLY. COORDINATE WITH THE ARCHITECTURAL DRAWINGS, 4. ROUTE ALL EXTERIOR LIGHTING CIRCUITS VIA LIGHTING CONTROL PANEL 6. NOT ALL CIRCUIT BREAKERS ARE SHOWN. REFER TO PANEL AND <br /> ELEVATIONS AND CASEWORK SUPPLIERS SHOP DRAWINGS FOR EXACT SWITCHBOARD SCHEDULES FOR OTHER LOADS SERVED,AND SPARE CIRCUIT <br /> LOCATION OF DEVICES PRIOR TO ROUGH-IN. 5. INSTALL AND WIRE REMOTE DRIVERS. REFER TO LUMINAIRE SCHEDULE. BREAKERS. <br /> MOUNT IN ACCESSIBLE LOCATIONS. SHOW LOCATIONS ON THE <br /> 5. PROVIDE EMT SLEEVES FOR LOW VOLTAGE WIRING RUNNING THROUGH AS-BUILT DRAWINGS. 7. CONTRACTOR TO PROVIDE COORDINATION AND ARC FLASH STUDY. ALL <br /> D <br /> NON-RATED WALLS,FLOORS AND CEILINGS. DISTRIBUTION SYSTEM EQUIPMENT SHALL BE RATED FOR THE AVAILABLE (i <br /> FAULT CURRENT AND SHALL BE LABELED WITH THE ARC FLASH HAZARD <br /> 6. PROVIDE SLEEVES WITH APPROVED FIRE STOPPING AT EACH LOCATION CATEGORY AND AVAILABLE FAULT CURRENT. ALL NEC 700 AND 701 <br /> WHERE LOW VOLTAGE WIRING PENETRATES A RATED WALL OR CEILING. PORTIONS OF THE DISTRIBUTION SYSTEM SHAT BE SELECTIVELY <br /> 7. SEAL ALL PENETRATIONS IN RATED FLOORS AND CEILINGS WITH A UL <br /> POWER REQUIREMENTS COORDINATED. <br /> APPROVED FIRE STOP SYSTEM. 8. PROVIDE GROUNDING AND BONDING OF ELECTRICAL POWER DISTRIBUTION <br /> 8. ALL LOW VOLTAGE WIRING NOT RUN IN A METALC RACEWAY SHALL <br /> THE FOLLOWING GENERAL NOTES APPLY TO ALL POWER PLAN DRAWINGS EQUIPMENT PER NEC ARTICLE 250. ALLIED <br /> BE PLENUM RATED. 1. CIRCUIT ALL FIRE/SMOKE DAMPERS AND SMOKE DAMPERS FROM <br /> 9. MOUNT ALL DEVICES ABOVE COUNTERS 6"ABOVE BACKSPLASH UNLESS NEAREST 120V EMERGENCY PANEL WITH Xt"-3$12. UTILIZE SPARE TELESIS <br /> NOTED OTHERWISE. 20A-lP BREAKER PROVIDED. RECORD CIRCUITING ON AS-BUILT PANEL <br /> SCHEDULES AND DRAWINGS. REFER TO MECHANICAL DRAWINGS FOR BRANCH CIRCUIT WIRING <br /> 10. ALL CONTROLLED RECEPTACLES SHALL BE PERMANENTLY LABELED AS DAMPER LOCATIONS. <br /> REQUIRED TO BY THE NEC. 2. COORDINATE LOCATIONS OF BAS CONTROL POWER WITH THE CONTROLS THE FOLLOWING GENERAL NOTES APPLY TO AL DRAWINGS Silver Plaza <br /> 11. REFER TO ARCHITECTURAL DRAWINGS FOR DEVICE MOUNTING HEIGHTS. CONTRACTOR PRIOR TO ROUGH-IN. 1. SHOW ALL RACEWAYS AND WIRING ON AS-BUILT DRAWINGS. Floor 2 <br /> 3. PRIOR TO ORDERING EQUIPMENT OR ROUGH-IN,COORDINATE WITH THE 2. MINIMUM RACEWAY SIZE SHAT BE ". <br /> MECHANICAL CONTRACTOR TO ESTABLISH THE ACTUAL LOAD AND <br /> OVERCURRENT PROTECTION REQUIREMENTS FOR EACH PIECE OF 3. NO MORE THAN 7$12 AWG CONDUCTORS SHALL BE INSTATED IN A 10521 19th Ave SE <br /> DOOR HARDWARE EQUIPMENT. <br /> RACEWAY. Everett, WA 98202 <br /> 4. Al RECEPTACLES WITHIN 6 FEET OF A SINK SHALL BE GFCI TYPE. 4. HOMERUNS GREATER THAN 75 FEET TO THE FIRST DEVICE SHAT BE N0. <br /> 1. PROVIDE ALL RACEWAYS AND WIRING REQUIRED TO INSTALL ELECTRONIC 5. PROVIDE 120-4 HARDWIRED CONNECTION TO EACH TRAP PRIMER FROM 10 AWG. <br /> DOOR HARDWARE. REFER TO DOOR HARDWARE SPECIFICATIONS, NEAREST ADJACENT GENERAL RECEPTACLE CIRCUIT UTILIZING)¢°- <br /> SCHEDULES AND DIAGRAMS. 3#12. REFER TO MECHANICAL DRAWINGS FOR LOCATIONS. RECORD 5. PROVIDE A GROUND CONDUCTOR IN ALL RACEWAYS. Construction Set <br /> CIRCUITING ON AS-BUILT PANEL SCHEDULES AND DRAWINGS. 6. PROVIDE A DEDICATED NEUTRAL CONDUCTOR FOR EACH BRANCH CIRCUIT. <br /> Revisions <br /> LIGHTING CONTROL PANELS (LCP) 7. PROVIDE CONDUCTORS AS REQUIRED TO PROVIDE CIRCUITING AND <br /> SWITCHING DUTY AS SHOWN ON THE DRAWINGS. <br /> 1. DOWNSTREAM OF A PANELBOARD WITH AN AC RATING OF 14,000 ASYM 8. FOR OTHER THAN 15 OR 20 AMP SINGLE PHASE RECEPTACLE BRANCH <br /> OR LESS: LOCATE LCP A MINIMUM OF 2'-0"FROM THE PANELBOARD. CIRCUITS PROVIDE A DEDICATED HOMERUN TO THE PANEL. <br /> 2. DOWNSTREAM OF A PANELBOARD WITH AN AC RATING GREATER THAN 9. FOR 30 AAP BRANCH CIRCUITS PROVIDE#10 AWG CONDUCTORS. <br /> 14,000 ASYM: LOCATE A LCP A MINIMUM OF 10'-0'FROM THE <br /> PANELBOARD. 10. FOR 40 AMP AND LARGER BRANCH CIRCUITS PROVIDE RACEWAYS AND <br /> WIRING AS SHOWN ON THE DRAWINGS. <br /> 11. GENERAL, <br /> 11.A. 120V BRANCH CIRCUIT HOMERUNS GREATER THAN 90 FEET TO THE <br /> FIRST DEVICE SHALL HAVE CONDUCTORS INCREASED ONE GAUGE SIZE <br /> WASHINGTON STATE NONRESIDENTIAL FOR EVERY 60'OF LENGTH. <br /> 11.B. 208V BRANCH CIRCUIT HOMERUNS GREATER THAN 125 FEET TO THE <br /> ENERGY CODE COMPLIANCE FIRST DEVICE SHALL HAVE CONDUCTORS INCREASED ONE GAUGE SIZE <br /> FOR EVERY 75'OF LENGTH. <br /> 11.C. 277V BRANCH CIRCUIT HOMERUNS GREATER THAN 175 FEET TO THE <br /> 1. LIGHTING: THE CONTRACTOR SHALL PROVIDE A WRITTEN CERTIFICATION FIRST DEVICE SHALL HAVE CONDUCTORS INCREASED ONE GAUGE SIZE <br /> VERIFYING THAT ALL LAMPS AND BALLASTS HAVE BEEN PROVIDED PER THE FOR EVERY 100'OF LENGTH. <br /> SPECIFICATIONS. PROVIDE A LIST WHICH INDICATES THE EXACT PART 11.D. 480V BRANCH CIRCUIT HOMERUNS GREATER THAN 300 FEET TO THE <br /> NUMBER OF THE LAMP AND BALLAST PROVIDED FOR EACH FIXTURE TYPE. FIRST DEVICE SHAT HAVE CONDUCTORS INCREASED ONE GAUGE SIZE <br /> INCLUDE THE CERTIFICATION AND THE LAMP/BALLAST LIST IN THE 0&M FOR EVERY 200'OF LENGTH. <br /> MANUAL 11.E. LIGHTING,POWER AND MECHANICAL EQUIPMENT CONDUCTORS SHAT Registration <br /> NOT BE COMBINED IN THE SAME RACEWAY. <br /> 2. COMMISSIONING REQUIREMENTS:ALL LIGHTING CONTROLS INCLUDING 11.F. PROVIDE A GROUND CONDUCTOR IN ALL RACEWAYS. <br /> DAYLIGHT OR OCCUPANT SENSING AUTOMATIC CONTROLS,AUTOMATIC SHUT BST <br /> OFF CONTROLS,OCCUPANCY SENSORS OR AUTOMATIC TIME SWITCHES,THE WASNf <br /> LIGHTING CONTROLS SHALL BE TESTED TO ENSURE THAT CONTROL DEVICES, <br /> COMPONENTS,EQUIPMENT AND SYSTEMS ARE CALIBRATED,ADJUSTED AND <br /> OPERATE IN ACCORDANCE WITH APPROVED PLANS AND SPECIFICATIONS. - t. <br /> SEQUENCE OF OPERATIONS SHALL BE FUNCTIONALLY TESTED TO ENSURE h <br /> THEY OPERATE IN ACCORDANCE WITH APPROVED PLANS AND SPECIFICATIONS. 45932 <br /> THE CONTRACTOR SHAT PROVIDE A WRITTEN STATEMENT CERTIFYING ALL ion.`P6CISR.ytg� <br /> LIGHTING CONTROLS HAVE BEEN COMMISSIONED. INCLUDE CERTIFICATION IN `s`70NAL <br /> O&M MANUAL. <br /> 3012023 <br /> 3. TRANSFORMERS: THE MINIMUM EFFICIENCY OF Al LOW VOLTAGE DRY-TYPE <br /> DISTRIBUTION TRANSFORMERS SHALL BE THE CLASS 1 EFFICIENCY LEVELS <br /> FOR DISTRIBUTION TRANSFORMERS SPECIFIED IN TABLE 4-2 OF THE"GUIDE Key Plan <br /> FOR DETERMINING ENERGY EFFICIENCY FOR DISTRIBUTION TRANSFORMERS' <br /> PUBLISHED BY THE NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION <br /> (NEMA Ti LATEST EDITION). <br /> GENERALNOTES <br /> Scale: NONE <br /> CEI Project No: 230312 <br /> Date: 3.7.2023 <br /> Designed: J. MAXWELL <br /> Drawn: R. FROGGE <br /> Checked: B. MAXWELL <br /> Sheet Number <br /> E-0 .2 <br />